2.5 Connecting a Henden H8VSPBT pump

The following section should be read in conjunction with 
the installation and operating instructions of the Henden 
H8VSPBT pump. This option requires the installation of a 
secondary relay. 
To achieve maximum heating efficiency from the Henden 
heat pump, connect a Henden H8VSPBT pump using 
an RJ45 cable. When connected and the Henden heat 
pump detects your pool needs to be heated, it sends a 
signal to turn the Henden H8VSPBT pump to full speed 
(or an overridden speed selected by you

)

. You will need 

to purchase a separate relay to accommodate this. 
Specifications of relay required:
•  24V AC coil;
•  No contact;
•  Contact current: 1A minimum;
•  Screw contacts preferred as they can be connected 

to the RJ45 network cable used to signal the Henden 
H8VSPBT pump more easily.

Figure 3

There is a 17.5mm rail available inside the Henden heat 
pump for the electrician to use to mount the relay. 
Alternatively, a panel mount relay may be used. 
For this feature to work correctly, both the Henden heat 
pump and Henden H8VSPBT pump must be run at the 
same time.

WARNING: The electrical connection 
should be done by a qualified electrician 
according to national, state and local 
city codes and standards.

The Henden heat pump uses a 24V AC contactor to turn on 
the compressor to operate. Depending on the system your 
chosen speed of the Henden H8VSPBT pump will require 
connections as shown in the following diagrams:

Henden H8VSPBT pump 50% speed using T-568A cable

To RJ45 Socket of VSD Pump 

Pin8 (Brown)

Heat Pump

Pin6 (Orange)

Relay (Dry) 

Contact

Extra Relay Coil,

must be 24VAC. 

Henden H8VSPBT pump 50% speed using T-568B cable

To RJ45 Socket of VSD Pump 

Pin8 (Brown)

Heat Pump

Pin6 (Green)

Relay (Dry) 

Contact

Extra Relay Coil,

must be 24VAC. 

Henden H8VSPBT pump 67% speed using T-568A cable

To RJ45 Socket of VSD Pump 

Pin8 (Brown)

Heat Pump

Relay (Dry) 

Contact

Extra Relay Coil,

must be 24VAC. 

Pin7 (Brown/White)

Pin3 (Orange/White)

Henden H8VSPBT pump 67% speed using T-568B cable

To RJ45 Socket of VSD Pump 

Pin8 (Brown)

Heat Pump

Relay (Dry) 

Contact

Extra Relay Coil,

must be 24VAC. 

Pin7 (Brown/White)

Pin3 (Green/White)

Henden H8VSPBT pump 83% speed using T-568A cable

To RJ45 Socket of VSD Pump 

Pin8 (Brown)

Heat Pump

Relay (Dry) 

Contact

Extra Relay Coil,

must be 24VAC. 

Pin7 (Brown/White)

Pin6 (Orange)

Henden H8VSPBT pump 83% speed using T-568B cable

To RJ45 Socket of VSD Pump 

Pin8 (Brown)

Heat Pump

Relay (Dry) 

Contact

Extra Relay Coil,

must be 24VAC. 

Pin7 (Brown/White)

Pin6 (Green)

Henden H8VSPBT pump 100% speed using either 
T-568A, or T-568B cable

To RJ45 Socket of VSD Pump 

Pin8 (Brown)

Heat Pump

Pin7 (Brown/White)

Relay (Dry) 

Contact

Extra Relay Coil,

must be 24VAC. 

Figure 4

403227-2_Heat_Pump_Installation_Manual.indd   7

12/3/19   10:10 am

Содержание HHP14

Страница 1: ...ING Failure to follow these instructions and comply with all applicable codes may cause serious bodily injury and or property damage The installation of this product should be carried out by a person...

Страница 2: ...403227 2_Heat_Pump_Installation_Manual indd 2 12 3 19 10 10 am...

Страница 3: ...n H8VSPBT pump 7 2 6 FIL Mode optional 8 3 BEFORE START UP 8 4 OPERATING INSTRUCTIONS 8 4 1 Electronic Card Setting 8 4 2 Mode Temperature Adjustment 9 4 3 Changing the Display from Celsius to Fahrenh...

Страница 4: ...ance and winterising of the Henden heat pump easier Image 2 Congratulations on the purchase of your Henden heat pump It is designed and manufactured in Canada and is renowned for its efficiency and re...

Страница 5: ...e solar absorber after the Henden heat pump Henden doesn t recommend this practice as solar absorbers can t typically accommodate the same flow rates as the Henden heat pump The solar absorber may als...

Страница 6: ...lation Manual 6 HENDEN INSTALLATION OWNERS MANUAL Wiring diagram for models HHP14 HHP22 HHP28 Wiring diagram for model HHP34 Figure 1 Where applicable Figure 2 403227 2_Heat_Pump_Installation_Manual i...

Страница 7: ...he Henden heat pump uses a 24V AC contactor to turn on the compressor to operate Depending on the system your chosen speed of the Henden H8VSPBT pump will require connections as shown in the following...

Страница 8: ...perature is reached Table below of other common number of filtering hours and running times Number of filtering hours Running Time 2 20 minutes 6 times a day 6 60 minutes 6 times a day 8 1 hr 20 minut...

Страница 9: ...he evaporator is de icing FS will be displayed as seen in image 6 During that process the fan will operate but the compressor will be turned off 5 WINTERISING Winterising is required in conditions whe...

Страница 10: ...ll pool to dillute Frequency of Testing Weekly Weekly Weekly Weekly Regularly Table2 6 2 Regular maintenance Inspect and clean the pool filter regularly to ensure adequate water flow to the Henden hea...

Страница 11: ...me hour for one of the reasons above code LP Cycle the power off then on to reset the Henden heat pump CODE HP The flow inside the Henden heat pump is insufficient The bypass valves are in the wrong p...

Страница 12: ...the provided installation and operating instructions failure to carry out maintenance corrosive or abrasive water or other liquid lightning or high voltage spikes or unauthorised persons attempting r...

Страница 13: ...Henden Heat Pump Owners Manual HENDEN INSTALLATION OWNERS MANUAL 13 NOTES 403227 2_Heat_Pump_Installation_Manual indd 13 12 3 19 10 10 am...

Страница 14: ...Henden Heat Pump Owners Manual 14 HENDEN INSTALLATION OWNERS MANUAL NOTES 403227 2_Heat_Pump_Installation_Manual indd 14 12 3 19 10 10 am...

Страница 15: ...Henden Heat Pump Owners Manual HENDEN INSTALLATION OWNERS MANUAL 15 403227 2_Heat_Pump_Installation_Manual indd 15 12 3 19 10 10 am...

Страница 16: ...P N 403227 2 403227 2_Heat_Pump_Installation_Manual indd 16 12 3 19 10 10 am...

Отзывы: