Fault reports and their corrections
10
75
10.1
Not indicated faults
Fault
Cause of fault
Fault correction
Boiler output
gradually decreases
Ash/slag on the grate; fly ash container is
full; heat exchanger heavily clogged/ sooted;
inferior quality fuel
Reduce cleaning intervals or clean
manually; empty the fly ash container;
clean heat exchanger
Desired operating
temperature is not
reached
Inferior quality fuel;
previous boiler output higher than current
boiler output;
fuel level too low
Replace fuel if necessary, install larger
boiler; increase fuel level
Ash is emitted from
the chimney
Fly ash container full; fuel contains of
excessive finds or super fines; fan speed too
high; chimney draught to high
Remove fly ash; replace fuel if
necessary or retrofit flue gas de duster;
reduce speeds; retrofit chimney
draught regulator
Deflagrations
Fuel to dry
Fuel to fine
Use fuel according to specifications
Flue gas outlet on
the boiler or exhaust
pipe
•
Incorrect layout / double occupancy of the
chimney
•
Leaks (defective seals on doors, ash box,
exhaust pipe ...)
•
Maintenance interval exceeded, soot
build-up, soiling, sooting in the boiler or
exhaust pipe
•
Burning chamber door opened
•
Unfavourable draft conditions, lack of air,
low delivery pressure;
•
Deflagration, unsuitable fuel
•
Design of the chimney according to
the specifications of the assembly /
installation instructions
•
Check seals and have defective /
damaged ones replaced by a
specialist.
•
Perform maintenance, clean boiler
or flue gas line.
•
Only open the combustion chamber
door in the cases recommended
according to the instructions.
•
Check air regulation
•
Use fuel according to specifications
Flue gas outlet on
the boiler or exhaust
pipe
automatically loaded
system
•
Too much fuel in the combustion chamber
•
Check and adjust timing of the slide
Содержание BioFire 1000
Страница 1: ...OPERATING INSTRUCTIONS Wood chips pellets heating system BioFire 500 600 800 1000 1250 1500 ...
Страница 18: ...8 Temperature manager 18 Figure 8 6 Example temperature manager when time mode without difference ...
Страница 89: ...Annex 14 89 14 ANNEX 14 1 Additional boiler module Hydraulic recommendation 1 ...
Страница 90: ...14 Annex 90 Hydraulic recommendation 2 ...
Страница 91: ...Annex 14 91 14 2 Solar module Program 1 ...
Страница 92: ...14 Annex 92 Program 2 ...
Страница 93: ...Annex 14 93 Program 3 ...
Страница 94: ...14 Annex 94 Program 4 ...
Страница 95: ...Annex 14 95 Program 5 ...
Страница 96: ...14 Annex 96 Program 6 ...
Страница 97: ...Notes 15 97 15 NOTES ...