SSelect input value 1
Setting range depends on measuring range [V / mA]
Select display value for INP.01.
Setting range -199999 … +999999 and decimal point.
Select input value
10
Setting range depends on measuring range [V / mA]
Select display value for
INP.
.
10.
Setting range -199999 … +999999 and decimal point.
Select input high value
Setting range depends on measuring range [V / mA]
Select display value for I
I
NP.HI.
Setting range -199999 … +999999 and decimal point.
x
A maximum of 12 linearization points is possible.
x
An input value INP must be entered for each linearization point (LP)
(input of the sensor value from the analog input in physical units)
as well as the corresponding display value DISP for this sensor value.
x
The linearization points (LP) may be entered in any order. They are then sorted in the
firmware in ascending order for the linearization function.
x
Linearization based on a negative slope is possible.
x
The setting range depends on the selected measuring range:
0 … 10 V
=
-0.500 … 10.500 [V]
2 … 10 V
=
1.500 … 10.500 [V]
-10 … +10 V
=
-10.500 ... +10.500 [V]
0 … 20 mA
=
-0.500 … 21.000 [mA]
4 … 20 mA
=
3.000 … 21.000 [mA]
x
The functions LO.LIM and HI.LIM limit the editable range.
The value for HI.LIM must always be greater than the value for LO.LIM
.