background image

1. Insert from outside the room cable into left side of the wall

hole, in which the pipe has already existed.

2. Pull out the cable on the front side, and connect the cable

making a loop.

When connecting the cable, con

rm the terminal number of indoor and

outdoor units carefully. If wiring is not correct, proper operation
can not be carried out and will cause defect.

1. If the supply cord is damaged, it must be replaced by the manufacturer or its

service agent or a similar quali

ed person. The type of connecting wire is

H07RN-F.

2. If the fuse on PC board is broken please change it with the type of

3. The wiring method should be in line with the local wiring standard.
4. After installation, the power plug should be easily reached.

5. A breaker should be incorporated into

xed wiring. The breaker should be

all-pole switch and the distance between its two contacts should be not less

than 3mm.

T.3.15A/250VAC (Indoor).

Connecting wiring

  4G1.0mm

2

JS025-C2

JS035-C2

JS050-C2

JS025-A1

JS035-A1

JS050-A1

JS070-C2

JS026-D2

JS035-D2

Note:

To Outdoor unit

On Drainage

Check forInstallation and Test Run

Insert the cable from the back

ƽ

side of  the unit, then pull it out on the front side.

Loosen the screws and insert

ƽ

the cable ends fully into terminal block, then

tighten the screws.

Pull the cable slightly to

ƽ

make sure the cables have been properly inserted and

tightened.

After the cable connection,

ƽ

never fail to fasten the connected cable with the

wiring cover.

When connecting the cable after installing the indoor unit

When connecting the cable before installing the indoor unit

C o d e

in d ic a tio n

T ro u b le d e s c rip tio n

A n a lyze a n d d ia g n o s e

E 1

E 2

E 4

E 7

E 1 4

H e a t-e xc h a n g e
s e n s o r fa ilu re

In d o o r E E P R O M
e rro r

C o m m u n ic a tio n
fa u lt b e tw e e n
in d o o r a n d o u td o o r
u n its

In d o o r fa n m o to r
m a lfu n c tio n

O p e ra tio n h a lt d u e to b re a k in g
o f w ire in s id e th e fa n m o to r;
O p e ra tio n h a lt d u e to b re a k in g
o f th e fa n m o to r le a d w ire s ;
D e te c tio n e rro r d u e to fa u lty
in d o o r u n it P C B ;

In d o o r u n it- o u td o o r u n it s ig n a l
tra n s m is s io n e rro r d u e to w irin g
e rro r;
F a u lty P C B ;

F a u lty E E P R O M d a ta ;
F a u lty E E P R O M ;
F a u lty P C B ;

F a u lty c o n n e c to r c o n n e c tio n ;
F a u lty th e rm is to r;
F a u lty P C B ;

Room temperature 
sensor failure

The power source must be exclusively used for air

ƽ

conditioner.

In the case of installing an air conditioner in a moist place,

ƽ

please install

an ea

For installation in other places, use a circuit breaker as far

ƽ

as possible.

Pipe cutting is carried out with  a  pipe cutter and burs must be removed.

After inserting the

are nut,

aring work is carried out.

Power Source Installation

Cutting and Flaring Work of Piping

Flare tool for R410A

Conventional

are tool

Clutch-type

clutch-type(Rigid-type) Wing-nut type (Imperial-type)

A

0~0.5mm

1.0~1.5mm

1.5~2.0mm

rth leakage breaker.

Lean

Damage of

are

Partial

Too outside

Correct

Incorrect

On Drainage

It becomes

high midway.

The gap with the

ground is too small.

There is the bad

smell from a ditch

It waves.

The end is imm-
ersed in water.

Please install the drain hose so as to be downward slope without fail.

Please don’t do the drainage as shown below.

ƽ

ƽ

Please pour water in the drain pan of the indoor unit, and

ƽ

is carried out surely to outdoor.

In case that the attached drain hose is in a room, please

ƽ

apply heat

insulation to

Less than

5cm

con

rm that

drainage

it without fail.

Crack

Indoor unit

Check Items for Test Run

Gas leak from pipe connecting?

Heat insulation of pipe connecting?

Are the connecting wirings of indoor and outdoor

rmly

Is the connecting wiring of indoor and outdoor

rmly

xed?

Is drainage securely carried out?

Is the earth line securely connected?

Is the indoor unit securely

xed?

Is power source voltage abided by the code?

Is there any noise?

Is the lamp normally lighting?
Are cooling and heating (when in heat pump) performed normally?

Is the operation of room temperature regulator normal?

Please kindly explain to our customers how to

operate through the instruction manual.

inserted to the terminal block?

Ƶ

Put check mark

in boxes

Flare tooling die

1.Cut pipe

2.Remove burs

3.Insert the

are nut

4.Flare pipe

ƽ

ƽ

7

Содержание JS025-A1

Страница 1: ...przeczytanie niniejszej instrukcji obs ugi przed rozpocz ciem korzystania z klimatyzatora Instrukcj nale y zachowa na przysz o Urz dzenie wype nione jest czynnikiem R32 JS025 C2 JS035 C2 JS050 C2 JS0...

Страница 2: ......

Страница 3: ...j wiedzy je eli nad ich bezpiecze stwem b dzie czuwa a osoba odpowiedzialna za ich bezpiecze stwo lub zosta y one przeszkolone z zakresu bezpiecznej obs ugi urz dzenia i rozumiej zagro enia zwi zane z...

Страница 4: ...Polski Spis tre ci CZ CI I FUNKCJE 1 OBS UGA 2 MONTA URZ DZENIA WEWN TRZNEGO 5 KONSERWACJA 8 RODKI OSTRO NO CI 9 ROZWI ZYWANIE PROBLEM W 10...

Страница 5: ...sji IOS9 0 lub wy szej System Android wymaga wersji Android 5 0 lub wy szej Spos b konfiguracji Zeskanuj poni szy kod QR aby pobra APLIKACJ Intelligent Air Inne opcje pobierania Znajd APLIKACJ Intelli...

Страница 6: ...sk SLEEP Przycisk LOCK Blokuje klawiatur i wy wie tlacz LCD Przycisk LIGHT Kontroluje pod wietlenie wy wietlacza LED urz dzenia wewn trznego 18 Przycisk POWER ON OFF 19 Przycisk DRY 20 Przycisk TEMP 2...

Страница 7: ...zenia FAN W trybie FAN urz dzenie nie pracuje w trybie COOL ani HEAT ale tylko w trybie FAN Tryb AUTO nie jest dost pny w trybie FAN Ustawienie temperatury jest wy czone W trybie FAN tryb komfortowego...

Страница 8: ...sowanym do automatycznie wybranego trybu pracy Uruchomienie trybu komfortowego snu SLEEP Uruchomienie trybu komfortowego snu SLEEP Zatrzymanie trybu komfortowego snu SLEEP Zatrzymanie trybu komfortowe...

Страница 9: ...D E F 2014 53 EU RED 2014 517 EU F GAS 2009 125 EC ENERGY 2010 30 EU ENERGY 2006 1907 EC REACH maksymalna moc transmisji bezprzewodowej 20dBm zakres cz stotliwo ci transmisji bezprzewodowej 2400 2483...

Страница 10: ...b pary gdzie otwory wylotowe i wlotowe nie b d blokowane z z Miejsce atwe do osuszania gdzie rury b dzie mo na pod czy do urz dzenia zewn trznego z z Miejsce gdzie zimne powietrze mo e rozprzestrzenia...

Страница 11: ...60mm 3 4 60mm 60mm 60mm 60mm 60mm 60mm A 170mm C 130mm B 60mm D 47mm A 222mm C 165mm B 60mm B 60mm B 60mm D 41 5mm D 41 5mm JS025 A1 D 47mm JS035 A1 JS050 A1 JS025 C2 JS035 C2 JS026 D2 JS035 D2 JS050...

Страница 12: ...j cy skropliny powinien tworzy lekk pochy o ku do owi Nie nale y wykonywa odp ywu w spos b pokazany na poni szych rysunkach Nale y wla wod do kratki ciekowej urz dzenia wewn trznego i upew ni si e wod...

Страница 13: ...c specjalnego ma ego wspornika umieszczonego po prawej stronie obudowy urz dzenia wewn trznego 2 Usun filtr standardowy Lekko przesun zaczep w g r aby poluzowa filtr a nast pnie go wyj 4 Za o y filtr...

Страница 14: ...wania urz dzenia do przechowywania ywno ci dzie sztuki urz dze delikatnych hodowli lub uprawy Nie montowa urz dzenia w pobli u kominka ani innych urz dze grzewczych Nie umieszcza ro lin ani zwierz t n...

Страница 15: ...zpo rednie wiat o s oneczne U ywa zas on Czy w pomieszczeniu nie znajduje si zbyt wiele os b lub r de ciep a podczas pracy w trybie ch odzenia Nie zastawia ani nie zakrywa kratek klimatyzatora Nie wk...

Страница 16: ...connection must be incorporated in the Make sure installation is done according to local wiring regulation by professional persons A leakage explosion proof breaker must be installed Make sure ground...

Страница 17: ...ernet Smart mobile phone requires IOS or Android system IOS system must support IOS 9 0 or above Android system must support Android 5 0 or above Configuration method Scan the QR code below to downloa...

Страница 18: ...t and ow Vertical blade right air fl Air Purifying Filter Inlet inside Emergency Switch Horizontal flap adjust up and down air flow Don t adjust it manually Outlet Inlet grille 6 5 2 1 4 3 6 4 2 1 5 3...

Страница 19: ...mode controller will automatically memorize the previous set swing position Note Vertical flap Pos 1 Auto swing 1 Status display of air flow 2 Left and right air flow adjustment Pos 1 Pos 2 Pos 3 Pos...

Страница 20: ...leeping function will be cancelled the machine will be in the Operation Mode 1 In COOL DRY mode SLEEP operation starts SLEEP operation stops Approx 6hrs 1 hr Rises 1O C Rises 1O C Temp setting Unit st...

Страница 21: ...posed of correctly you will help to prevent potential negative cons equences for the environment and humen health Please contact the installer or local authority for more information Battery must be r...

Страница 22: ...disturbed Place possible to drain easily where piping can be conne cted with the outdoor unit Place where cold air can be spread in a room entirely Place nearby a power receptacle with enough space ar...

Страница 23: ...dhesive tape Left Left rear piping In case of left side piping cut away with a nipper the lid for left piping In case of left rear piping bend the pipes according to the piping direction to the mark o...

Страница 24: ...due to faulty indoor unit PCB Indoor unit outdoor unit signal transm ission error due to wiring error Faulty PCB Faulty EEPROM data Faulty EEPROM Faulty PCB Faulty connector connection Faulty therm i...

Страница 25: ...door unit using vacuum cleaner or flaping them lightly otherwise its performance will be affected the cool and dry conditions For Smart Use of The Air Conditioner Replacement of Air Purifying Filter T...

Страница 26: ...TION PROHIBITION PROHIBITION PROHIBITION Do not start or stop the operation by disconnecting Do not channel the air flow directly at people especially at infants or the aged Do not try to repair or re...

Страница 27: ...is it with the type of T 3 15A 250V outdoor broken change it with the type of T 25A 250V The refrigerating circuit is leak proof 1 Applicable ambient temperature range Specifications The machine is a...

Страница 28: ...ng unter Aufsicht einer f r ihre Sicherheit zust ndigen Person oder gem von dieser Person bergebenen Bedienungsanleitung des Ger tes erfolgt und diese Personen sich der Gefahren aus der Handhabung des...

Страница 29: ...DEUTSCH Inhaltsverzeichnis TEILE UND FUNKTIONEN 1 BEDIENUNG 2 MONTAGE DES INNENGER TS 5 WARTUNG 8 SICHERHEITSHINWEISE 9 PROBLEME UND URSACHEN 10...

Страница 30: ...0 oder h her ist n tig Android System Die Unterst tzung f r Android 5 0 oder h her ist n tig Konfigurationsmethode Scannen Sie den folgenden QR Code um die App Intelligent Air herunterzuladen Weitere...

Страница 31: ...msteuerung SWING 4 Anzeige der Ventilatorgeschwindigkeit 5 Anzeige der Sperre 6 Anzeige f r Timer Modus TIMER OFF TIMER ON 7 Temperaturanzeige Batterieaustausch Den Batteriedeckel entfernen 2 x AAA Ba...

Страница 32: ...in folgenden Betriebsarten arbeiten Zimmer temperatur Temperature instellung Timer Modus Ventilator geschwin digkeit Betriebs art ber 23 C 26 C Nein AUTO COOL Unter 23 C 23 C Nein AUTO HEAT Keine Ver...

Страница 33: ...Luftstromgeschwindigkeit vor der Aktivierung der Sleep Funktion auf hoch oder mittel eingestellt ist die niedrige Geschwindigkeit w hlen Wenn die Luftstromgeschwindigkeit bereits auf niedrig eingestel...

Страница 34: ...op ischen Vorschriften Niederspannungsrichtlinie 2014 35 EG Richtlinie ber die elektromagnetische Vertr glichkeit 2014 30 EG RoHS Die Produkte erf llen Anforderungen der EU Richtlinie 2011 65 EU des E...

Страница 35: ...ung eine Stelle an der das Innenger t die Signale der Fernbedienung empfangen kann wenn Leuchtstofflampen brennen Versorgungsquelle Vor dem Anschluss des Ger ts an die Stromversorgung die Netzspannung...

Страница 36: ...ichtung mit K ltemittel l einschmieren und die Rohre miteinander verbinden Die Verbindungsstelle mit b ndig anliegendem Isolationsmaterial absichern und mit Klebeband befestigen Das intern externe Net...

Страница 37: ...ialschraube A 0 0 5 mm 1 0 1 5 mm 1 5 2 0 mm Richtig Falsch Geneigt Flansch besch digt Bruch Teilweise Zu weit nach au en aufgegangen Abfluss Die Drainageleitung sollte leicht nach unten geneigt sein...

Страница 38: ...er rechte und linke Filter nicht korrekt eingesetzt werden k nnen Besch digungen die Folge sein 5 Das Einlassgitter schlie en Wenn das Ger t ber l ngere Zeit nicht benutzt wird den Netzschalter aussch...

Страница 39: ...den Luftauslass einf hren VERBOTEN VERBOTEN VERBOTEN Niemals das Klimager t durch Einstecken oder Herausziehen der Anschlussleitung ein oder ausschalten Niemals den Luftstrom direkt auf Personen rich...

Страница 40: ...r Vorh nge verwenden Befinden sich w hrend des K hlbetriebs zu viele W rmequellen oder zu viele Personen im Raum Sicherheitshinweise Das L ftungsgitter des Klimager ts nicht blockieren oder abdecken K...

Отзывы: