COMMUNICATIONS
HeatNet Control REV 1.38-1
Page 59
Figure 41
MODBUS — BoilerStatus2 Flags
Bit
Description
Valid Values/Range
0
Disabled
0 = enabled, 1 = disabled
1
Heat Demand
0 = no demand, 1 = demand (1)
2
Alarm
0 = ok, 1 = alarm
3
Failed
0 = ok, 1 = failed
4
Member Error
0 = ok, 1 = error
5
Boiler Running
0 = off, 1 = running
6
Pump Running
0 = off, 1 = running
7
Spare 3 Interlock
0 = open, 1 = closed
8
LWCO Interlock
0 = open, 1 = closed
9
VFD Interlock
0 = open, 1 = closed
10
Gas Prove Interlock
0 = open, 1 = closed
11
Spare 4 Interlock
0 = open, 1 = closed
12
Operator Interlock
0 = open, 1 = closed
13
Water Prove (Flow) Interlock
0 = open, 1 = closed
14
UV Sensor Air Prove Interlock
0 = open, 1 = closed
15
Main Valve
0 = closed, 1 = open
This BoilerStatus2 Heat Demand Flag is a combination of the Heat Demand input and the Modbus Heat Demand (40001).
Содержание Smith Series