24
for the technician
First firing, regulation and servicing instructions
Parameter numbers, description, available values and default settings:
1 Gas type: Natural gas = 0 / LPG = 1. Default setting: 0. See “GAS transformation” for the
complete regulation procedure.
2 Temperature range for heating system: Normal = 0 / Reduced = 1. Default setting: 0.
Leave default setting unchanged.
3 Gas pressure* during slow opening: from 00 to 99. See ‘Slow opening regulation’ for
default setting (they may be different depending on boiler model and/or gas type) and for
complete regulation procedure.
4 Maximum heating power gas pressure*: from 00 to 99. Default setting: 99. See ‘Maximum
heating power regulation’ for the complete regulation procedure.
* = All values shown on to display are NOT gas pressure values and must be considered
for indication only. All correct gas pressure values must be verified through a micro
manometer correctly calibrated
5 Pump working in Winter mode: Normal = 0; Always on = 1; Always off = 2. Default
setting: 0. See ‘Other boiler programming’ for more info.
6 Switching on delay after reaching set heating temperature: from 0 to 7 minutes. Default
setting: 3. See ‘Other boiler programming’ for more info.
7 Temperature difference between heating flow and domestic set: from 10 to 20 °C.
Default setting: 15°C. We advice to leave default setting unchanged.
8 Minitank temperature setting according to dhw temperature setting: 0, 1, 2 and 3.
Default setting: 0. See “Other boiler programming” for more info.
Parameters 7 and 8 allow to optimise comfort level of the domestic hot water system,
according to water hardness. It is recommended to keep these values to default setting,
especially in case of hard water, unless a suitable scale reducing device is fitted.
9 Ignition delay for motorised mixing valve calibration: Activated = 0 - Excluded = 1.
Default setting: 0. See ‘Other boiler programming’ for more info.
It is MANDATORY that parameter n° 9 is set = 0 for normal boiler functioning.
10 External probe indication (not modifiable): No probe / disconnected = 0; Probe detected
= 1. See ‘Other boiler programming’ for more info.