State list of the corresponding equipment ID, If it is on Host or extension host, you can
double click to see it’s details. Please see below.
:
Above picture please see below instruction.
“online” means device online
;
“offline” means device offline
,
Please check whether there is a fault detection on line cable or no
device
;
“Normal” means device model is normal
;
“Fault” means device fault
;
“None” means the DIP on the host rear panel was forbidden to the function. In other wor ds,
system function without configuration
;
“Open” mean speaker or CIE detection loop is open. In other words, system detects the
impendence is more than 10%
-30% of the spe aker first time system
building
,
base
on“
”
《
can not designate error to single device or designated zone
》
or cable is
disconnect between device to CIE
(
if device input configuration is “Level mode”
);
“Short” means speaker or CIE is short circuit, that is detec ting the speaker loop impedance is
(
10%~30%
)
more than the one system first time building. Zone short circuit forbid to control
the zone(forbid the output automatically to protect the amplifier, until the failure recovery) or
cable short circuit between speaker and CIE
(
if device input configuration is “Level mode”
);
“CONTACT OUTPUT STAUS” Device relay contact output can be controlled by click. Its output
status can be programming by the contact event in the “Fire mode”
;