OPERATING INSTRUCTIONS                                               TREND SERIES 

SETTING HIGH - LOW TOLERANCE LIMITS 

 
Every TREND system features tolerance alarms which are used to establish a “quality window” that the 
process will operate within.  These alarms are set as a percentage of the forming force and automatically 
adjusted each time a sample is taken or a new job is started. 
 
The ability to establish alarms in percent eliminates the need to re-adjust settings for each job change.  For 
example, with high and low tolerance settings of 10%, a 100 ton job has alarms automatically set at 110 tons 
high and 90 tons low.  A 40 ton job has alarms automatically set at 44 tons high and 36 tons low. 
 

 

 
There are two switches for each channel of monitoring; one to establish the LOW alarm setting and one for 
the HIGH alarm setting.  Each switch is selectable from 5% to 45%, in increments of 5%.  There is also a 
position to turn the alarms off. 
 
A tolerance setting of plus 5% on an individual channel will cause an alarm when the load level increases 
5% above the sampled load. 
 
A tolerance setting of minus 45% on a particular channel will cause an alarm when the load decreases 45% 
from the sampled load. 
 
 
 

ESTABLISHING OPTIMUM TOLERANCE SETTINGS 

 
A good baseline starting point is 25%, high and low.  With the instrument in Monitor Parts mode, watch the 
trend lights during a production run.  Begin lowering tolerance percents until the center green (GOOD) LED 
starts flashing one LED up and down from center. 

 
 
 

12 

Содержание Trend Loadgard TLG2300

Страница 1: ...nt Company Inc 361 West Dussel Drive Maumee Ohio 43537 USA 419 893 4356 Fax 419 893 1371 www helminstrument com Trend Series TLG2300 TLG4500 Loadgard Operating Instructions Force Measurement and Contr...

Страница 2: ...e limited to repairing or replacing any defective Product at no additional charge and returning Product to customer freight paid Repair parts and replacement Products shall be furnished on an exchange...

Страница 3: ...OPERATING INSTRUCTIONS TREND SERIES EXPLANATION OF SYMBOLS Alternating Currrent Earth ground TERMINAL On Supply Off Supply Caution risk of electric shock Caution refer to accompanying documents iii...

Страница 4: ...Procedures 10 Setting Capacity Alarm 11 Setting High Low Tolerance Limits 12 Establishing Optimum Tolerance Settings 12 Job Data Control Jdc 13 Initial Storing Of Capacity And Tolerance Settings 13 S...

Страница 5: ...e HELM TREND LOADGARD control system provides protection for the die the product and the machine with minimal operator involvement The Loadgard takes a sample of the forming force of an ideal part sto...

Страница 6: ...from vibration Care should be taken to insure that the instrument chassis ground is the same potential as the machine ground See Mounting Detail Illustration in Appendix A ENVIROMENTAL CONDITIONS This...

Страница 7: ...20V operation 120V 10 50 60 Hz 500 mA Max Unit marked for 220V operation 220V 10 50 60 Hz 250 mA Max Installation Class III Replacement Fuses Replace fuses with main power OFF o Replace fuses with TT...

Страница 8: ...eel cabinet card rack inside the instrument holds all the circuit boards Slot 1 is reserved for the optional computer interface card Slot 2 contains the microprocessor board that controls all instrume...

Страница 9: ...on numbers will be noted on a tag inside the instrument Once calibrated it is not necessary to re calibrate unless the machine is moved dismantled or otherwise structurally changed If you have any que...

Страница 10: ...AUTO ZERO switch to the OFF back position 2 Pull CALIBRATION switch to the OFF forward position 3 Adjust the ZERO BALANCE The zero balance BALANCE ADJUST controls are the small multi turn potentiomet...

Страница 11: ...ess has been calibrated use the CAL numbers that are recorded for each channel If the press has not been calibrated use 50 as a temporary cal number Watch the digital meter and turn the GAIN ADJUST co...

Страница 12: ...ND INCLUDING 500 TON TOTAL CAPACITY Put the METER RANGE selector to the LOW position Calculate the capacity of one corner by dividing the total machine capacity by the number of channels 4 Set the MET...

Страница 13: ...witches labeled SW1 SW2 and SW3 EXAMPLE For a 100 ton machine rated at 50 tons per side set switches to 050 by setting left switch SW1 to 0 middle switch SW2 to 5 and right switch SW3 to 0 Re install...

Страница 14: ...S ALARM SET PROCEDURES Capacity and tolerance alarm adjustments are located on the inside door panel Capacity alarms provide press overload protection Tolerance alarms provide tooling and die protecti...

Страница 15: ...by four 4 for four channel systems Divide by two 2 for two channel systems 6 Watch the digital meter s and adjust capacity for each channel Models 2100 4100 use the LEFT or RIGHT DISPLAY button for di...

Страница 16: ...44 tons high and 36 tons low There are two switches for each channel of monitoring one to establish the LOW alarm setting and one for the HIGH alarm setting Each switch is selectable from 5 to 45 in...

Страница 17: ...h indicating data is being stored 6 To over ride and store new settings follow steps 1 5 STORING OF TARGET LOADS 1 Put JDC switch in Auto mode 2 Turn front panel keyswitch to monitor parts mode 3 TARG...

Страница 18: ...Select job number to be recalled 2 Put JDC switch in auto mode 3 Capacity and Tolerance settings are activated for first hit protection 4 Press Target Load button on front panel to display target valu...

Страница 19: ...Machine capacity alarms are active Press button labeled CAPACITY ALARMS to display alarm settings on each channel The alarm RESET button will initiate a PEAK reset The REVERSE LOAD and strokes per min...

Страница 20: ...aken Any load change that meets or exceeds the tolerance settings will cause an alarm condition and activate the machine stop relay In Monitor Parts Reset Not Active the ALARM RESET button is inactive...

Страница 21: ...from remote location With computer set limits JDC and manual selector switches are inactive and computer has control DIGITAL METER DISPLAY During normal operation the center digital meter displays the...

Страница 22: ...lights are on the last part was formed at the same load as the sampled benchmark no deviation in load The top red lights of each column represents the HIGH alarm trip point as set by the tolerance se...

Страница 23: ...ng developed throughout the entire stroke of the machine Each die has its own unique signature similar to an electro cardiogram Analyzing each of the subtle peak forces developed during the stamping p...

Страница 24: ...STROKES PER MINUTE button to display machine operating speed on center meter Two machine cycles are required before SPM is displayed TOLERANCE ALARMS Press the TOLERANCE ALARMS button to display high...

Страница 25: ...t only The unit should be wiped dry then allowed to air dry before returning to service Internal printed circuit board cleaning is accomplished by removing individual boards and cleaning with an appro...

Страница 26: ...OPERATING INSTRUCTIONS TREND SERIES A...

Страница 27: ...OPERATING INSTRUCTIONS TREND SERIES B...

Страница 28: ...OPERATING INSTRUCTIONS TREND SERIES C...

Страница 29: ...OPERATING INSTRUCTIONS TREND SERIES D...

Страница 30: ...the filter board on the inside panel marked DO NOT REMOVE Use existing thumbwheel screws on left side of panel Remove the top two screws and attach filter board on top of panel as shown below Route c...

Страница 31: ...The connector for computer hook up is J4 2 J14 is the connector for the sine cosine resolver input Refer to drawing B10W996 1 for wiring detail 3 There is a 422 to TTL converter on the card 422 plugs...

Страница 32: ...OPERATING INSTRUCTIONS TREND SERIES G...

Страница 33: ...OPERATING INSTRUCTIONS TREND SERIES H...

Страница 34: ...ONS TREND SERIES Model TLG 8000 This appendix describes additional operating instructions for the standard TLG 8000 and TLG 8000DP with Cam Limit Switch Refer to drawings T 2435 42 and T 2435 41 follo...

Страница 35: ...OPERATING INSTRUCTIONS TREND SERIES J Appendix C TLG 8000 Operation Guidelines...

Страница 36: ...OPERATING INSTRUCTIONS TREND SERIES K Appendix C TLG 8000 Operation Guidelines...

Страница 37: ...nit page 3 3 Monitor Calibrate switch in left monitor position page 7 4 Capacity alarm switch in left off position page 11 5 Auto Zero switch on each channel board in forward on position pages 6 7 6 C...

Страница 38: ...to 4 2 volts Red 3 8 to 4 2 volts Orange 3 8 to 4 2 volts Yellow 11 5 to 12 5 volts Green 11 5 to 12 5 volts Blue 3 8 to 4 2 volts Grey 0 volts White 4 75 to 5 25 volts Miscellaneous Troubleshooting S...

Страница 39: ...OPERATING INSTRUCTIONS TREND SERIES N...

Страница 40: ...OPERATING INSTRUCTIONS TREND SERIES O...

Страница 41: ...OPERATING INSTRUCTIONS TREND SERIES P...

Страница 42: ...OPERATING INSTRUCTIONS TREND SERIES Q...

Страница 43: ...OPERATING INSTRUCTIONS TREND SERIES R...

Страница 44: ...OPERATING INSTRUCTIONS TREND SERIES S...

Страница 45: ...ections Tolerance alarms stop machine before tolerance setting is reached Capacity alarms settings have been activated Check Capacity Alarm Sets Reset capacity alarms if required Alarms are fired or m...

Страница 46: ...OPERATING INSTRUCTIONS TREND SERIES U...

Отзывы: