Battery condition test (BCT)

 

An internal jumper must be fitted to enable the automatic battery condition test function.  If this jumper is 
fitted the battery condition test function may also be initiated manually by pushing the 

BATT SYS OK 

but-

ton for approx. 2 seconds.

 

 

Battery Condition Test Fail Reset

 

If the system fails the BCT the 

BATT SYS OK 

LED continues flashing and the 

BATT LOW

 

alarm latches  

until either both the mains power input and the battery are disconnected briefly,  or the system passes 
the next BCT.

 

 

Battery 

 

System OK 

LED

 

Power OK 

LED

 

Power 

 

Stand

-

by 

LED

 

Battery 

 

System 

 

OK Alarm

 

Power OK 

Alarm

 

Condition

 

 

 

 

Normal

 

Normal

 

System Normal:  Input power on, battery circuit is OK 

 

 

 

 

Normal

 

Normal

 

Battery detection in progress

 

 

 

 

Alarm

 

Normal

 

Input power on, battery system fault:

 

 

1.

 

Internal battery fuse has opened 

or

 

2.

 

Battery circuit wiring open circuit,  battery missing, ECB has tripped

 

 

 

 

Normal

 

Alarm

 

Input power off,  battery system is OK (battery volts > Vbatl)

 

 

 

 

Alarm

 

Alarm

 

Input power off  and battery has discharged to < V batl 

 

 

 

 

Alarm

 

Alarm

 

Input power off, ELVD has activated and disconnected battery from load.

 

 

 

 

Normal

 

Normal

 

PSU in standby, input power on,  battery system OK

 

 

 

 

Alarm

 

Alarm

 

PSU is in standby 

and

 battery has discharged to < Battery Low, unit will continue 

delivering battery current until next level initiates ELVD.

 

 

 

 

Alarm

 

Alarm

 

PSU is in standby 

and

 ELVD has activated and disconnected battery from load. 

 

 

 

 

Normal

 

Normal

 

BCT in progress

 

 

 

 

Alarm

 

Normal

 

Input power on, BCT failed (battery voltage < Vpres during BCT)

 

LEGEND :

 

=Off

 

=fast flash

 

=On

 

=slow flash

 

LED FLASH CODES

 

Содержание SR250C

Страница 1: ...d 64 9 8350700 Sydney 61 2 9809 5022 Singapore 65 6871 4140 www heliosps com SR500C SR750C with optional V I meter shown SR250C User Manual SR250C SR500C SR750C No BreakTM DC UPS 15 09 2016 REFER TO B...

Страница 2: ...shortened lifetimes if subjected to high ambient temperatures Water Dust Every effort must be made in the installation to minimise the risk of ingress of water or dust Water will almost always cause...

Страница 3: ...tery circuit integrity Fast electronic battery overcurrent protection Deep discharge protection by disconnecting the load at low battery voltage Temperature compensated output voltage using external t...

Страница 4: ...anks Power OK YES Battery Missing YES Battery Low YES Battery Condition Test Fail YES Alarms Available 2 Peak load connection using 1 x No Break DC charger Use this connection when there is a connecte...

Страница 5: ...tteries 7 Connect input power Charger should be fully operational at this stage ALARM BCT RELAYS Relay contacts shown in de energised state ie when there is a fault condition Alarm relays are energise...

Страница 6: ...eshold for battery detection and BCT Note that if the voltage drops to this level during a BCT the test is aborted and the BAT LOW SYS alarm shows Vshutd Internal voltage level of the power supply dur...

Страница 7: ...al System Normal Input power on battery circuit is OK Normal Normal Battery detection in progress Alarm Normal Input power on battery system fault 1 Internal battery fuse has opened or 2 Battery circu...

Страница 8: ...ve is also activated for the low voltage disconnect function on mains fail no input power It will reset when input power is restored or can be manually reset by briefly shorting the BAT and LOAD termi...

Страница 9: ...Specifications are subject to change without notice No liability accepted for errors or omissions 9 This page is intentionally blank...

Страница 10: ...open circuit to 100 load 1 output voltage 0 03 C 20 ms without battery nominal max Vin 1 sec Yes self resetting Over voltage protection on output at 130 of nominal output voltage CISPR 22 EN55022 cla...

Страница 11: ...eak load on mains fail A SR250C12 13 8 18 0 18 0 12 0 27 SR250C24 27 6 9 0 9 0 5 0 13 5 SR250C30 34 5 7 2 7 2 3 7 10 8 SR250C36 41 4 6 0 6 0 3 0 9 SR250C48 55 2 4 5 4 5 2 0 6 7 MODELS MODEL TABLE rati...

Страница 12: ...uit to 100 load 1 output voltage 0 03 C 20 ms without battery nominal max Vin 2 sec Yes self resetting Over voltage protection on output at 130 of nominal output voltage to CISPR 22 EN55022 class A to...

Страница 13: ...May be fitted with SR500 in 19 rack add SR METER or SR METERV2 SHUNT Charger may be fitted into enclosure with MCBs and terminals Code SEC SR Use external output diode eg P50 Add code INT METER Ethern...

Страница 14: ...uit to 100 load 1 output voltage 0 03 C 20 ms without battery nominal max Vin 2 sec Yes self resetting Over voltage protection on output at 130 of nominal output voltage to CISPR 22 EN55022 class A to...

Страница 15: ...for S versions OPTIONS 19 Rack Mount Digital V I meter Wall Mount Enclosure Parallel redundancy Internal V I Meter Communications Port SR750i MODEL IDENTIFICATION CODES 2U sub rack option add SR RM2U...

Страница 16: ...ip defects Liability under this warranty is limited to the replacement or repair of the defective product as long as the prod uct has not been damaged through misapplication negligence or unauthorized...

Отзывы: