Page 5

Issue 1, March 2005

Heritage Medcall   Sentry Emergency Call System

Model 560B Smoke Detector

Installation and Service Instructions

460-560B   0305    ©Heritage MedCall, Inc.

FIGURE 5 SENSITIVITY TESTING

MAINTENANCE

The smoke detectors are designed for easy field
service and maintenance. If a detector drifts beyond
its approved sensitivity range for more than 24 hours,
or fails internal diagnostic tests, the unit automatically
indicates trouble by flashing its LED every second.
This meets field sensitivity testing requirements
without the need for external meters.

NOTE

Connect to a power supply that will not automatically
reset. Since the self-diagnostics only indicate trouble
after 27 hours, if the power supply automatically
resets the self-diagnostic indication will never be
signaled (the smoke detector will still signal alarm
correctly).

In accordance with NFPA 72, smoke detector sensitiv-
ity should be checked within one year after installa-
tion and every alternate year thereafter, in commercial
installations, or every three years in residential sites.
See 

Sensitivity Test.

The detector’s replaceable optical block chamber
unsnaps for easy field cleaning and service. Whenever
the status LED indicates cleaning is necessary, follow
these steps:

1. Open the detector cover, unsnap and throw away
the optical block chamber. See Figure 6.

2. Thoroughly blow off the optical base and snap a
new optical block chamber (part #211) back in place.

NOTE

Be sure the new optical block chamber is seated all
the way down.

3. Close the detector cover and verify sensitivity. See

Sensitivity Test

.

FIGURE 6 DETECTOR MAINTENANCE

OPERATION

Smoke detectors are powered, monitored, and
supervised by the apartment host panel. The host
panel is the master call panel for each apartment.

The host panel monitors the detector’s contacts and
will send an alarm to the console when the detector’s
relay is energized greater than 20 seconds.  This
delay is built-in to the host panels’ program to provide
a “verification” feature often specified on installations.

Host panels are polled by the console every 3.5
seconds, and the host panel must report the smoke
alarm on two consecutive poll cycles before the
console will announce the smoke condition.

These delays are intentional and will greatly reduce
nuisance alarms; however when testing, a delay of up
to 49 seconds can be realized before the alarm is
announced at the console.

TANDEM OPERATION - MULTIPLE DETECTORS

When more than one smoke detector is installed in
an apartment, they are connected to all sound when
any one detector senses smoke. This connection
method is referred to as “tandem” operation.

Содержание HM-560B

Страница 1: ...Sentry E Call Model HM 560B Photoelectric Smoke Detector Issue 1 March 2005 430 560B 0305 Heritage MedCall Inc Heritage MedCall...

Страница 2: ...aily and upon power up the detector performs a full diagnostic test that includes a dynamic test of the sensing chamber and internal electronics This meets NFPA 72 field sensitivity testing requiremen...

Страница 3: ...EGULATIONS PERTAINING TO SMOKE DETECTOR INSTALLATIONS VARY FROM STATE TO STATE FOR MORE INFORMATION CONTACT YOUR LOCAL FIRE DEPARTMENT OR LOCAL AUTHORITY HAVING JURISDICTION In addition to NFPA 72 use...

Страница 4: ...alled so when a detector is disconnected for any reason the end of line resistor or device must become disconnected A break in the detector power circuit or contact circuit will cause a trouble annunc...

Страница 5: ...low the directions on the can B Hold a smoldering punk or cotton wick close to the unit and gently direct the smoke into the smoke entry openings for 20 seconds or until an alarm is indicated Be sure...

Страница 6: ...eaning is necessary follow these steps 1 Open the detector cover unsnap and throw away the optical block chamber See Figure 6 2 Thoroughly blow off the optical base and snap a new optical block chambe...

Страница 7: ...apartment Check for detector operation as described in SMOKE TEST at each detector Normal Operation will sound the horn after applying smoke for 20 seconds NOTE When multiple smoke detectors are prese...

Страница 8: ...Heritage Medcall Sentry Emergency Call System Model 560B Smoke Detector Installation and Service Instructions 460 560B 0305 Heritage MedCall Inc FIGURE 7 SINGLE SMOKE DETECTOR WIRING FIGURE 8 MULTIPL...

Отзывы: