11 Parameter description
Positioner DC 6-06
75
No. Name
Meaning
1700 ActuatorTestSetpoint
Level:
2
Range: 0..100
%
Page(s):
Setpoint for the control path in test mode for setting and
testing the actuator
1701
ActuatorTstAmplitude
Level:
2
Range: 0..100
%
Page(s):
Amplitude of the control path step generator in test
mode for setting and testing the actuator
1702
ActuatorTstFrequency
Level:
2
Range: 0..100
%
Page(s):
Frequency setting for test mode for setting and testing
the actuator
1800 Level
Level:
1
Range: 1..7
Page(s):
User level
Maximum level of the dongle or hand programmer,
can be reduced
1876 ValueStep
for hand programmers only
Level:
2
Range: 0..65535
Increment for value changes
1900 FeedbackAdjustTime
Level:
6
Range: 0..100
s
Page(s):
Position hold time with the auto adjust
1905 ServoCorrFactor
Level:
6
Range: 0..400
%
Page(s):
Correction factor of the PID value for servo loop
1906 ServoCorrRange
Level:
6
Range: 0..50
%
Page(s):
Position range for correction factor
1911 ServoGain
Level:
6
Range: 0..100
%
Page(s):
Proportional factor for the servo loop
1912 ServoStability
Level:
6
Range: 0..100
%
Page(s):
Integral factor for the servo loop
1913 ServoDerivative
Level:
6
Range: 0..100
%
Page(s):
Differential factor for the servo loop