44.4. Additional Parameters for Preselections and Switching Outputs
(model
$
The following additional settings for the Preselections appear in the Basic Menu:
Menu
Default
Switching Characteristics of Output 1
Greater/Equal. Output to switch statically ON
when Display Value
Preselection1
Lower/Equal. Output to switch statically ON
when Display Value
Preselection1
Greater/Equal. Output to switch dynamically ON
when Display Value
Preselection1
(timed output pulse) *)
Lower/Equal. Output to switch dynamically ON
when Display Value
Preselection1
(timed output pulse) *)
Switching Characteristics of Output 2
See above, but Preselection2
See above, but Preselection2
See above, but Preselection2
See above, but Preselection2
Output to switch statically ON when
Display Value
Preselection1 – Preselection2 **)
Output to switch dynamically ON when
Display Value
Preselection1 – Preselection2 **)
HYSt 1
Hysteresis 1
Adjustable hysteresis for output 1
Setting range 0 ... 99999 display units
0
HYSt 2
Hysteresis 2
Adjustable hysteresis for output 2
Setting range 0 ... 99999 display units
0
*)
Timed output pulses have a fixed duration of 500 msec (factory adjustable only)
**)
Trailing Preset to generate an anticipation signal with a fixed distance to the main signal