background image

Page 2

Heritage Medcall   Sentry Emergency Call System

Model 560B Smoke Detector

Installation and Service Instructions

430-560B   0305    ©Heritage MedCall, Inc.

Issue 1, March 2005

upper level, or in both locations.  The basement
smoke alarm should be installed in close proximity to
the stairway leading to the floor above.  Where
installed on an open-joisted ceiling, the alarm should
be placed on the bottom of the joists.  The alarm
should be positioned relative to the stairway to
intercept smoke coming from a fire in the basement
before the smoke enters the stairway.

Where to Locate the Required Smoke Alarms in
Existing Construction

All of the smoke alarms specified for existing con-
struction are required and, in addition, a smoke alarm
is required in each bedroom.

Are More Smoke Alarms Desirable?

The required number of smoke alarms might not
provide reliable early warning protection for those
areas separated by a door from the areas protected
by the required smoke alarms.  For this reason, it is
recommended that the (designer/installer) consider
the use of additional smoke alarms for those areas for
increased protection.  The additional areas include the
basement, bedrooms, dining room, furnace room,
utility room, and hallways not protected by the
required smoke alarms.  The installation of smoke
alarms in kitchens, attics (finished or unfinished), or
garages is not normally recommended, as these
locations occasionally experience conditions that can
result in improper operation.

IMPORTANT!

REGULATIONS PERTAINING TO SMOKE

DETECTOR INSTALLATIONS VARY FROM STATE

TO STATE.  FOR MORE INFORMATION, CONTACT

YOUR LOCAL FIRE DEPARTMENT OR LOCAL

AUTHORITY HAVING JURISDICTION.

In addition to NFPA 72, use the following location
guidelines to optimize performance and reduce the
chance of false alarms.

Locate ceiling mounted smoke detectors in the center
of a room or hallway at least 4 inches from any walls
or partitions.

Locate wall mounted smoke detectors so the top of
the alarm is 4 to 12 inches below the ceiling.

When more than one detector is required, spacing of
30 feet may be used as a guide on smooth ceilings.
Other spacing may be used depending on ceiling

height, high air movement, and other conditions or
response requirements.

Locate in a suitable environment:

-Temperature between 32°F (0°C) and 100°F (38°C)

-Humidity between 0 and 95% non-condensing

Locate away from air conditioners, heating registers
and any other ventilating source that may interfere
with smoke entering the detector. Locate away from
kitchens, wood stoves, garages, furnaces and
bathrooms.

Mount smoke detectors on a firm permanent surface,
typically a stud or metal runner.

Additional information on Household Fire Warning is
available at nominal cost from: The National Fire
Protection Association, 1 Batterymarch Park, Quincy,
MA 02169-7471 or www.nfpa.org.  Request the latest
Standard No. NFPA 72.

FIGURE 2 DETECTOR PLACEMENT

PENDANT RECEIVER OPTION

The Model HM-547 Pendant Receiver is sometimes
used in apartment installations to receive a call signal
from a handheld wireless pendant. The location of a
smoke detector towards the center of the living area
within an apartment makes a good location to install

Содержание HM-560B

Страница 1: ...Sentry E Call Model HM 560B Photoelectric Smoke Detector Issue 1 March 2005 430 560B 0305 Heritage MedCall Inc Heritage MedCall...

Страница 2: ...aily and upon power up the detector performs a full diagnostic test that includes a dynamic test of the sensing chamber and internal electronics This meets NFPA 72 field sensitivity testing requiremen...

Страница 3: ...EGULATIONS PERTAINING TO SMOKE DETECTOR INSTALLATIONS VARY FROM STATE TO STATE FOR MORE INFORMATION CONTACT YOUR LOCAL FIRE DEPARTMENT OR LOCAL AUTHORITY HAVING JURISDICTION In addition to NFPA 72 use...

Страница 4: ...alled so when a detector is disconnected for any reason the end of line resistor or device must become disconnected A break in the detector power circuit or contact circuit will cause a trouble annunc...

Страница 5: ...low the directions on the can B Hold a smoldering punk or cotton wick close to the unit and gently direct the smoke into the smoke entry openings for 20 seconds or until an alarm is indicated Be sure...

Страница 6: ...eaning is necessary follow these steps 1 Open the detector cover unsnap and throw away the optical block chamber See Figure 6 2 Thoroughly blow off the optical base and snap a new optical block chambe...

Страница 7: ...apartment Check for detector operation as described in SMOKE TEST at each detector Normal Operation will sound the horn after applying smoke for 20 seconds NOTE When multiple smoke detectors are prese...

Страница 8: ...Heritage Medcall Sentry Emergency Call System Model 560B Smoke Detector Installation and Service Instructions 460 560B 0305 Heritage MedCall Inc FIGURE 7 SINGLE SMOKE DETECTOR WIRING FIGURE 8 MULTIPL...

Отзывы: