COMMUNICATIONS
HeatNet Control REV 1.38-1
Page 57
Figure 39
MODBUS Input Variables (Read Only)
Address
Name
Raw Data
Type
Scale
Description
Valid Values/Range
30075
Boiler14RuntimeLow16
30076
Boiler15RuntimeHigh16
30077
Boiler15RuntimeLow16
30078
Boiler16RuntimeHigh16
30079
Boiler16RuntimeLow16
30080
Boiler01Status3
16 bit
unsigned
---
Boiler (1 – 16) stage control input
flags. These bits indicate the state
of the stage control inputs. See
the values column for a list of
conditions.
See the “BoilerStatus3”
Table below.
30081
Boiler02Status3
30082
Boiler03Status3
30083
Boiler04Status3
30084
Boiler05Status3
30085
Boiler06Status3
30086
Boiler07Status3
30087
Boiler08Status3
30088
Boiler09Status3
30089
Boiler10Status3
30090
Boiler11Status3
30091
Boiler12Status3
30092
Boiler13Status3
30093
Boiler14Status3
30094
Boiler15Status3
30095
Boiler16Status3
30096
Boiler01SupplyTemp
16 bit
signed
0.01
Boiler (1 – 16) supply temperature
(if available). See BoilerStatus2 to
determine if the sensor is present.
Boiler01 = Master
Boiler02 = Member01
…
Boiler16 = Member15
32 – 250 °F
30097
Boiler02SupplyTemp
30098
Boiler03SupplyTemp
30099
Boiler04SupplyTemp
30100
Boiler05SupplyTemp
30101
Boiler06SupplyTemp
30102
Boiler07SupplyTemp
30103
Boiler08SupplyTemp
30104
Boiler09SupplyTemp
30105
Boiler10SupplyTemp
30106
Boiler11SupplyTemp
30107
Boiler12SupplyTemp
30108
Boiler13SupplyTemp
30109
Boiler14SupplyTemp
30110
Boiler15SupplyTemp
30111
Boiler16SupplyTemp
30112
Boiler01ReturnTemp
16 bit
signed
0.01
Boiler (1 – 16) return temperature
(if available). See BoilerStatus2 to
determine if the sensor is present.
Boiler01 = Master
Boiler02 = Member01
…
Boiler16 = Member15
32 – 250 °F
30113
Boiler02ReturnTemp
30114
Boiler03ReturnTemp
30115
Boiler04ReturnTemp
30116
Boiler05ReturnTemp
30117
Boiler06ReturnTemp
30118
Boiler07ReturnTemp
30119
Boiler08ReturnTemp
30120
Boiler09ReturnTemp
30121
Boiler10ReturnTemp
30122
Boiler11ReturnTemp
30123
Boiler12ReturnTemp
30124
Boiler13ReturnTemp
30125
Boiler14ReturnTemp
30126
Boiler15ReturnTemp
30127
Boiler16ReturnTemp
30128
Boiler01CyclesHigh16
16 bit
unsigned
---
Boiler (1 – 16) Cycles High
(Upper) and Low (Lower) 16 bit
counters. To get the actual cycle
count for any given boiler (##), the
high and low 16 bit counters must
0 – 4294967295
30129
Boiler01CyclesLow16
30130
Boiler02CyclesHigh16
30131
Boiler02CyclesLow16
30132
Boiler03CyclesHigh16
Содержание Smith Series
Страница 33: ...WIRING CONNECTIONS HeatNet Control REV 1 38 1 Page 33 Wiring Connections Figure 26 Power Connections...
Страница 65: ...OPERATION HeatNet Control REV 1 38 1 Page 65 Smith Series Run Screen...
Страница 68: ...OPERATION HeatNet Control REV 1 38 1 Page 68 Smith Series Menu Tree Version 1 38...
Страница 81: ......
Страница 82: ...Smith 260 North Elm Street Westfield MA 01085...