Central ventilation unit –
KWL 200/300 W/W ET
Installation and Operating Instructions
EN
EN
34
8.3.2 Heat exchanger cleaning
m
Risk of burns due to hot surfaces!
Hot surfaces can cause serious burns.
> Allow unit to cool down for at least 5 minutes or wait until the fans are turned off.
m
Risk of injury due to rotating fans!
Rotating fans can injure limbs and cause serious injuries.
> Before working on the unit, wait until the fans are turned off.
m
Risk of injury due to the unit door falling down!
The unit door can fall down when removing and cause serious injuries.
> Wear protective footwear.
> Carefully remove the unit door with both hands.
1. Open both upper snap-in hooks on the unit door.
2. Remove the unit door.
m
Risk of injury due to the high weight of the heat exchanger!
The heat exchanger can fall down and cause serious injuries when removed from the unit.
> Wear protective footwear.
> Carefully remove the heat exchanger from the unit with both hands.
3. Remove terminal strip
ò
at top of heat exchanger (see Fig. 53).
4. Carefully remove the heat exchanger
ù
Damage to the heat exchanger due to the use of aggressive cleaning agents.
Aggressive cleaning agents can damage the heat exchanger.
> Do not use aggressive cleaning agents.
5. Clean the heat exchanger with a vacuum cleaner with a brush nozzle or with water.
6. During installation, place the heat exchanger
ù
on the guide rail and push up to the stop. Ensure that the receptacle
seals are not damaged!
7. Re-insert the terminal strip
ò
.
8. Re-attach the unit door and close with the snap-in hooks.
8.4 Condensate drain maintenance
The condensate drain must be checked for functionality and, if necessary, replaced as needed and at least every 6
months.
Carry out functional inspection as follows:
m
Risk of burns due to hot surfaces!
Hot surfaces can cause serious burns.
> Allow unit to cool down for at least 5 minutes or wait until the fans are turned off.
m
Risk of injury due to rotating fans!
Rotating fans can injure limbs and cause serious injuries.
> Before working on the unit, wait until the fans are turned off.
m
Risk of injury due to the unit door falling down!
The unit door can fall down when removing and cause serious injuries.
> Wear protective footwear.
> Carefully remove the unit door with both hand.
1. Open both upper snap-in hooks on the unit door.
2. Remove the unit door.
3. Pour some water into the condensation tray with a watering can.
4. Check whether the water drains via the condensate hose and clean the condensate drain, if necessary.
5. Re-attach the unit door and close with the snap-in hooks.
m
WARNING
m
WARNING
m
m
WARNING
m
m
WARNING
Fig. 53
ò
ù
ATTENTION
m
WARNING
m
WARNING
m
m
WARNING
Содержание easyControls 3.0 KWL 200 W
Страница 37: ...Zentrales Lüftungsgerät KWL 200 300 W W ET Montage und Betriebsvorschrift DE 36 ...
Страница 73: ...Central ventilation unit KWL 200 300 W W ET Installation and Operating Instructions EN 36 ...
Страница 109: ...Unité de ventilation centrale KWL 200 300 W W ET Notice de montage et d utilisation FR 36 ...
Страница 110: ...Unité de ventilation centrale KWL 200 300 W W ET Notice de montage et d utilisation FR 37 ...
Страница 111: ...Unité de ventilation centrale KWL 200 300 W W ET Notice de montage et d utilisation FR 38 ...