The communication parameter can be set as "8n1", "8o1", "8e1".
Parity: n (no parity), o (odd parity), e (even parity)
Data bits: 8 Stop bit: 1
After the setting, please press "V/A" to confirm and enter the next setting interface.
Serial Port 0 Setting Interfaces
(5) Voltage Connection Method Setting
“UL” interfaces is the setting interfaces of voltage wiring mode, and we can see the voltage
wiring mode of the energy meter in this interfaces
There are 3 kinds of voltage connection methods optional as follows (by pressing button P
or E to choose):
3Ln (Three-phase four-wire 3PT connection)
2Ln (Three-phase four-wire 2PT star (Y) connection)
2LL (Three-Phase Three-Line open delta (Δ) connection)
After the setting, please press "V/A" to confirm and enter the next setting interface.
Voltage Wiring Mode
(6) Current Connection Method Setting
“IL” is the current wiring mode setting interfaces, we can see the connection mode of the
meter in this interfaces.
There are 3 kinds of voltage connection methods optional as follows (by pressing button P
or E to choose):
3C (with 3 CTs)
2C (This mode of connection is used for the balanced three-phase circuits, and it’s capable
to calculate Ib according to "Kirchhoff's laws". The current input mode of the meter should
be set to 2C)
1C (this mode of connection is used for the balanced three-phase circuits, and we only
need to measure Ia, Ia=Ib=Ic )
After the setting, please press "V/A" to confirm and enter the next setting interface.
7)PT & CT Ratio
The setting range is 1~9999.