OPERATING INSTRUCTIONS TREND SERIES
TLG Unit Voltage Checks
-9 pin connector located under “Do Not Remove” plate, upper LH Corner
Pin
Satisfactory
Voltage
Range
Brown
-3.8
to
-4.2
volts
Red
-3.8
to
-4.2
volts
Orange
+3.8
to
+4.2
volts
Yellow
-11.5
to
-12.5
volts
Green
+11.5
to
+12.5
volts
Blue
+3.8
to
+4.2
volts
Grey
0 volts
White
+4.75 to +5.25 volts
Miscellaneous Troubleshooting Specifications
HT-400
Sensor
Ohm
Readings
Green - Black
350 ohms
Red
-
White
350
ohms
All other color combinations
266 ohms
All
color
to
Ground
open
Shield
to
Ground open
M
Содержание Trend Loadgard TLG2300
Страница 26: ...OPERATING INSTRUCTIONS TREND SERIES A...
Страница 27: ...OPERATING INSTRUCTIONS TREND SERIES B...
Страница 28: ...OPERATING INSTRUCTIONS TREND SERIES C...
Страница 29: ...OPERATING INSTRUCTIONS TREND SERIES D...
Страница 32: ...OPERATING INSTRUCTIONS TREND SERIES G...
Страница 33: ...OPERATING INSTRUCTIONS TREND SERIES H...
Страница 35: ...OPERATING INSTRUCTIONS TREND SERIES J Appendix C TLG 8000 Operation Guidelines...
Страница 36: ...OPERATING INSTRUCTIONS TREND SERIES K Appendix C TLG 8000 Operation Guidelines...
Страница 39: ...OPERATING INSTRUCTIONS TREND SERIES N...
Страница 40: ...OPERATING INSTRUCTIONS TREND SERIES O...
Страница 41: ...OPERATING INSTRUCTIONS TREND SERIES P...
Страница 42: ...OPERATING INSTRUCTIONS TREND SERIES Q...
Страница 43: ...OPERATING INSTRUCTIONS TREND SERIES R...
Страница 44: ...OPERATING INSTRUCTIONS TREND SERIES S...
Страница 46: ...OPERATING INSTRUCTIONS TREND SERIES U...