HEIL DLFBHC01K1A Скачать руководство пользователя страница 15

 328 014525201  

15

Specifications  subject to change without notice.

TROUBLESHOOTING (CON’T)

This unit has on

board diagnostics. Error codes are displayed on the wired remote controller and the outdoor unit microprocessor board with colored

LED lights. Table 10 explains the error codes on both.

Table 10—Malfunction Status Table Outdoor Multi

zone Sizes 30, 36, & 42

NAME OF MALFUNCTION

THE INDICATOR DISPLAY

INDOOR

DISPLAY

YELLOW LIGHT

RED LIGHT

GREEN LIGHT

Compressor runs

Flash once

Defrost

Flash twice

H1

Anti-freezing protection

Flash 3 times

E2

IPM protection

Flash 4 times

H5

AC over-current protection

Flash 5 times

E5

Over-burden protection

Flash 6 times

H4

Compressor exhaust high temperature protection

Flash 7 times

E4

Compressor overload protection

Flash 8 times

H3

Power protection

Flash 9 times

L9

EEPROM reads and write protection

Flash 11 times

Low PN voltage protection

Flash 12 times

PL

Over voltage protection for PN

Flash 13 times

PH

PFC protection

Flash 14 times

HC

PFC module temperature protection

Flash 15 times

oE

Low pressure protection

Flash 17 times

E3

High pressure protection

Flash 18 times

E1

Limit/decline frequency(electric current)

Flash 1 times

Frequency limit

(

exhaust)

Flash 2 times

Frequency limit(Over-burden)

Flash 3 times

Outdoor ambient sensor malfunction

Flash 6 times

F3

Outdoor tube sensor malfunction

Flash 5 times

F4

Exhaust sensor malfunction

Flash 7 times

F5

Attain the temperature of switch on

Flash 8 times

Frequency limit(power)

Flash 13 times

Outdoor fan malfunction

Flash 14 times

Frequency limit(PFC module temperature)

Flash 15 times

PFC module sensor malfunction

Flash 16 times

oE

Liquid pipe temperature sensor malfunction of A

Flash 17 times

Gas pipe temperature sensor malfunction of A

Flash 18 times

Liquid pipe temperature sensor malfunction of B

Flash 19 times

Gas pipe temperature sensor malfunction of B

Flash 20 times

Liquid pipe temperature sensor malfunction of C

Flash 21 times

Gas pipe temperature sensor malfunction of C

Flash 22 times

Liquid pipe temperature sensor malfunction of D

Flash 23 times

Gas pipe temperature sensor malfunction of D

Flash 24 times

Liquid pipe temperature sensor malfunction of E

Flash 25 times

Gas pipe temperature

sensor malfunction of E

Flash 26 times

Exit of the condenser tube sensor malfunction

Flash 27 times

Correspondence is normal

Flash 7 Times

(n = indoor

unit number)

Communication failure between indoor unit and outdoor unit

Often bright

(

indoor unit all Communication failure)

Indoor ambient sensor malfunction

F1

Indoor evaporate sensor malfunction

F2

Mode conflict

E7

Accept fluorine mode

Fo

Jumper cap malfunction protection

C5

Содержание DLFBHC01K1A

Страница 1: ...4 NOTE Read the entire instruction manual before starting the installation TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS LIST 3 SYSTEM REQUIREMENTS 4 DIMENSIONS INDOOR 5 CLEARANCES INDOOR 7 INS...

Страница 2: ...entifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe pract...

Страница 3: ...e Indoor Cassette Size Name Qty 12 18 Remote control 1 Battery 1 5V 2 Screw M4X25 2 GasketM6X 18X1 4 4 GasketM10X 30X2 5 10 Screw ST4 8X13 HC 4 Screw M6X25 4 Nut of Connector Pipe B Package 1 Pipe Con...

Страница 4: ...Power and Communication Wiring The main power is supplied to the outdoor unit The field supplied 14 3 power communication wiring from the outdoor unit to the indoor unit consists of four 4 wires and...

Страница 5: ...thout notice DIMENSIONS INDOOR Fig 2 Size 12 and 18 Cassette Dimensions Table 4 Dimensions Indoor SYSTEM SIZE 12 18 Height H in cm 9 1 23 1 9 1 23 1 Width W in cm 22 4 56 9 22 4 56 9 Depth D in cm 22...

Страница 6: ...s subject to change without notice DIMENSIONS INDOOR CONTINUED Fig 3 Size 24 Cassette Dimensions Table 5 Dimensions SYSTEM SIZE 24 Height H In CM 9 4 23 9 Width W In CM 33 1 84 1 Depth D In CM 33 1 84...

Страница 7: ...328 014525201 7 Specifications subject to change without notice CLEARANCES INDOOR Fig 4 Cassette Clearance...

Страница 8: ...tioner IMPORTANT To guarantee the good performance the unit must be installed by professional personnel according with this instruction 253 5in 650mm 224 9in 570mm 153 4in 400mm m m 0 7 5 n i 9 4 2 2...

Страница 9: ...6 in 4 mm Clamp Drain hose Sponge gray Fig 9 Drain Hose NOTE Drain Setup pipe S The install height of the drain raising pipe should less than 11 in 280 mm S The drain raising pipe should form a right...

Страница 10: ...l by turning it toward the direction pointed by the arrow see Fig 15 so the adjust board connects well to the ceiling 5 Tighten the screws until the thickness of the sealing material between the panel...

Страница 11: ...s 18 to 42 and powered by the Branch Box sizes 48 and 56 18K 0 18 1 72 24K 0 43 1 20 LEGEND FLA Full Load Amps CONNECTION DIAGRAMS 18 42 Fig 19 Connection Diagram Outdoor Multi zone Sizes 18 42 48 56...

Страница 12: ...g Align center of the pipes and or service valve Indoor unit tubing Flare nut Piping A150769 Fig 24 Align Pipe Center h Connect both the liquid and gas piping to the indoor unit i Tighten the flare nu...

Страница 13: ...pushing it twice again after finishing test operation SYSTEM CHECKS 1 Conceal the tubing where possible 2 Make sure that the drain tube slopes downward along its entire length 3 Ensure all tubing and...

Страница 14: ...on Viewing malfunction code through remote controller within 200s displayed directly on indoor display after 200s P8 Refrigerant lacking or blockage protection of system not available for residential...

Страница 15: ...uency limit Over burden Flash 3 times Outdoor ambient sensor malfunction Flash 6 times F3 Outdoor tube sensor malfunction Flash 5 times F4 Exhaust sensor malfunction Flash 7 times F5 Attain the temper...

Страница 16: ...ror Flash 20 times U1 U1 Compressor current protection Flash 21 times L9 L9 Compressor overload protection Flash 22 times H3 H3 Compressor discharge temperature protection Flash 23 times E4 E4 Lack of...

Страница 17: ...B Indoor unit C Branch Box 3 Indoor unit A Indoor unit B Indoor unit C Communication error between the main board and driving board P6 Communication error between the main board and testing board CE I...

Страница 18: ...18 328 014525201 Specifications subject to change without notice Copyright 2016 International Comfort Products Lewisburg Tennessee 37091 USA...

Отзывы: