Room sensor
KWL-VOC eC
Installation and operating instructions
Any use other than the intended use is prohibited!
1.8 Functionality
The air quality is detected by KWL-VOC eC (mixed gas sensor for volatile organic
substances). This sensor determines the loading of the room air due to contami-
nated gases such as cigarette smoke, body perspiration, exhaled breathing air,
solvent vapours, emissions, etc.
2.1 Technical data
KWL-VOC eC
Dimensions (W x H x D) mm
98 x 98 x 32,6 mm
Power supply
24 V AC ⁄ DC (± 10 %)
Power consumption
0.6 W ⁄ 24 V DC;
peak current 200 mA
Sensor
VOC sensor (metal oxide) (VOC = volatile
organic compounds), with manual calibration
(via zero button), with automatic calibration
(permanently active)
Output
Bus output with offset potentiometer
(± 10 % of the measuring range)
Measuring accuracy
± 20 % of final value (referred to calibrating gas)
Service life
> 60 months (under normal load conditions),
depending on the type of loading and gas
concentration
Gas exchange
by diffusion
Ambient temperature
0...+ 50 °C
Warm up time
approx. 1 hour
Response time
approx 1minute
Electrical connection
0.14 - 1.5 mm
2
, via screw terminals
Housing
plastic, material ABS, colour pure white (simi
lar to RAL 9010)
Installation
wall mounting or on in-wall flusch box, Ø 55
mm, base with 4-hole for mounting on vertically
or horizontally installed in-wall flush boxes for
cable entry from the back, with predetermined
breaking point for on-wall cable entry from top ⁄
bottom in case of plain on-wall installation
Protection class
III (according to EN 60 730)
Protection type
IP 30 (according to EN 60 529)
Standards
CE conformity, electromagnetic compatibility
according to EN 61 326, EMC
Directive 2014 ⁄ 30 ⁄ EU, Low Voltage Directive
2014 ⁄ 35 ⁄ EU
The recommended installation height for the room sensor KWL-VOC eC is between
1.4 and 1.5 m, persons who are usually standing and sitting are considered equally
at this height.
The room sensor KWL-VOC eC can also be installed at a different height if the specific
spatial conditions do not allow the recommended installation height.