1.
BEFORE YOU INSTALL
Inspect the delivery as soon as you receive it.
Report any transport damages to the deliverer.
1.1. INSPECTION OF THE DELIVERY
With regard to safety distances, the E3 regulations
of the Finnish building code or equivalent regula-
tions in your country of residence must be adhered
to.
A normal delivery includes the chimney elements in
accordance with the order document:
• non-insulated connection pipe of 1m which can
be shortened (permitted minimum length 0.2 m)
• the insulated section (1.5m) is always delivered in
four parts, which are connected to each other
with a tie ring
• finishing piece
• starting piece
• the supporting flat ceiling plate, which is suited
for pitches of the roof of 0°–30°
• roof seal (to seal the chimney root),
• rain cap (slid on top of the upper element and
tightened in place)
• CE decals (2)
• installation manual
Insulation cylinder
The equivalence of the delivery to the order docu-
ment must be checked as soon as possible. Any
missing, defective or wrong parts must be reported
immediately to the supplier. When the missing or
faulty parts are due to the supplier, he will deliver
the required new parts as soon as possible to the
assembly site.
The manufacturer and supplier do not take re-
sponsibility for costs arising from indirect damage,
delays, work stoppages etc.
1.2. MATTERS AND REGULATIONS TO BE
CONSIDERED PRIOR TO INSTALLATION
Remember to account for the E3 regulations of the
Finnish building code or equivalent regulations
in.Your country of residence regarding the height
of the chimney with regard to the highest part of
the roof. See chapter 2.3.1 Illustration 3.
Check the following as well:
• The installation permits for the chimney are in
order
• The chimney’s length and its inner pipe’s internal
diameter are in accordance with the fireplace’s
manufacturer’s instructions
• Prior to cutting the through holes, make sure
there are no floor joists or wall supports in the
way
• Ensure beforehand by measuring that any exten-
sion pieces will not be going through floors or the
roof. See chapter 2.3. Illustration 2.
1.3. SAFETY DISTANCES AND PROTECTIVE
CASING
ATTENTION! Disregarding these instructions may
cause fire hazards!
Flammable parts of the building must be situated
so far from the outer surface of the flue channel
that their temperature cannot rise 85
o
Celsius (+185
o
Fahrenheit), but with a minimum
distance of 50 mm.
In flammable building parts, such as floors and
ceilings, the through hole will be equipped with
insulation cylinder.
Note! Stove chimneys chapter 2.10.
Chimney safety distances
The safety distance for insulated section is
50mm
If the flue channel borders a cupboard or other
storage space, the protective casing against the
chimney’s mantle must not contain insulation and
the casing must have a ventilated airing slot to pre-
vent overheating in the storage space and chimney.
If there needs to be casing for some reason, the
casing must be made of non-flammable material
and have sufficient internal ventilation. We recom-
mend conferring about the details with your local
fire department’s fire inspector.
The safety distance for non-insulated connection
pipes and extension pipes is 400mm. This distance
can be reduced by 50 % with a lightweight, single
layer protection. This protection can consist of
either 1mm thick metal sheeting or 7mm thick fibre-
reinforced cement panels (not gypsum panels with
paper sur- face). Leave a ventilation gap of 30 mm
between wall and protective layer and keep them
detached from floor and ceiling.
Width and height of the protection are defined
according to the 400 mm rule mentioned above, so
that the minimum distances from the bare pipe to
flammable material are kept. The lower part of the
insulated flue channel must extend at least
400mm
downwards from the ceiling. The reducer cone of a
semi-insulated chimney can be right below the
ceiling.
The safety distance is always measured from flam-
mable material to the heating device or flue pipe.
When the connection pipe is used, there must be at
least 400 mm of insulated pipe segment below the
ceiling.
1.
1.1.
1.2.
1.3.
Содержание KIUASPIIPPU
Страница 45: ......
Страница 46: ...1 1 1 1 2 1 3 1 4 2 2 1 2 2 2 3 2 3 1 E3 2 4 2 5 2 6 2 7 115 2 8 2 9 2 10 3 3 1 3 2 4 4 1 4 2 4 3...
Страница 48: ...400 1 4 80 o C 250 o C 500 o C 1 3 1 4...
Страница 49: ...2 2 3 4 2 1 2 2 2 3 1 0 2 1 5 0 30 2550 400 3 3 3 400 1500 2 2 1 2 2 2 3...
Страница 51: ...2 5 1000 2000 2 4 2 6 2 7 1550 2 8 2 9 500 50 100 100 3 2 5 2 6 2 7 2 8 2 9...
Страница 52: ...2 10 0 30 Vartti 1250 800 50 Wurth Sikaflex 1 2 50 3 4 5 2 10...
Страница 53: ...3 3 1 3 2 3 3 1 3 2...
Страница 56: ...HELO OY Tehtaankatu 5 7 11710 Riihim ki FINLAND www helo fi...