10
Helvar | Data is subject to change without notice.
o
Last poll duration value.
This value shows the number of seconds that it has taken to poll all the configured Helvar
routers.
3.
Configure the BACnet device settings. These settings define the connection details for the
unit to appear as a BACnet device on the BACnet/IP based control system.
Note:
Each BACnet device includes a default set of properties that are displayed in a BACnet
Explorer. They are described in the BACnet PICS: see
Annex A – Protocol
Implementation Conformance Statement
(Normative)
.
o
Device instance.
Default: 370001; range: 1 – 999999.
This number identifies the unit on the
BACnet/IP based control system. Change this
number if you have more than one 435 on the
BACnet/IP network.
Caution:
If the network has more than one 435 , each unit requires individual Device instance
numbers.
o
DCC password (max. 30 characters).
This is used to permit the DCC (Device Communication Control) and RD (Reinitialise
Device) operations.
o
Description.
You can enter any desired descriptive information in the BACnet/IP based control system.
This information will be read by the communication partners.
4.
Press Save to apply the changes.
2.4.
Configure the Map points
The Map points page is used to expose predetermined parameters in a single workgroup to a
BACnet Supervisor (BACnet client) on the BACnet/IP based control system. These predetermined
parameters are available from discovered Helvar routers and Helvar router subnet devices.
Tip:
Use Helvar Designer software to configure the lighting system and to assign IP
addresses to Helvar routers. All Helvar programming should be completed before you
map the points to the 435 Gateway