background image

12

Installation Instructions and Owner’s Manual

Unvented Natural Gas Vent Free Room Heaters

CLEANING AND MAINTENANCE

WARNING:

 Turn off heater and let cool before 

servicing. 

For maintenance of the inside cabinet or to access the burner 
and pilot assembly for cleaning or service. Remove the four 

screws(two located on each side) that secure the front shell 
to the unit (Figure 6). Gently lift up on the front shell to 

disengage the hooks and pull forward to remove it. You will 
now be able to access all of the internal components of the 
appliance.

CAUTION:

 You must keep control areas, burner and 

circulation air passageways of heater clean. Inspect these 
areas of heater before use. Have the heater inspected 
yearly by a qualified service person. Heater may need more 
frequent cleaning due to excess lent from carpeting, bedding 
material, pet hair, etc. 
Make sure grille guard is in place before running heater. If 
screen or grille guard is removed for servicing it must be 
replaced prior to operating the heater. 

WARNING:

 Failure to keep the primary air opening(s) 

of the burner(s) clean may result in sooting and 

property damage. 

CLEANING ODS/PILOT AND BURNER

• 

Use as vacuum cleaner, pressurized air or small soft 
bristled brush to clean.

CLEANING BURNER PILOT AIR HOLE INLET

We recommend that you clean the unit every 2,500 hours of 

operation or every three months. We also recommend that 
you keep the burner tube and pilot assembly clean and free 
of dust and dirt. To clean these parts we recommend using 
compressed air no greater than 30 psig.
This can be done by using a vacuum cleaner in the blow 
position or using compressed air in a can. If using canned air 

please follow the directions on the can. If you don’t follow 

directions on the can you could damage the burner or pilot 
assembly. In addition, the directions below should also be 
followed.

1.  Shut off the unit, including the pilot. Allow the unit 

to cool for at least thirty minutes.

2.  Inspect burner and pilot for dust and dirt.
3.  Blow air through the port/slots and holes in the 

burner.

A yellow tip on the pilot flame indicates dust and dirt in the 
pilot assembly. To clean the pilot assembly find the small pilot 
air inlet hole about two inches from where the pilot flame 

comes out of the pilot assembly (see figure 18). With the unit 

off, lightly blow air through the air inlet hole. You may blow 
through a drinking straw if compressed air is not available.

Pilot Air Inlet Hole

Pilot Assembly

Figure 18

CLEANING HEATER CABINET

Air passageways

• 

Use a vacuum cleaner or pressurized air to clean

Exterior

• 

Use a soft cloth dampened with a mild soap and 
water mixture. Wipe the cabinet to remove dust.

Содержание HSSVFBF20NGBT

Страница 1: ...llation and service must be performed by a qualified installer service agency or the gas supplier This is an unvented gas fired heater It uses air oxygen from the room in which it is installed Provisi...

Страница 2: ...lts should be alerted to the hazard of high surface temperature and should stay away to avoid burns or clothing ignition Young children should be carefully supervised when they are in the same room wi...

Страница 3: ...ximum 14 Inches of Water 14 Inches of Water 14 Inches of Water 14 Inches of Water Inlet Gas Pressure Minimum 7 Inches of Water 7 Inches of Water 7 Inches of Water 7 Inches of Water Electrical Rating B...

Страница 4: ...ose volume is less than 50 cubic feet per 1 000 Btu per hour 4 8 m3 per kW of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is no...

Страница 5: ...space because the actual Btu hr used is more than the maximum Btu hr the space can support You must provide additional fresh air Your options are as follows A Rework worksheet and the space of an adj...

Страница 6: ...ble alternative to test gauge connection Purchase a CSA AGA certified equipment shutoff valve from your dealer LOCATING HEATER This heater is designed to be mounted on the wall The heater can also be...

Страница 7: ...wall stud mounting locate one end of the mounting bracket over a wall stud WARNING Maintain minimum clearances shown in fig ure 7 If you can provide greater clearances from the floor and joining wall...

Страница 8: ...ING AWAY FROM WALL Installing Support Feet See figure 11 1 Lay heater onto table on its back with bottom edge overhanging table edge 2 Securely attach feet to bottom of heater using 2 self tapping scr...

Страница 9: ...ppliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of psi 3 5 kPa 2 Cap off open en...

Страница 10: ...ettle on the floor WHAT TO DO IF YOU SMELL GAS Shut off gas supply Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call you gas s...

Страница 11: ...HEATER 1 Turn off equipment shutoff valve 2 Turn control knob clockwise to the OFF position SHUTTING OFF BURNER ONLY PILOT STAYS LIT 1 Turn control knob clockwise to the PILOT IGN position THERMOSTAT...

Страница 12: ...lean CLEANING BURNER PILOT AIR HOLE INLET We recommend that you clean the unit every 2 500 hours of operation or every three months We also recommend that you keep the burner tube and pilot assembly c...

Страница 13: ...13 Installation Instructions and Owner s Manual Unvented Natural Gas Vent Free Room Heaters PAGE LEFT INTENTIONALLY BLANK...

Страница 14: ...d by any metal or tubing Keep igniter cable dry Broken igniter cable Replace igniter cable Bad Piezo igniter Replace control valve Low Battery Replace battery When igniter button is pressed in there i...

Страница 15: ...irty or partially clogged burner orifice Clean burner orifice see Cleaning and Maintenance on page 1 1 or replace burner orifice White powder residue forming within burner box or on adjacent walls or...

Страница 16: ...Valve 1 12 80019 Igniter Module 1 ITEM P N PART DESCRIPTION QTY 13 80010 Thermostat Valve Mounting Bracket 1 14 8001 1 Igniter Module Mounting Bracket 1 15 80058 Floor Mounting Feet Beige 1 80214 Floo...

Страница 17: ...Valve 1 12 80019 Igniter Module 1 ITEM P N PART DESCRIPTION QTY 13 80010 Thermostat Valve Mounting Bracket 1 14 8001 1 Igniter Module Mounting Bracket 1 15 80058 Floor Mounting Feet Beige 1 80214 Floo...

Страница 18: ...1 ITEM P N PART DESCRIPTION QTY 14 70640 Thermostat Valve 1 15 80014 Igniter Wire 1 16 80019 Igniter Module 1 17 8001 1 Igniter Module Mounting Bracket 1 18 80010 Thermostat Valve Mounting Bracket 1...

Страница 19: ...1 ITEM P N PART DESCRIPTION QTY 14 70640 Thermostat Valve 1 15 80014 Igniter Wire 1 16 80019 Igniter Module 1 17 8001 1 Igniter Module Mounting Bracket 1 18 80010 Thermostat Valve Mounting Bracket 1...

Страница 20: ...MITED WARRANTY Enerco Group Inc EGI warrants Heatstar Vent free heaters to be free from defects in material and workmanship for a period of five years from the date of manufacture During the first two...

Отзывы: