www.heinner.com 9000 BTU, 220-240V~50Hz
10
10. Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used in the searching for or
detection of refrigerant leaks. A halide torch (or any other detector using a naked flame)
shall not be used.
11. Leak detection methods
The following leak detection methods are deemed acceptable for systems containing
flammable refrigerants. Electronic leak detectors shall be used to detect flammable
refrigerants, but the sensitivity may not be adequate, or may need re-calibration.
(Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the
detector is not a potential source of ignition and is suitable for the refrigerant used. Leak
detection equipment shall be set at a percentage of the LFL of the refrigerant and shall
be calibrated to the refrigerant employed and the appropriate percentage of gas (25 %
maximum) is confirmed. Leak detection fluids are suitable for use with most refrigerants
but the use of detergents containing chlorine shall be avoided as the chlorine may react
with the refrigerant and corrode the copper pipework. If a leak is suspected, all naked
flames shall be removed/ extinguished.
If a leakage of refrigerant is found which requires brazing, all of refrigerant shall be
recovered from the system, or isolated (by means of shut off valves) in a part of the
system remote from the leak.
Oxygen free nitrogen (OFN) shall then be purged through the system both before and
during the brazing process.
12. Removal and evacuation
When breaking into the refrigerant circuit to make repairs or for any other purpose
conventional procedures shall be used. However, it is important that best practice is
followed since flammability is a consideration. The following procedure shall be adhered
to: remove refrigerant; purge the circuit with inert gas; evacuate; purge again with inert
gas; open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders. The system
shall be flushed with OFN to render the unit safe. This process may need to be repeated
several times. Compressed air or oxygen shall not be used for this task. Flushing shall be
achieved by breaking the vacuum in the system with OFN and continuing to fill until the
working pressure is achieved, then venting to atmosphere, and finally pulling down to a
vacuum. This process shall be repeated until no refrigerant is within the system. When
the final OFN charge is used, the system shall be vented down to atmospheric pressure
to enable work to take place. This operation is absolutely vital if brazing operations on
the pipework are to take place. Ensure that the outlet for the vacuum pump is not close
to any ignition sources and there is ventilation available.
13. Charging procedures
In addition to conventional charging procedures, the following requirements shall be
followed. Ensure that contamination of different refrigerants does not occur when using
charging equipment. Hoses or lines shall be as short as possible to minimise the amount
of refrigerant contained in them.
Содержание HPAC-09WH
Страница 29: ...www heinner com 9000 BTU 220 240V 50Hz 28 Atentie Risc de incendiu materiale inflamabile...
Страница 54: ...www heinner com 9000 BTU 220 240V 50Hz 53 HPAC 09WH www heinner com 9000 BTU...
Страница 55: ...www heinner com 9000 BTU 220 240V 50Hz 54 III IV...
Страница 56: ...www heinner com 9000 BTU 220 240V 50Hz 55...
Страница 57: ...www heinner com 9000 BTU 220 240V 50Hz 56 III...
Страница 58: ...www heinner com 9000 BTU 220 240V 50Hz 57 1 T 3 15A 250V 8...
Страница 59: ...www heinner com 9000 BTU 220 240V 50Hz 58...
Страница 60: ...www heinner com 9000 BTU 220 240V 50Hz 59 R290 1 CO2 2 3...
Страница 62: ...www heinner com 9000 BTU 220 240V 50Hz 61 R32 R290 1 2 3 4 5 6 Verific rile locale...
Страница 63: ...www heinner com 9000 BTU 220 240V 50Hz 62...
Страница 64: ...www heinner com 9000 BTU 220 240V 50Hz 63 7 A 8 9...
Страница 65: ...www heinner com 9000 BTU 220 240V 50Hz 64 10 11 25 12 13...
Страница 66: ...www heinner com 9000 BTU 220 240V 50Hz 65 14 80 15 16...
Страница 67: ...www heinner com 9000 BTU 220 240V 50Hz 66...
Страница 69: ...www heinner com 9000 BTU 220 240V 50Hz 68 COOL FAN DRY 30 50...
Страница 70: ...www heinner com 9000 BTU 220 240V 50Hz 69...
Страница 71: ...www heinner com 9000 BTU 220 240V 50Hz 70 VI INFORMA II REFERITOARE LA ELECTRICITATE...
Страница 72: ...www heinner com 9000 BTU 220 240V 50Hz 71 VII...
Страница 74: ...www heinner com 9000 BTU 220 240V 50Hz 73 P1...
Страница 76: ...www heinner com 9000 BTU 220 240V 50Hz 75 3 3 3 5 8 3 4...
Страница 77: ...www heinner com 9000 BTU 220 240V 50Hz 76 X 2 P1 FAN 12...
Страница 78: ...www heinner com 9000 BTU 220 240V 50Hz 77...
Страница 79: ...www heinner com 9000 BTU 220 240V 50Hz 78 P1 COOL E0 EEPROM XI...
Страница 83: ...www heinner com 9000 BTU 220 240V 50Hz 82 Vigy zat T zvesz ly gy l kony anyagok...
Страница 108: ...www heinner com 9000 BTU 220 240V 50Hz 107...