Helvar 435 BACnet Gateway: User Guide
7
2.2.
Connect to the 435 BACnet Gateway
After the BACnet Gateway has been correctly installed (see the
Installation Leaflet supplied with
each unit or the
Installation Guide), you need to configure the communication protocols and the
required parameters.
Each unit is supplied with a default IP address that identifies the unit on the IP network. You must
replace this IP address with a unique IP address as required by the applicable local network
policy.
Before configuring the unit, make sure that the connected computer has a compatible IP address,
i.e. an IP address in the same IP range as the BACnet Gateway. Otherwise, change the computer’s
IP address.
To connect to the BACnet Gateway:
1.
After physically connecting the unit to the computer (see the
Installation Guide), open a
browser application (Firefox recommended).
2.
In the browser Navigation toolbar, type the required IP address using the standard 32-bit
dotted-decimal notation.
Default IP address: 10.254.0.100 (255.0.0.0)
The Login page will appear.
3.
Type the User name and Password (both are case
sensitive), and then press Log in.
o
User name: Admin
o
Password: password
Tip:
If the ‘Login’ page fails to appear, use the ping test to
confirm that the expected IP address is used.
If the valid ‘User name’ and ‘Password’ fails to launch
the configuration page, clear the browser cache, and
then contact technical support for instructions.
4.
Press
to display the Home page. This provides access to the configuration pages.
Tip:
Zoom out to display more information.
2.3.
Configure the Comms interface
The IP config and Comms settings menu options allow you to configure the communication
protocols needed to transmit data between:
•
The Helvar routers and the BACnet Gateway.
•
The BACnet Gateway and the BACnet client on the BACnet/IP based control system.
Caution:
Configure the IP address, the subnet mask and the default gateway according to the
applicable local network policy.