5

 

CONNECTION PROCEDURE

 

 

1

 

Check input and output voltages of system, ensure that they match the equipment.

 

2

 

Connect battery /batteries to  

BATTERY

 

and 

BATTERY

 

-

 

terminals.  Although there is built in reverse 

polarity  protection,  under some circumstances reverse polarity connection will not only result in the 
rupture of the internal battery protection fuse but destroy the input circuitry of the unit.

 

3

 

The ECB and battery circuit may be tested at this point.   To close the 

ECB

 with no mains power pre-

sent, briefly short together the 

BATTERY

 

ve 

and 

LOAD

 

ve  

terminals.   The battery voltage will 

then appear at the load terminals, 

BATT LOW  

relay energises & 

BATT SYSTEM OK 

LED turns on.   The 

POWER OK 

LED stays on for about 30s.   Disconnect one battery lead briefly to open the ECB.

 

4

 

Connect load/s to 

LOAD

and 

LOAD

-

 

terminals.

 

5

 

To minimize the volt drop at the output connections always use all the terminals provided by linking 
them together.

 

6

 

Place temperature sensor probe near or on batteries.

 

7

 

Connect input power.  Charger should be fully operational at this stage.

 

ALARM & BCT RELAYS

 

 

Relay contacts shown in 

de

-

energised 

state (ie.  when there is a fault condition).

 

Alarm relays are 

energised

 when power supply is operating normally.   

BCT

 relay is energised when battery 

condition test is in progress.

 

OUTPUT FUSES/ MCB RATING

 

 

The battery circuit is the one which has the highest fault current potential and fuses/MCBs should be correctly 
rated for the wiring used.

 

FRONT PANEL LEDS 

(with built

-

in switches)

 

 

BATTERY SYSTEM OK:

 

LED on:

 

Battery present and above V batl.

 

 

 

Note: 

If the battery condition test function is enabled,  pushing this switch 

 

for approx. 2 sec will manually initiate a battery condition test.

 

 

POWER OK:

 

LED on:

 

Input power present

 

 

LED off:

 

No input power or charger in standby mode

 

 

STANDBY:

 

LED on:

 

Charger in standby mode (no output from charger)

 

 

Note: 

Push standby button to turn off charger, this allows load to run off bat

 

tery.  Push button again to turn on charger.

 

AUX

 

(BCT)

 

MAINS FAIL

 

(POWER OK)

 

BATTERY LOW

 

(BATT SYS OK)

 

COM

 

NC

 

NO

 

COM

 

NC

 

NO

 

COM

 

NC

 

NO

 

 

FG

 

ALARMS 

(refer to specific data sheets for operational details)

 

 

POWER OK:

 

Approx. 30 second delay before activation.

 

 

BATTSYS OK:

 

Battery detection alarm my take up to 60 minutes to activate during normal operation

 

Содержание SR250C

Страница 1: ...d 64 9 8350700 Sydney 61 2 9809 5022 Singapore 65 6871 4140 www heliosps com SR500C SR750C with optional V I meter shown SR250C User Manual SR250C SR500C SR750C No BreakTM DC UPS 15 09 2016 REFER TO B...

Страница 2: ...shortened lifetimes if subjected to high ambient temperatures Water Dust Every effort must be made in the installation to minimise the risk of ingress of water or dust Water will almost always cause...

Страница 3: ...tery circuit integrity Fast electronic battery overcurrent protection Deep discharge protection by disconnecting the load at low battery voltage Temperature compensated output voltage using external t...

Страница 4: ...anks Power OK YES Battery Missing YES Battery Low YES Battery Condition Test Fail YES Alarms Available 2 Peak load connection using 1 x No Break DC charger Use this connection when there is a connecte...

Страница 5: ...tteries 7 Connect input power Charger should be fully operational at this stage ALARM BCT RELAYS Relay contacts shown in de energised state ie when there is a fault condition Alarm relays are energise...

Страница 6: ...eshold for battery detection and BCT Note that if the voltage drops to this level during a BCT the test is aborted and the BAT LOW SYS alarm shows Vshutd Internal voltage level of the power supply dur...

Страница 7: ...al System Normal Input power on battery circuit is OK Normal Normal Battery detection in progress Alarm Normal Input power on battery system fault 1 Internal battery fuse has opened or 2 Battery circu...

Страница 8: ...ve is also activated for the low voltage disconnect function on mains fail no input power It will reset when input power is restored or can be manually reset by briefly shorting the BAT and LOAD termi...

Страница 9: ...Specifications are subject to change without notice No liability accepted for errors or omissions 9 This page is intentionally blank...

Страница 10: ...open circuit to 100 load 1 output voltage 0 03 C 20 ms without battery nominal max Vin 1 sec Yes self resetting Over voltage protection on output at 130 of nominal output voltage CISPR 22 EN55022 cla...

Страница 11: ...eak load on mains fail A SR250C12 13 8 18 0 18 0 12 0 27 SR250C24 27 6 9 0 9 0 5 0 13 5 SR250C30 34 5 7 2 7 2 3 7 10 8 SR250C36 41 4 6 0 6 0 3 0 9 SR250C48 55 2 4 5 4 5 2 0 6 7 MODELS MODEL TABLE rati...

Страница 12: ...uit to 100 load 1 output voltage 0 03 C 20 ms without battery nominal max Vin 2 sec Yes self resetting Over voltage protection on output at 130 of nominal output voltage to CISPR 22 EN55022 class A to...

Страница 13: ...May be fitted with SR500 in 19 rack add SR METER or SR METERV2 SHUNT Charger may be fitted into enclosure with MCBs and terminals Code SEC SR Use external output diode eg P50 Add code INT METER Ethern...

Страница 14: ...uit to 100 load 1 output voltage 0 03 C 20 ms without battery nominal max Vin 2 sec Yes self resetting Over voltage protection on output at 130 of nominal output voltage to CISPR 22 EN55022 class A to...

Страница 15: ...for S versions OPTIONS 19 Rack Mount Digital V I meter Wall Mount Enclosure Parallel redundancy Internal V I Meter Communications Port SR750i MODEL IDENTIFICATION CODES 2U sub rack option add SR RM2U...

Страница 16: ...ip defects Liability under this warranty is limited to the replacement or repair of the defective product as long as the prod uct has not been damaged through misapplication negligence or unauthorized...

Отзывы: