background image

Document Ref. EPD05183

(08.11.99)

ENGLISH

Part No. I380GB

issue 2

page 4

Connections

Low voltage connections:

+,  -

24 VDC power supply from dimmer to Master Panel

A, SC, B

Data cable with screen

OVR,  0

Level override: connecting between OVR and 0 sets light output
of all channels to 100%

0V 

1 2 3 4

10V

Analogue 0-10V control for 4 channels

Mains voltage connections:

Mains voltage output for use with preheat transformers, switches

off only when all four channels are switched off.

1-4

Dimmed phase for individual channels.

N

Neutral for individual channels.

L in

Phase of incoming mains, alternatively as L1 of delta-network.

N in

Neutral of incoming mains, alternatively as L2 of delta-network.

Earth connector block for all earth cables.

Control Wiring

  

24VDC supply cable:

Wiring distance:

max. 200 m

Supply voltage:

24 VDC nominal (20 VDC - 28 VDC), max.100 mA

Cable type:

solid or stranded, shield is not required, 0.22 - 1.5 mm²,

1.0 mm² recommended, maximum loop resistance 8 Ohm

(4 Ohm/cable)

  Level override:

Wiring distance:

max. 200 m

Cable type:

see 24VDC supply cable specifications

  Data cable:

Control distance:

max. 200 m

Signal type:

RS 422/485 115 kbaud

Cable type:

multistranded, twisted and shielded,  0.22 - 1.5 mm²,

attenuation max 62 dB/km at 1 MHz, characteristic impedance

80 ±20 Ohm,

recommended cable type Belden 8762, Alpha 2411C, Nokia NOMAK or

equivalent.  A combined 24v DC supply and data cable available from
Electrosonic 100m (ES9910) 500m (ES9950).

  

Pushbutton cable:

Control distance:

max. 100 m

Signal type:

digital, typ10 VDC, min 0 VDC, max +20 VDC

Cable type:

multistranded, twisted and shielded, 0.22  - 1.5 mm²

10 kbaud capable, maximum loop resistance 8 Ohm

(4 Ohm/cable), maximum capacitance 15 nF between any wires,

recommended cable type Belden 8762, Alpha 2411C, Nokia NOMAK or

equivalent

Содержание HES99300

Страница 1: ...93 251 63 211 230 HES99300 4 CHANNEL DIMMER Technical Data Mains voltage 200 250v AC single phase 100 130v AC single phase to special order Mains frequency 45 65 Hz Mains quality all data is based on...

Страница 2: ...ballast is about 0 5 mA Due to harmonic currents the leakage current can rise up to 5 0 mA ballast when dimmed This has to be taken into account in those installations where earth leakage circuit brea...

Страница 3: ...panel are only used when connected to an Ambience 24 or an Imagine system For use within a 4 Channel system do not change factory settings A SC B 0VR 0V 0V 1 2 3 4 10V 1 2 2 3 4 N N N N Nin Lin 24 VD...

Страница 4: ...0 m Supply voltage 24 VDC nominal 20 VDC 28 VDC max 100 mA Cable type solid or stranded shield is not required 0 22 1 5 mm 1 0 mm recommended maximum loop resistance 8 Ohm 4 Ohm cable Level override W...

Страница 5: ...ECTRONICS CONTROL ELECTRONICS 0v D1 D2 D3 D4 10v 0v D1 D2 D3 D4 10v A SCN B A SCN B 0 10v CONTROL 0 10v CONTROL S DIM 0VR 0V 0VR 0V SUPPLY INPUT SUPPLY INPUT E D1 D2 D3 D4 S L 1 S L 1 SWITCHED DIMMED...

Страница 6: ...ty alarms etc Total max 4 slave panels including one IR receiver Facility for 0 10v DC control input Dimmer outputs Channels 1 4 HES99040 4 Scene Off Panel B SC A B A SC A B SC Ovr 0 1 N 4 3 2 Power i...

Страница 7: ...Changing the Channel Addresses 1 Press and hold the pair of buttons for the corresponding dimmer until the display shows the Channel Address Mode then release both buttons For example the left hand pa...

Страница 8: ...9 HELVAR LIGHTING CONTROL LIMITED Part No I380GB Hawley Mill Hawley Road Dartford Kent DA2 7SY U K Document Ref EPD05183 Tel 01322 222211 Fax 01322 282282 issue 2 08 11 99 S DIM S DIM is an Electroson...