13

Specifications  subject to change without notice.

START

UP

Test Operation

Perform a test operation after completing gas leak and electrical safety

check (see Fig. 26).

Fig. 26

 - 

Test Operation

1. Push the “ON/OFF” button on the Remote Control to begin test-

ing.

NOTE

:  A protection feature prevents air conditioner from being

activated for approximately 3 to 4 minutes.

2. Push MODE button, select COOLING, HEATING, FAN mode

to check that all functions work correctly.

3. To run the test using the manual button in the indoor unit:

(4.) Open front panel of the indoor unit;
(5.) Push the manual switch once to energize the unit.  The

set conditions of manual operation are as follows:

· Preset set point: 76

_

F (24

_

C)

· Fan speed: AUTO

· Discharge air direction: Pre

set position based on

operation in “Cool” or “Heat” mode.

4. Be sure to set manual switch to “OFF” (by pushing it twice

again) after finishing test operation.

SYSTEM CHECKS

1. Conceal the tubing where possible.
2. Make sure that the drain tube slopes downward along its entire

length.

3. Ensure all tubing and connections are properly insulated.
4. Fasten tubes to the outside wall, when possible.
5. Seal the hole through which the cables and tubing pass.

INDOOR UNIT

1. Do all Remote Control buttons function properly?
2. Do the display panel lights work properly?
3. Does the air deflection louver function properly?
4. Does the drain work?

Explain Following Items To Customer

(with the aid of the Owner’s Manual):

1. How to turn air conditioner on and off; selecting COOLING,

HEATING and other operating modes; setting a desired

temperature; setting the timer to automatically start and stop air

conditioner operation; and all other features of the Remote

Control and display panel.

2. How to remove and clean the air filter.
3. How to set air deflection louver.
4. Explain care and maintenance.
5. Present the Owner’s Manual and installation instructions to cus-

tomer.

Содержание DLFBHC01K1A

Страница 1: ...4 NOTE Read the entire instruction manual before starting the installation TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS LIST 3 SYSTEM REQUIREMENTS 4 DIMENSIONS INDOOR 5 CLEARANCES INDOOR 7 INS...

Страница 2: ...entifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe pract...

Страница 3: ...e Indoor Cassette Size Name Qty 12 18 Remote control 1 Battery 1 5V 2 Screw M4X25 2 GasketM6X 18X1 4 4 GasketM10X 30X2 5 10 Screw ST4 8X13 HC 4 Screw M6X25 4 Nut of Connector Pipe B Package 1 Pipe Con...

Страница 4: ...Power and Communication Wiring The main power is supplied to the outdoor unit The field supplied 14 3 power communication wiring from the outdoor unit to the indoor unit consists of four 4 wires and...

Страница 5: ...thout notice DIMENSIONS INDOOR Fig 2 Size 12 and 18 Cassette Dimensions Table 4 Dimensions Indoor SYSTEM SIZE 12 18 Height H in cm 9 1 23 1 9 1 23 1 Width W in cm 22 4 56 9 22 4 56 9 Depth D in cm 22...

Страница 6: ...s subject to change without notice DIMENSIONS INDOOR CONTINUED Fig 3 Size 24 Cassette Dimensions Table 5 Dimensions SYSTEM SIZE 24 Height H In CM 9 4 23 9 Width W In CM 33 1 84 1 Depth D In CM 33 1 84...

Страница 7: ...328 014525201 7 Specifications subject to change without notice CLEARANCES INDOOR Fig 4 Cassette Clearance...

Страница 8: ...tioner IMPORTANT To guarantee the good performance the unit must be installed by professional personnel according with this instruction 253 5in 650mm 224 9in 570mm 153 4in 400mm m m 0 7 5 n i 9 4 2 2...

Страница 9: ...6 in 4 mm Clamp Drain hose Sponge gray Fig 9 Drain Hose NOTE Drain Setup pipe S The install height of the drain raising pipe should less than 11 in 280 mm S The drain raising pipe should form a right...

Страница 10: ...l by turning it toward the direction pointed by the arrow see Fig 15 so the adjust board connects well to the ceiling 5 Tighten the screws until the thickness of the sealing material between the panel...

Страница 11: ...s 18 to 42 and powered by the Branch Box sizes 48 and 56 18K 0 18 1 72 24K 0 43 1 20 LEGEND FLA Full Load Amps CONNECTION DIAGRAMS 18 42 Fig 19 Connection Diagram Outdoor Multi zone Sizes 18 42 48 56...

Страница 12: ...g Align center of the pipes and or service valve Indoor unit tubing Flare nut Piping A150769 Fig 24 Align Pipe Center h Connect both the liquid and gas piping to the indoor unit i Tighten the flare nu...

Страница 13: ...pushing it twice again after finishing test operation SYSTEM CHECKS 1 Conceal the tubing where possible 2 Make sure that the drain tube slopes downward along its entire length 3 Ensure all tubing and...

Страница 14: ...on Viewing malfunction code through remote controller within 200s displayed directly on indoor display after 200s P8 Refrigerant lacking or blockage protection of system not available for residential...

Страница 15: ...uency limit Over burden Flash 3 times Outdoor ambient sensor malfunction Flash 6 times F3 Outdoor tube sensor malfunction Flash 5 times F4 Exhaust sensor malfunction Flash 7 times F5 Attain the temper...

Страница 16: ...ror Flash 20 times U1 U1 Compressor current protection Flash 21 times L9 L9 Compressor overload protection Flash 22 times H3 H3 Compressor discharge temperature protection Flash 23 times E4 E4 Lack of...

Страница 17: ...B Indoor unit C Branch Box 3 Indoor unit A Indoor unit B Indoor unit C Communication error between the main board and driving board P6 Communication error between the main board and testing board CE I...

Страница 18: ...18 328 014525201 Specifications subject to change without notice Copyright 2016 International Comfort Products Lewisburg Tennessee 37091 USA...

Отзывы: