Temperature manager
16
If the required buffer-top-temperature (required temperature) is higher than the sum of buffer-bottom-MUST-
temperature and the set difference, then the required boiler temperature is the result of the required buffer-
top-temperature (required temperature) + the adjusted temp. increase (see Figure 8.2).Caution: Consider the
set minimum requirement
.
Figure 8.2: Example temperature manager with buffer and without difference
If the required buffer-top-temperature (required temperature) is lower than the buffer-bottom-MUST-
temperature than the required boiler temperature is the result of the required buffer-bottom-temperature +
the adjusted temp. in the adjusted difference (see Figure 8.3). Caution: Consider the set minimum
requirement.
Figure 8.3: Example temperature manager with buffer and difference