en
34
HeatMaster TC :
664Y6800 • A
EN
FR
NL
ES
IT
DE
PL
RU
TECHNICAL CHARACTERISTICS
DHW PERFORMANCE
Domestic hot water performance* (cold drink water at 10°C)
Operating conditions at 90°C
HM 25 TC
HM 35 TC
HM 45 TC
Constant flow at
40 °C [∆T = 30 K]
L/h
789
1104
1392
45 °C [∆T = 35 K]
L/h
676
946
1207
Peak flow at
40 °C [∆T = 30 K]
L/10’
382
440
498
45 °C [∆T = 35 K]
L/10’
331
370
409
Peak flow 1st hour at
40 °C [∆T = 30 K]
L/60’
1125
1360
1595
45 °C [∆T = 35 K]
L/60’
973
1159
1345
Reheat time from 10°C to 80°C
min.
35
26
23
DHW efficiency at
T = 30 K
%
105.4
105.4
103.1
Domestic hot water performance* (cold drink water at 10°C)
Operating conditions at 90°C
HM 70 TC
HM 85 TC
HM 120 TC
Constant flow at
40 °C [∆T = 30 K]
L/h
2234
2713
3402
45 °C [∆T = 35 K]
L/h
1915
2325
2928
Peak flow at
40 °C [∆T = 30 K]
L/10’
820
868
964
45 °C [∆T = 35 K]
L/10’
668
718
819
Peak flow 1st hour at
40 °C [∆T = 30 K]
L/60’
2761
3076
3706
45 °C [∆T = 35 K]
L/60’
2306
2513
3153
Reheat time from 10°C to 80°C
min.
27
24
23
DHW efficiency at
T = 30 K
%
103.9
103.9
102.2
* for DHW temperatures > 45°C ( T > 35K), please contact ACV
** For special applications, please contact ACV.
MAXIMUM OPERATING CONDITIONS
Maximum Service Pressure [DHW tank full of water]
- Primary circuit : .......................................................................................................................................... 3 bar
- DHW circuit : ........................................................................................................................................... 8,6 bar
- Recommended safety valve (central heating) : .................................................................... 3 bar
- Recommended safety valve (DHW) : .......................................................................................... 7 bar
Mains supply pressure
- Max 6 bar, without a pressure reducing valve being required (to avoid discharge of the safety pressure
valve)
Maximum Operating Conditions
- Maximum temperature (primary) : ................................................................................................ 90°C
- Maximum temperature (DHW) for the HM 25 / 35 / 45 / 70 TC** : ........................... 75°C
- Maximum temperature (DHW) for the HM 85 / 120 TC : ................................................. 90°C
Water Quality
See "Recommendations for the Prevention of Corrosion and Scaling".
Содержание 120 TC
Страница 63: ...en 63 HeatMaster TC 664Y6800 A EN FR NL ES IT DE PL RU DECLARATION OF CONFORMITY EC ...
Страница 64: ...en 64 HeatMaster TC 664Y6800 A EN FR NL ES IT DE PL RU DECLARATION OF CONFORMITY EC ...
Страница 65: ...en 65 HeatMaster TC 664Y6800 A EN FR NL ES IT DE PL RU ...
Страница 66: ...en 66 HeatMaster TC 664Y6800 A EN FR NL ES IT DE PL RU ...
Страница 67: ...en 67 HeatMaster TC 664Y6800 A EN FR NL ES IT DE PL RU ...
Страница 68: ...MARKINGS LABELS en 68 HeatMaster TC 664Y6800 A EN FR NL ES IT DE PL RU ...