10 Error handling
Positioner DC 6-06
69
Bit Meaning
0
Program identifier in the E
2
PROM is invalid, the program stays in
the bootloader, start is not possible
1
Operating data memory 2 in the E
1
PROM is invalid, the operating
data are cleared, start is possible
2
Operating data memory 2 in the E
2
PROM is invalid, the operating
data are cleared, start is possible
3
Serial number memory in the E
2
PROM is invalid, start is possible
4
Error memory in the E
2
PROM is invalid, the error memory is
cleared, start is possible
5
Parameter memory in the E
2
PROM is invalid, standard parameters
of the firmware are transferred, start is not possible
6
Exception memory in the E
2
PROM is invalid, start is possible
Action:
- Check data for correct settings,
- Restart control unit with
- Notify
HEINZMANN
.
Note:
The error only occurs after control unit reset. Bit 5 is signalled after each
program download.
3092 ErrConfiguration
3192 SErrConfiguration
Cause: Configuration
error
Reaction:
- System cannot be started.
- Control unit operates with standard parameters
Action:
- Check configuration for correct settings,
- Restart control unit with
Reference: