background image

14

Smoke exhaust fan control system – 

EVS

Installation and Operating Instructions

PE

L3

L2

L1

1

-X1

1
2

3
4

5
6

-Q5

-F3

D02 10A

 

2 3

95

96

0,39A

ZE-0,4

-F4

2 4 6

97

98

4

PE

5

-X1

-F5

D02 10A

6 7

95

96

0,39A

ZE-0,4

-F6

2 4 6

97

98

8

PE

PE

N

N

L3

L2

L1

1
2

3
4

5
6

-Q6

1
2

3
4

5
6

-Q5

-F3

D02 10A

95

96

0,7A

ZE-1,0

-F4

 

2 4 6

97

98

-F5

D02 10A

95

96

0,7A

ZE-1,0

-F6

2 4 6

97

98

1

-X1

2

N

3

PE

4

-X1

1
2

3
4

5
6

-Q6

5

N

6

PE

U1 V1 W1

PE

3

M

Cooling air fan 

0,175kW / 0,39A

-W5 / * 4x1,5mm²

U1 V1 W1

PE

3

M

Cooling air fan 2 

0,175kW / 0,39A

-W6 / * 4x1,5mm²

L N

PE

0,16kW / 0,7A

Cooling air fan 1

1

M

-W5 / * 3x1,5mm²

L N

PE

0,16kW / 0,7A

Cooling air fan 2

1

M

-W6 / * 3x1,5mm²

N

L01

KL

KL

-M1

-W4

Fan

-K2

11

12

11

14

95

96

-F4

6

6

10

10

2

2

8

8

1

1

9

9

7

7

R1

R1

-B1

-B2

4

4

3

3

4

4

5

5

13
14

-Q5

 

 

Air flow monitor 

SWE 

2x2x0,8mm

-W7

Air flow monitor 

SWE 

2x2x0,8mm

-W8

For 2 B KLG 500/1000, SWE 

(-B2) included in control 

system.

1

3

-X3

-X3

2

4

-K2

230V

A1

A2

11

12

11

14

21

22

21

24

21

22

21

24

-K2

N

St.1

L01

Cooling air fan 1 Cooling air fan 2

95

96

-F6

14
13

-Q6

-Q5

A1

A2

1

2

3

4

5

6

13

14

-Q6

A1

A2

1

2

3

4

5

6

14

13

Power unit for 1 or 2 cooling air fans B KLG 1000

Control system for 1 or 2 cooling air fans B KLG 1000 and B KLG 500

KLG

Connection in

control system

for KLG

Connection in

control system

for KLG

Connection in

control system

for KLG

Connection in

control system

for KLG

Wiring diagram Cooling air fan B KLG 500 and B KLG 1000 to EVS-SD

27

28

Control board

Motors prot.

Reset

To unlock 

Main switch off and 

reactivate.

1

2

1

2

Vers

: 25.10.2017

Issue

: 007

Power unit for 1 or 2 cooling air fans B KLG 500

   

EVS-SD

    EN    

Содержание EVS Series

Страница 1: ...ren Steuerung Smoke exhaust fan control system EVS für maschinelle Rauchabzugsanlagen for mechanical smoke extraction systems EN Helios Ventilatoren MONTAGE UND BETRIEBSVORSCHRIFT INSTALLATION AND OPERATING INSTRUCTIONS DE ...

Страница 2: ...hme Seite 2 2 4 Einlagerung Seite 2 KAPITEL 3 INSTALLATION Seite 3 3 0 Technische Daten Seite 3 3 1 Montage Seite 4 3 2 Elektrischer Anschluss Seite 4 3 2 1 Anschlussmöglichkeiten Seite 4 3 2 2 Anschlussleitungen Seite 5 3 2 3 Anschlusspläne Seite 6 KAPITEL 4 INBETRIEBNAHME Seite 23 4 0 Funktionen Seite 23 4 1 Anzeige und Bedienung Seite 24 4 2 Inbetriebnahme Seite 25 KAPITEL 5 INSTANDHALTUNG UND ...

Страница 3: ...chutz vor schweren herabfallenden Teilen und verhindern Ausrutschen auf rutschigem Untergrund Haarnetz Dient vorwiegend zum Schutz vor Erfassen von langen Haaren durch be wegliche Teile Für Einsatz Anschluss und Betrieb gelten besondere Bestimmungen bei Zweifel ist Rückfrage erforderlich Die Bundes sowie regionale Brand schutzverordung ist zu beachten Weitere Informationen sind den einschlä gigen ...

Страница 4: ...Be und Entlüftungsfunktion Entrauchungsventilatoren mit Doppelfunktion Ein bestimmungsfremder Einsatz ist nicht zulässig 2 0 Gewährleistung und Haftungsansprüche Alle Ausführungen dieser Montage und Betriebsvorschrift müssen beachtet werden sonst entfällt die Gewährleistung Gleiches gilt für Haftungsansprüche an Helios Der Gebrauch von Zubehörteilen die nicht von Helios empfohlen oder angeboten we...

Страница 5: ... 40 C 0 C bis 40 C 0 C bis 40 C 0 C bis 40 C 0 C bis 40 C Schutzart IP54 IP54 IP54 IP54 IP54 Nennleistung Type Material Abmessungen HxBxT Schutzart Schutzklasse 4 kW EVS W EVS D EVS FUEC Kunststoff 320 x 240 x 130 IP54 II 4 kW EVS SD EVS DA Kunststoff 400 x 320 x 130 IP54 II 5 5 kW EVS SD EVS DA Kunststoff 400 x 320 x 190 IP54 II 7 5 kW EVS SD EVS DA Kunststoff 400 x 320 x 190 IP54 II 11 kW EVS SD...

Страница 6: ...andardmäßig bis zu 20 Druckknopfmelder in einer Melderlinie angeschlossen werden Bei Melderbetätigung wird der Entrauchungsbetrieb ausgelöst und der Alarm gespeichert Die Meldeschleife wird auf Drahtbruch und Kurzschluss über wacht Bei Unterbrechung der Verbindungsleitung und bei Kurzschluss wird eine Störmeldung ausgegeben Eine Rücksetzung des Alarms kann direkt am Druckknopfmelder erfolgen Die R...

Страница 7: ...paraten Lastteil und einen be reits integrierten Luftströmungswächter für den Betrieb des Radial Kühlluftgebläses Eine Überbrückung der Überwachungsfunktion durch den Luftströmungswächter und die Abschaltung der Schutzeinrichtung im Brandfall ermöglichen das Erreichen der maxima len Dauer der Entrauchungsfunktion bis zur Zerstörung des Entrauchungsventilators Es gibt eine separate Steuerbaugruppe ...

Страница 8: ... x 4 0 mm EVS SD bis 11 kW 35 A 5 x 6 0 mm 2 x 4 x 6 0 mm EVS SD bis 15 kW 50 A 5 x 10 0 mm 2 x 4 x 10 0 mm EVS SD bis 18 5 kW 63 A 5 x 16 0 mm 2 x 4 x 16 0 mm EVS SD bis 22 kW 80 A 5 x 25 0 mm 2 x 4 x 25 0 mm EVS SD bis 30 kW 100 A 5 x 35 0 mm 2 x 4 x 35 0 mm EVS SD bis 45 kW 125 A 5 x 50 0 mm 2 x 4 x 50 0 mm EVS SD bis 55 kW 160 A 5 x 70 0 mm 2 x 4 x 70 0 mm EVS DA bis 4 00 kW 20 A 5 x 2 5 mm 2 ...

Страница 9: ...7 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS D DE ...

Страница 10: ...8 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS D DE ...

Страница 11: ...9 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS D DE ...

Страница 12: ...10 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS D DE ...

Страница 13: ...11 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS SD DE ...

Страница 14: ...12 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS SD DE ...

Страница 15: ...13 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS SD DE ...

Страница 16: ...14 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS SD DE ...

Страница 17: ...15 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS DA DE ...

Страница 18: ...16 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS DA DE ...

Страница 19: ...17 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS DA DE ...

Страница 20: ...18 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS DA DE ...

Страница 21: ...19 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS W DE ...

Страница 22: ...20 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS W DE ...

Страница 23: ...21 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS W DE ...

Страница 24: ...ntrauchung N N 45 46 43 44 Freig Lüftung 60 61 Taster drücken direkt DKM BMZ 1sec RMR 3sec FWS Entrauchung Steuerung AUS FWS Off Sperre 19 20 21 14 16 15 Lüftungsfunktion Rauchmelder Druckknopfmelder Rückmeldung Revisionsschalter Schalter Taster Rep Alarm Alarm Betrieb Betrieb Störung Störung Rev Schalter RS 3 1 2x2x0 8mm geschirmt W9 Angegebene Leitungstypen und Dimensionen sind Mindestanforderun...

Страница 25: ... Hochlaufzeit EVS SD Der Antriebsmotor des Entrauchungsventilators wird zur Belastungsminimierung der bauseitigen Stromversorgung bei der EVS SD immer über Stern Dreieck eingeschaltet Die Hochlaufzeit des Stern Dreieck Anlaufs lässt sich an dem integrierten Zeitrelais zwischen 1 5 und 30 Sek einstellen Hierzu sind Einstellungen an den beiden Drehschaltern Range Zeitbereich und Time Zeitfenster vor...

Страница 26: ...eit leuchtet Bei Auslösung einer externen Entrauchungsmeldung wird der Entrauchungsbetrieb ausgelöst wie unter Entrauchung beschrieben Der Entrauchungsventilator kann in dieser Schaltstellung im Lüftungsbetrieb auch über eine angeschlossene Fernschaltstelle z B Wochenzeiltschaltuhr WSUP ge schaltet werden wie unter EIN oder St 1 St 2 beschrieben Lüftung Ein Lftg Ein oder Lüftung Stufe 1 und Stufe ...

Страница 27: ...lter einschalten Stellung 1 Betriebsartschalter auf EIN schalten Bei Entrauchungsbetrieb läuft der Entrauchungsventilator ohne Motorschutz Den Drehschalter niemals sofort auf Entrauchung schalten Bei Inbetriebnahme im Entrauchungsmodus ist die zulässige Motor Einschaltanzahl pro Stunde zu beachten da sonst wegen der überbrückten Motorschutzorgane der Antriebsmotor zerstört werden kann Die LED der ...

Страница 28: ...ten sind in den Prüfverordnungen der Länder geregelt Fristen für Funktionskontrollen sowie Prüfungen und Wartungen sind darüber hinaus entsprechend der Vorgaben im Helios Prüf und Wartungsplan zwingend einzuhalten Eine Funktionskontrolle oder Prüfung und Wartung umfasst neben der eigentlichen Anlage auch alle Zubehörkomponenten die Energieversorgung und Ansteuerungen etc Alle Funktionskontrollen P...

Страница 29: ...ckzusetzen Schalter ON Auslösung über die Brandmeldeanlage nicht selbsthaltend OFF Auslösung über die Brandmeldeanlage selbsthaltend Schalter DKM Melderschleife für rastende oder tastende Druckknopfmelder Drahtbruch Auslösung Einstellung für Analogausgang an Klemme 25 26 Drehpoti St 1 Einstellung Ausgangsspannung 0 5 V für Lüftungsstufe 1 St 2 Einstellung Ausgangsspannung 5 10 V für Lüftungsstufe ...

Страница 30: ... entriegeln Leitung überpürfen Anschließend Meldung über Taster TK KL Reset quittieren Gelbe Diagnose LED erlischt wenn kein Motorschutzorgan angeschlos sen Brücke entriegeln RepSW Fuse Steuersicherung F1 F2 gefallen Reparaturschalter wurde geschalten oder Drahtbruch zwischen Klemme 29 30 Ausgelöste Steuersicherung erset zen Gelbe Diagnose LED erlischt Reparaturschalter bzw Leitung überprüfen Wenn...

Страница 31: ...on mechanische Belastung Ermüdung und oder durch andere nicht unmittelbar erkennbare Einwirkungen sind nach erfolgter Demontage entsprechend den nationalen und internationalen Gesetzen und Vorschriften fach und sachgerecht zu entsorgen Das Gleiche gilt für im Einsatz befindliche Hilfsstoffe wie Öle und Fette oder sonstige Stoffe Die bewusste oder unbewusste Weiterverwendung verbrauchter Bauteile w...

Страница 32: ...age 2 2 4 Storage Page 2 CHAPTER 3 INSTALLATION Page 3 3 0 Technical data Page 3 3 1 Installation Page 4 3 2 Electrical connection Page 4 3 2 1 Connection options Page 4 3 2 2 Connection cables Page 5 3 2 3 Wiring diagrams Page 6 CHAPTER 4 COMMISSIONING Page 23 4 0 Functions Page 23 4 1 Display and operation Page 24 4 2 Commissioning Page 25 CHAPTER 5 SERVICING AND MAINTENANCE Page 25 5 0 Function...

Страница 33: ...rves to protect against heavy falling parts and from slipping on slippery surfaces Hair net The hair net primarily serves to protect long hair against contact with mo ving parts Special regulations apply for use connection and operation of smoke venti lation fans Consultation is required in case of doubt The federal and regio nal fire protection regulations must be observed Further information can...

Страница 34: ...tion smoke exhaust fans with double function Any use other than the intended use is not permitted 2 0 Warranty claims and exclusions of liability All versions of this documentation must be observed otherwise the warranty shall cease to apply The same applies to liability claims against Helios The use of accessory parts which are not recommended or offered by Helios is not permitted Any possible da...

Страница 35: ...0 C to 40 C 0 C to 40 C Protection category IP54 IP54 IP54 IP54 IP54 Rated output Type Material Dimensions HxWxD Protection cat Prot class 4 kW EVS W EVS D EVS FUEC Plastic 320 x 240 x 130 IP54 II 4 kW EVS SD EVS DA Plastic 400 x 320 x 130 IP54 II 5 5 kW EVS SD EVS DA Plastic 400 x 320 x 190 IP54 II 7 5 kW EVS SD EVS DA Plastic 400 x 320 x 190 IP54 II 11 kW EVS SD EVS DA Plastic 400 x 320 x 190 IP...

Страница 36: ... and short circuits A fault signal is issued in case of an interruption of the connection cable or short circuit The alarm can be reset directly on the pushbutton alarm The alarm is reset by the preceding resetting of the triggered pushbutton alarm and subsequent resetting using the system reset When connecting pushbutton alarms to the EVS the position of the slide switch should be taken into acco...

Страница 37: ...tion by the air flow monitor and the deactivation of the protection device in case of fire allows the maximum smoke extraction function duration to be achieved until the destruction of the smoke exhaust fan There is a separate control unit for an AC cooling air fan and a three phase current cooling air fan EVS for smoke exhaust fans F600 with centrifugal cooling air fan Cooling air fan connection ...

Страница 38: ...5 A 5 x 6 0 mm 2 x 4 x 6 0 mm EVS SD up to 15 kW 50 A 5 x 10 0 mm 2 x 4 x 10 0 mm EVS SD up to 18 5 kW 63 A 5 x 16 0 mm 2 x 4 x 16 0 mm EVS SD up to 22 kW 80 A 5 x 25 0 mm 2 x 4 x 25 0 mm EVS SD up to 30 kW 100 A 5 x 35 0 mm 2 x 4 x 35 0 mm EVS SD up to 45 kW 125 A 5 x 50 0 mm 2 x 4 x 50 0 mm EVS SD up to 55 kW 160 A 5 x 70 0 mm 2 x 4 x 70 0 mm EVS DA up to 4 00 kW 20 A 5 x 2 5 mm 2 x 4 x 2 5 mm E...

Страница 39: ...21 14 16 15 Ventilation funct Smoke detector Pushbutton alarm Fan 1 Return signal Isolator switch Switch Button Rep Alarm Alarm Opera Opera Fault Fault Isol switch RS 3 1 2x2x0 8mm shielded W9 ye ye gn gn rd rd Vers 25 10 2017 Issue 006 Wiring diagram EVS D Note Valid for the connection of smoke extraction fans without PTC thermistor KL or thermal contact TK 2 Prev detector 1 10kW 10kW BMZ 2x2x0 8...

Страница 40: ... PE PE Op Cl Fault Ready Smoke extraction Control sys OFF FWS Off locked Signals 1 10kW Ref no 08255 004 Fireman s switch FWS2 4x2x0 8mm shielded W4 max no 6 19 20 21 14 16 15 Vers 25 10 2017 Issue 006 Wiring diagram EVS D Note Valid for the connection of smoke extraction fans with PTC thermistor KL Ventilation funct Smoke detector Pushbutton alarm Return signal Isolator switch Fan 1 Switch Button...

Страница 41: ...ing diagram EVS D Note Valid for the connection of smoke extraction fans with thermal contact TK Ventilation funct Smoke detector Pushbutton alarm Return signal Isolator switch Fan 1 Switch Button 23 22 2 Prev detector 1 10kW 10kW BMZ 2x2x0 8mm shielded W5 WSUP 2x2x0 8mm shielded W6 Ref no 08255 004 Fireman s switch FWS2 4x2x0 8mm shielded W4 max no 6 Ref no 04984 005 Smoke detector RMR 2x2x0 8mm ...

Страница 42: ...tion in control system B KLG 500 2x2x0 8mm 95 96 KL KL 27 28 Control board K2 11 12 11 14 Vers 25 10 2017 Issue 006 Wiring diagram Cooling air fan B KLG 500 to EVS D Power unit for 1 cooling air fan Motor prot Reset F4 6 10 2 8 1 9 7 R1 B1 4 3 4 5 13 14 Q3 Air flow monitor SWE 2x2x0 8mm W7 1 X3 2 K2 K1 K1 230V A1 A2 11 12 11 14 21 22 21 24 21 22 21 24 K2 N St 1 L01 Cooling air fan Q3 A1 A2 1 2 3 4...

Страница 43: ...onnection of smoke extraction fans without PTC thermistor KL or thermal contact TK Fan 1 Ventilation funct Switch Button Pushbutton alarm Return signal isolator switch Smoke detector 23 22 2 Prev detector 1 10kW 10kW BMZ 2x2x0 8mm shielded W5 WSUP 2x2x0 8mm shielded W6 Ref no 08255 004 Fireman s switch FWS2 4x2x0 8mm shielded W4 max no 6 Ref no 04984 005 Smoke detector RMR 2x2x0 8mm shielded W7 ma...

Страница 44: ... 3x1 5mm W11 M 1 PE Z A N PE PE PE Op Cl 1 10kW 19 20 21 14 16 15 Wiring diagram EVS SD Note Valid for the connection of smoke extraction fans with PTC thermistor KL Fan 1 Ventilation funct Smoke detector Pushbutton alarm Return signal isolator switch Switch Button 23 22 2 Prev detector 1 10kW 10kW BMZ 2x2x0 8mm shielded W5 WSUP 2x2x0 8mm shielded W6 Ref no 08255 004 Fireman s switch FWS2 4x2x0 8m...

Страница 45: ...5 Wiring diagram EVS SD Note Valid for the connection of smoke extraction fans with thermal contact TK Fan 1 Ventilation funct Smoke detector Switch Button Pushbutton alarm Return signal isolator switch 23 22 2 Prev detector 1 10kW 10kW BMZ 2x2x0 8mm shielded W5 WSUP 2x2x0 8mm shielded W6 Ref no 08255 004 Fireman s switch FWS2 4x2x0 8mm W4 max no 6 Ref no 04984 005 Smoke detector RMR 2x2x0 8mm shi...

Страница 46: ...10 2 2 8 8 1 1 9 9 7 7 R1 R1 B1 B2 4 4 3 3 4 4 5 5 13 14 Q5 Air flow monitor SWE 2x2x0 8mm W7 Air flow monitor SWE 2x2x0 8mm W8 For 2 B KLG 500 1000 SWE B2 included in control system 1 3 X3 X3 2 4 K2 230V A1 A2 11 12 11 14 21 22 21 24 21 22 21 24 K2 N St 1 L01 Cooling air fan 1 Cooling air fan 2 95 96 F6 14 13 Q6 Q5 A1 A2 1 2 3 4 5 6 13 14 Q6 A1 A2 1 2 3 4 5 6 14 13 Power unit for 1 or 2 cooling a...

Страница 47: ...ct DKM BMZ 1sec RMR 3sec FWS 1 10kW 19 20 21 14 16 15 Vers 25 10 2017 Issue 007 Wiring diagram EVS DA Note Valid for the connection of smoke extraction fans without PTC thermistor KL or thermal contact TK Fan 1 Ventilation funct Smoke detector Pushbutton alarm Return signal isolator switch Switch Button 2 Prev detector 1 10kW 10kW 4 BMZ 2x2x0 8mm shielded W5 WSUP 2x2x0 8mm shielded W6 Ref no 08255...

Страница 48: ...nnection of smoke extraction fans with PTC thermistor KL Switch Button 23 22 BMZ 8 9 ON BMZ autoRST BMZ BMZ 1 3 2 7kW 2 7kW 3 1 2 A selection can be made between stage 1 t 11 and stage 2 t 12 for two timers Stage2 Stage1 3 3 1 1 2 2 11 10 12 2 Prev detector 1 10kW 10kW 4 BMZ 2x2x0 8mm shielded W5 WSUP 2x2x0 8mm shielded W6 Ref no 08255 004 Fireman s switch FWS2 4x2x0 8mm shielded W4 max no 6 Ref n...

Страница 49: ...for the connection of smoke extraction fans with thermal contact TK Switch Button 23 22 BMZ 8 9 ON BMZ autoRST BMZ BMZ 1 3 2 7kW 2 7kW 3 1 2 A selection can be made between stage 1 t 11 and stage 2 t 12 for two timers Stage2 Stage1 3 3 1 1 2 2 11 10 12 2 Prev detector 1 10kW 10kW 4 BMZ 2x2x0 8mm shielded W5 WSUP 2x2x0 8mm shielded W6 Ref no 08255 004 Fireman s switch FWS2 4x2x0 8mm shielded W4 max...

Страница 50: ...3 14 Q4 Q2 Q5 A1 A2 1 2 3 4 5 6 13 14 Q6 A1 A2 1 2 3 4 5 6 14 13 Power unit for 1 or 2 cooling air fans B KLG 1000 Control system for 1 or 2 cooling air fans B KLG 1000 and B KLG 500 Connection in control system for KLG Connection in control system for KLG Connection in control system for KLG Connection in control system for KLG F1 F2 F5 F7 K2 95 95 95 95 96 96 96 96 11 14 12 Wiring diagram Coolin...

Страница 51: ...e 1 Stage 2 OnBoard diagnosis System reset 24 24VDC Lamp test 60 61 Press button direct DKM BMZ 1sec RMR 3sec FWS 1 10kW 19 20 21 14 16 15 Wiring diagram EVS W Note Valid for the connection of smoke extraction fans without PTC thermistor KL or thermal contact TK Fan 1 BMZ 2x2x0 8mm shielded W5 WSUP 2x2x0 8mm shielded W6 Ref no 08255 004 Fireman s switch FWS2 4x2x0 8mm shielded W4 max no 6 Ref no 0...

Страница 52: ...iring diagram EVS W Note Valid for the connection of smoke extraction fans with PTC thermistor KL Ventilation funct Switch Button 22 23 2 Prev detector 1 10kW 10kW BMZ 2x2x0 8mm shielded W5 WSUP 2x2x0 8mm W6 Ref no 08255 004 Fireman s switch FWS2 4x2x0 8mm shielded W4 max no 6 Ref no 04984 005 Smoke detector RMR 2x2x0 8mm shielded W7 max no 60 4 shielded Ein 2 1 3 4 5 7 6 8 1 3 4 5 6 8 2 1 3 4 5 7...

Страница 53: ...2017 Issue 006 Wiring diagram EVS W Note Valid for the connection of smoke extraction fans with thermal contact TK Switch Button 22 23 2 Prev detector 1 10kW 10kW BMZ 2x2x0 8mm shielded W5 WSUP 2x2x0 8mm shielded W6 Ref no 08255 004 Fireman s switch FWS2 4x2x0 8mm shielded W4 max no 6 Ref no 04984 005 Smoke detector RMR 2x2x0 8mm shielded W7 max no 60 4 Ein 2 1 3 4 5 7 6 8 1 3 4 5 6 8 2 1 3 4 5 7 ...

Страница 54: ...set System reset St 1 St 2 Smoke extr N N 45 46 43 44 Rel ventil 60 61 Press button direct DKM BMZ 1sec RMR 3sec FWS Smoke extraction Control sys OFF FWS Off locked 19 20 21 14 16 15 Ventilation funct Smoke detector Pushbutton alarm Return signal isolator switch Switch Button Rep Alarm Alarm Opera Opera Fault Fault Isol switch RS 3 1 2x2x0 8mm shielded W9 ye ye gn gn rd rd 2 Prev detector 1 10kW 1...

Страница 55: ...exhaust fan drive motor is always activated using the star delta start up for load minimisation on the on site power sup ply for the EVS SD The star delta start up time allows the integrated time relay to be set between 1 5 and 30 sec In this respect settings can be adjusted for both rotary switches Range time range and Time window The third rotary switch Function Function on the time relay is res...

Страница 56: ...will activate as described under Smoke extraction In this switch position the smoke exhaust fan can also be switched using a connected remote switching point in ventilation mode e g weekly autotimer WSUP as described under ON or St 1 St 2 Ventilation On Vent On or fan stage 1 and stage 2 St 1 St 2 Ventilation damper move to OPEN position The smoke exhaust fan is set to the selected peed in ventila...

Страница 57: ...motor starts in smoke extraction mode must be taken into account during commissio ning as otherwise the drive motor could be destroyed due to the bridged motor protection devices The EVS LEDs Operation and Ready must light up Check motor for correct direction of rotation and observe the installation and operating instructions for the smoke exhaust fan in the process Measure and compare actual moto...

Страница 58: ...ore the intervals for functional inspections tests and maintenance must be observed according to the specifications in the Helios test and maintenance plan A functional inspection test and maintenance also includes all accessory components the power supply and controls etc in addition to the actual system All functional inspections tests and maintenance must be recorded in a logbook and measured r...

Страница 59: ...o reset signal Switch ON Trigger via the fire alarm system not self holding OFF Trigger via the fire alarm system self holding Switch DKM Detector circuit for latching or spring return pushbutton alarm wire breakage trigger Setting for analogue output to terminal 25 26 Rot poti St 1 Setting output voltage 0 5 V for fan stage 1 St 2 Setting output voltage 5 10 V for fan stage 2 and smoke extraction...

Страница 60: ... LED goes out if no motor protection connected unlock jumper RepSW Fuse Control fuse F1 F2 dropped Repair switch has been switched or wire breakage between terminal 29 30 Replace triggered control fuse Yellow diagnosis LED goes out Check repair switch or cable If no repair switch connected insert jum per Yellow diagnosis LED goes out Alarm SysOFF Control system locked via input terminal 31 32 Cont...

Страница 61: ...sposed of expertly and properly after disassembly in accordance with the national and international laws and regulations The same also applies to auxiliary materials in use Such as oils and greases or other substances The intended and unintended further use of worn parts e g impellers rolling bearings filters etc can result in danger to persons the environment as well as machines and sys tems The ...

Страница 62: ...30 Smoke exhaust fan control system EVS Installation and Operating Instructions ...

Страница 63: ...31 Smoke exhaust fan control system EVS Installation and Operating Instructions ...

Страница 64: ...4 8112 Otelfingen GB HELIOS Ventilation Systems Ltd 5 Crown Gate Wyncolls Road Severalls Industrial Park A HELIOS Ventilatoren Postfach 854 Siemensstraße 15 6023 Innsbruck Colchester Essex CO4 9HZ www heliosventilatoren de Als Referenz am Gerät griffbereit aufbewahren Druckschrift Nr Please keep this manual for reference with the unit Print No Conservez cette notice à proximité de l apapreil N Réf...

Отзывы: