Description
The UH6 is an 6 Zone wiring centre for use with Heatmiser 230v powered thermostats.
The UH6 can be used to control any actuator or valve which requires a 230v AC signal to open. For mid position valves and those requiring a closing
signal, a changeover relay would be required.
At the same time, the UH6 offers the ability to operate a boiler or other heat source through a volt free output.
A manifold pump output designed for use with underfloor heating systems, is also included as standard.
UH6 – Installation Manual
When zones 1-5 are being used for underfloor heating zones, zone 6
can be used as an isolated radiator zone by using the UFH/RAD switch.
Switch set to RAD;
When zone 6 calls for heat this will provide an output to a radiator
zone valve from the 4 x 230v L & N zone outputs , but WILL NOT
enable the Heat or UFH Pump outputs.
Switch set to UFH;
When Zone 6 calls for heat, this will act as an underfloor heating
zone, by enabling the 4 x actuator, Heat and UFH pump outputs.
Wiring Centre
1