background image

Henden Heat Pump Owners Manual

 

HENDEN

 INSTALLATION & OWNERS MANUAL 

|

 

11

8. TROUBLESHOOTING

PROBLEM

LIKELY CAUSE(S)

WHAT TO LOOK FOR

Digital  

Control Displays

CODE: FLO

• The water flow inside the Henden 

heat pump is insufficient;

• There is no water circulation inside 

the Henden heat pump;

• The flow switch is faulty.

• Make sure that the circulating pump works;

• Make sure the bypass valves are properly positioned;

• Check the pool skimmer basket is clear;

• Check the water pressure of your circulation system. Ideally it 

should be between 68 – 137kPa.

CODE: FL3

The flow switch has cut out 3 times 
in the same hour for one reason 
shown above (code FLO).

• Cycle the power off then on to reset the Henden heat pump;

• Make sure FIL is set to OFF (section 2.6).

CODE: FS

The Henden heat pump is in 
de-icing mode.

Wait until the end of the de-icing cycle. The Henden heat pump 
will restart automatically.

CODE: LP

• Ventilation on the evaporator is 

insufficient;

• The fan is faulty;

• There’s a refrigerant leak;

• The outside ambient temperature 

is too low.

• Check the evaporator is not obstructed by pollen, grass, leaves 

etc. Refer to section 6 for safety instructions;

• Be sure there is enough free space around the Henden heat 

pump. Refer to section 2;

• Check that the fan is running.

CODE: LP3

The Henden heat pump low pressure 
switch has cut out 3 times in the 
same hour for one of the reasons 
above (code LP).

• Cycle the power off then on to reset the Henden heat pump

CODE: HP

• The flow inside the Henden heat 

pump is insufficient;

• The bypass valves are in the wrong 

position;

• Flow switch is incorrectly set and 

static pressure in the system is 
keeping the flow switch activated 
(pump not running);

• The water exit is blocked.

• Ensure there is correct water flow through the Henden heat 

pump;

• Check the bypass valves are properly positioned;

• Adjust flow switch so that static pressure does not activate 

flow switch;

• Check if there’s an object obstructing the water hose.

CODE: HP3

The (high) pressure switch has cut 
out 3 times in the same hour for one 
of the reasons above (code HP).

•  Cycle the power off then on to reset the Henden heat pump. 

CODE: SPI

The general control is faulty.

Cycle the power off then on to reset the Henden heat pump. If 
the problem is not resolved, the digital control will have to be 
changed. In this case, call your installer or 1300 HENDEN (1300 
436 336).

CODE: DPO

The de-icing sensor is not properly 
connected or is not receiving power.

Call your Installer or 1300 HENDEN (1300 436 336).

CODE: PO

The water temperature sensor 
is faulty.

CODE: DPC

The de-icing sensor is faulty.

CODE: PC

The water temperature sensor 
is faulty.

NO CODE: Heat 
is needed, the fan 
is functioning, no 
code is displayed 
and the compressor 
does not start.

Electrical problem in the compressor 
circuit

Capacitor defective

Compressor defective

403227-2_Heat_Pump_Installation_Manual.indd   11

12/3/19   10:10 am

Содержание HHP14

Страница 1: ...ING Failure to follow these instructions and comply with all applicable codes may cause serious bodily injury and or property damage The installation of this product should be carried out by a person...

Страница 2: ...403227 2_Heat_Pump_Installation_Manual indd 2 12 3 19 10 10 am...

Страница 3: ...n H8VSPBT pump 7 2 6 FIL Mode optional 8 3 BEFORE START UP 8 4 OPERATING INSTRUCTIONS 8 4 1 Electronic Card Setting 8 4 2 Mode Temperature Adjustment 9 4 3 Changing the Display from Celsius to Fahrenh...

Страница 4: ...ance and winterising of the Henden heat pump easier Image 2 Congratulations on the purchase of your Henden heat pump It is designed and manufactured in Canada and is renowned for its efficiency and re...

Страница 5: ...e solar absorber after the Henden heat pump Henden doesn t recommend this practice as solar absorbers can t typically accommodate the same flow rates as the Henden heat pump The solar absorber may als...

Страница 6: ...lation Manual 6 HENDEN INSTALLATION OWNERS MANUAL Wiring diagram for models HHP14 HHP22 HHP28 Wiring diagram for model HHP34 Figure 1 Where applicable Figure 2 403227 2_Heat_Pump_Installation_Manual i...

Страница 7: ...he Henden heat pump uses a 24V AC contactor to turn on the compressor to operate Depending on the system your chosen speed of the Henden H8VSPBT pump will require connections as shown in the following...

Страница 8: ...perature is reached Table below of other common number of filtering hours and running times Number of filtering hours Running Time 2 20 minutes 6 times a day 6 60 minutes 6 times a day 8 1 hr 20 minut...

Страница 9: ...he evaporator is de icing FS will be displayed as seen in image 6 During that process the fan will operate but the compressor will be turned off 5 WINTERISING Winterising is required in conditions whe...

Страница 10: ...ll pool to dillute Frequency of Testing Weekly Weekly Weekly Weekly Regularly Table2 6 2 Regular maintenance Inspect and clean the pool filter regularly to ensure adequate water flow to the Henden hea...

Страница 11: ...me hour for one of the reasons above code LP Cycle the power off then on to reset the Henden heat pump CODE HP The flow inside the Henden heat pump is insufficient The bypass valves are in the wrong p...

Страница 12: ...the provided installation and operating instructions failure to carry out maintenance corrosive or abrasive water or other liquid lightning or high voltage spikes or unauthorised persons attempting r...

Страница 13: ...Henden Heat Pump Owners Manual HENDEN INSTALLATION OWNERS MANUAL 13 NOTES 403227 2_Heat_Pump_Installation_Manual indd 13 12 3 19 10 10 am...

Страница 14: ...Henden Heat Pump Owners Manual 14 HENDEN INSTALLATION OWNERS MANUAL NOTES 403227 2_Heat_Pump_Installation_Manual indd 14 12 3 19 10 10 am...

Страница 15: ...Henden Heat Pump Owners Manual HENDEN INSTALLATION OWNERS MANUAL 15 403227 2_Heat_Pump_Installation_Manual indd 15 12 3 19 10 10 am...

Страница 16: ...P N 403227 2 403227 2_Heat_Pump_Installation_Manual indd 16 12 3 19 10 10 am...

Отзывы: