background image

15

Installation Instructions and Owner’s Manual

Unvented Natural Gas Vent Free Room Heaters

OBSERVED SYMPTOM 

POSSIBLE CAUSE

REMEDY 

Burner does not light after 

ODS/pilot is lit

Burner orifice is clogged

Clean burner orifice (see Cleaning and Maintenance on page 
11), or replace burner orifice

Burner orifice diameter to small

Replace burner orifice

Inlet gas pressure is too low

Contact local gas company

Delayed ignition of burner

Manifold pressure is too low

Contact local gas company

Burner orifice is clogged

Clean burner orifice (see Cleaning and Maintenance on page 
11), or replace burner orifice

Burner backfiring during 

operation

Burner orifice is clogged or damaged

Clean burner orifice (see Cleaning and Maintenance on page 
11), or replace burner orifice

Burner damaged

Replace burner

Gas regulator defective

Replace gas regulator

Burner plaque(s) does not 

glow [Infrared Only]

Plaque damaged

Replace burner

Control knob set between locked 
positions

Turn control knob until it locks at desired setting.

Inlet gas pressure is too low

Replace gas regulator

Slight smoke or odor 
during initial operation

Residues from manufacturing process

Problem will stop after a few hours of operation

Heater produces a 
whistling noise when 
burner is lit

Turning control knob to HI position when 
burner is cold

Turn control knob to LO position and let warm up for a minute

Air in gas line

Operate burner until air is removed from line have gas line 
checked by local gas company

Air passageways on heater blocked

Observe minimum installation clearances (see Figure 4 page 6)

 Dirty or partially clogged burner orifice.

Clean burner orifice (see Cleaning and Maintenance on page 
11), or replace burner orifice

White powder residue 
forming within burner box 
or on adjacent walls or 
furniture

When heated, vapors from furniture 
polish, wax, carpet cleaners, etc., turn 
into white powder residue

Turn heater off when using furniture polish, wax, carpet cleaner  
or similar products

Heater produces unwanted 
odors. 

Heater burning vapors from paint, 
hair spray, glues, etc. See IMPORTANT 
statement on page 14

Ventilate room. Stop using odor-causing products while heater 

is running.

Gas leak. See WARNING statement at top 

of page 14

Locate and correct all leaks (see Checking Gas Connections, 
page 9) 

Heater shuts off in use 

(ODS operates) 

Not enough fresh air is available 

Open window and/or door for ventilation 

Low line pressure 

Contact local gas company

ODS/pilot is partially clogged  

Clean ODS/pilot (see Cleaning and Maintenance, page 11)  

Gas odor even when 

control knob is in OFF 
position 

Gas leak. See WARNING statement at top 

of page 14

Locate and correct all leaks (see Checking Gas Connections, 
page 9) 

Control valve is defective  

Replace control valve  

Gas odor during 

combustion

Foreign matter between control valve 
and burner 

Take apart gas tubing and remove foreign matter 

Gas leak. See WARNING statement at top 

of page 14

Locate and correct all leaks (see Checking Gas Connections, 
page 9) 

Heater produces a clicking/
ticking noise just after 
burner is lit or shut off

Metal expanding while heating or 
contracting while cooling

This is common with most heaters. If noise is excessive, contact  
qualified service person

Moisture/condensation 
noticed on windows

Not enough combustion/ventilation air

Refer to Fresh Air for Combustion and Ventilation page 3 
through 5.

Содержание HSSVFBF20NGBT

Страница 1: ...llation and service must be performed by a qualified installer service agency or the gas supplier This is an unvented gas fired heater It uses air oxygen from the room in which it is installed Provisi...

Страница 2: ...lts should be alerted to the hazard of high surface temperature and should stay away to avoid burns or clothing ignition Young children should be carefully supervised when they are in the same room wi...

Страница 3: ...ximum 14 Inches of Water 14 Inches of Water 14 Inches of Water 14 Inches of Water Inlet Gas Pressure Minimum 7 Inches of Water 7 Inches of Water 7 Inches of Water 7 Inches of Water Electrical Rating B...

Страница 4: ...ose volume is less than 50 cubic feet per 1 000 Btu per hour 4 8 m3 per kW of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is no...

Страница 5: ...space because the actual Btu hr used is more than the maximum Btu hr the space can support You must provide additional fresh air Your options are as follows A Rework worksheet and the space of an adj...

Страница 6: ...ble alternative to test gauge connection Purchase a CSA AGA certified equipment shutoff valve from your dealer LOCATING HEATER This heater is designed to be mounted on the wall The heater can also be...

Страница 7: ...wall stud mounting locate one end of the mounting bracket over a wall stud WARNING Maintain minimum clearances shown in fig ure 7 If you can provide greater clearances from the floor and joining wall...

Страница 8: ...ING AWAY FROM WALL Installing Support Feet See figure 11 1 Lay heater onto table on its back with bottom edge overhanging table edge 2 Securely attach feet to bottom of heater using 2 self tapping scr...

Страница 9: ...ppliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of psi 3 5 kPa 2 Cap off open en...

Страница 10: ...ettle on the floor WHAT TO DO IF YOU SMELL GAS Shut off gas supply Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call you gas s...

Страница 11: ...HEATER 1 Turn off equipment shutoff valve 2 Turn control knob clockwise to the OFF position SHUTTING OFF BURNER ONLY PILOT STAYS LIT 1 Turn control knob clockwise to the PILOT IGN position THERMOSTAT...

Страница 12: ...lean CLEANING BURNER PILOT AIR HOLE INLET We recommend that you clean the unit every 2 500 hours of operation or every three months We also recommend that you keep the burner tube and pilot assembly c...

Страница 13: ...13 Installation Instructions and Owner s Manual Unvented Natural Gas Vent Free Room Heaters PAGE LEFT INTENTIONALLY BLANK...

Страница 14: ...d by any metal or tubing Keep igniter cable dry Broken igniter cable Replace igniter cable Bad Piezo igniter Replace control valve Low Battery Replace battery When igniter button is pressed in there i...

Страница 15: ...irty or partially clogged burner orifice Clean burner orifice see Cleaning and Maintenance on page 1 1 or replace burner orifice White powder residue forming within burner box or on adjacent walls or...

Страница 16: ...Valve 1 12 80019 Igniter Module 1 ITEM P N PART DESCRIPTION QTY 13 80010 Thermostat Valve Mounting Bracket 1 14 8001 1 Igniter Module Mounting Bracket 1 15 80058 Floor Mounting Feet Beige 1 80214 Floo...

Страница 17: ...Valve 1 12 80019 Igniter Module 1 ITEM P N PART DESCRIPTION QTY 13 80010 Thermostat Valve Mounting Bracket 1 14 8001 1 Igniter Module Mounting Bracket 1 15 80058 Floor Mounting Feet Beige 1 80214 Floo...

Страница 18: ...1 ITEM P N PART DESCRIPTION QTY 14 70640 Thermostat Valve 1 15 80014 Igniter Wire 1 16 80019 Igniter Module 1 17 8001 1 Igniter Module Mounting Bracket 1 18 80010 Thermostat Valve Mounting Bracket 1...

Страница 19: ...1 ITEM P N PART DESCRIPTION QTY 14 70640 Thermostat Valve 1 15 80014 Igniter Wire 1 16 80019 Igniter Module 1 17 8001 1 Igniter Module Mounting Bracket 1 18 80010 Thermostat Valve Mounting Bracket 1...

Страница 20: ...MITED WARRANTY Enerco Group Inc EGI warrants Heatstar Vent free heaters to be free from defects in material and workmanship for a period of five years from the date of manufacture During the first two...

Отзывы: