![Hekatron FSZ Pro Скачать руководство пользователя страница 24](http://html1.mh-extra.com/html/hekatron/fsz-pro/fsz-pro_instruction-manual_2120416024.webp)
24
9 Electrical Installation
Silent alarm – DIP 6
If the „silent alarm“ DIP switch 6 „ON“ is activated, alarm forwarding via the two relays is
prevented when the internal and external manual buttons are triggered. If the external alarm
input is triggered, alarm forwarding is not prevented! If the horn has not been deactivated, an
alarm is always acoustically signalled at the FSZ Pro. The magnet output is always switched off.
OFF
Silent alarm OFF
ON
Silent alarm ON
The „silent alarm“ has the function to enable the closing of the door with a manual but-
ton without triggering an alarm via the optical/acoustic alarm devices.
If „silent alarm“ is activated,
no
hold-open system
may
be activated via relay 1 and
relay 2.