Heatit Controls HEATIT Z-TRM3 Скачать руководство пользователя страница 4

14.  CALIBRATION 
(CAr, CAF, CAE – Parameters 10, 11, 12)
Using Floor / External sensor (F, A2 or A2F-mode)

In this mode, you may adjust the displayed temperature. If the 
Temperature sensor is not calibrated properly, you can make minor 
changes to the temperature readout. You can calibrate the measured 
temperature by up to ±4°C.

You may later adjust the temperature recorded by the sensor using in the 
menu structure or using parameters.

SENSOR TYPE

CALIBRATION FROM 
MENU STRUCTURE

PARAMETER

Internal Sensor

CAr

10

Floor Sensor

CAF

11

External Sensor

CAE

12

15.  BRIGHTNESS

Use Left and Right (up and down) buttons to adjust the brightness level 
from 0 to 9. Confirm with the Center (confirm) button.

16.  HYSTERESIS (dIF)

In this mode, you can make changes to the thermostat hysteresis. You 
may change the hysteresis from 0,3°C up to max 3,0°C. Confirm with the 
Center (confirm) button. The Default setting is 0,5°C. When using water 
based heating, the recommended hysteresis is a minimum of 1,0°C.  
This only applies when using a floor sensor or an external sensor.

17.   MIN/MAX TEMPERATURE SETTINGS

Flo

  Min Floor temperature

FHI

  Max Floor temperature

ALo

  Min Air/room temperature 

AHI

  Max Air/room temperature

 

Confirm with Center (confirm)

ESC

  Leaving programming mode.

 

Confirm with the Center (confirm) button.

When using the thermostat is used in (AF or A2F) the floor limiter FHI is 
automatically set to 27°C. When using any other sensor type (A, F or A2F) 
the max temperatures is default 5°C minum and 40°C maximum.

18.  FAST FUNCTIONS FROM STANDBY / MAIN SCREEN

This is a list of some functions that you may use without entering the 
menu structure. From standby modus you may do the following:

18.1 DISPLAY ON/OFF  (don/doF)

Activate by pressing the Left and Center (up and confirm) buttons for
10 seconds. The display light is temporarily activated if one of the 
buttons is pushed.

In case doF is activated, the screen will be blank (may be used if installed 
where people are sensitive to the display light). When touching the 
display, the screen lights up.

18.2 CHILD LOCK (LOC)

By pressing the Left and Right (up and down) buttons for 10 seconds, 
child lock will be activated, and no changes can be made. Trying to 
make changes causes the LOC text to appear on the display. 

Child lock is deactivated by pressing Left and Right (up and down) 
buttons for 10 seconds. OPn will appear on the display.

19.  ERROR CODES

Err

 

Adding fail

 

See Chapter 6.1 ”Add/Remove”.

Er1

  Internal error

 

Contact your local dealer.

Er2

  Z-Wave error

 

Contact your local dealer.

Er3

  Internal error

 

Contact your local dealer.

Er4

  Floor sensor error

 

You have chosen F, AF or A2F sensor mode without having a  

 

floor sensor connected, or the sensor may be damaged.

Er5

  External sensor error

 

You have chosen A2 or A2F, and there are no external   

 

 

sensors installed or the sensor may be damaged.

20.  Z-WAVE QR-CODE / DSK 

The QR-Code is needed when including a device using S2 security or 
SmartStart. The Z-Wave DSK can be found in the QR-Code which is 
located in 3 locations:
1.  On the product box. 
2.  On the physical product, placed on the black plastic underneath 

the front. 

3.  On the PCB internally. 

21.  SECURITY

S2 security enhances Z-Wave Plus with an additional layer of AES 128-bit 
encryption of the wireless Z-Wave communication to prevent hacking 
and man-in-middle attacks on the home network. This device supports 
S2 and has a Z-Wave DSK QR-Code label that may be used when the 
module is added to the Z-Wave home network. The primary controller will 
ask for a 5-digit code, which can be found underneath the QR-Code. The 
primary controller will then ask you to confirm the rest of the code that is 
contained in the QR-Code. 

22.  NODE INFORMATION FRAME

The node information frame is the ”business card” of a Z-Wave device. 
It contains information about the device type and its technical features. 
The add and remove procedure of the device is confirmed by sending 
out a node information frame. Besides this, it may be necessary for certain 
network operations to send out a node information frame.

23.  ASSOCIATIONS

Z-Wave devices interact with other Z-Wave devices. The relationship 
between one device controlling another device is called an association. 
In order to control a subordinate device, the controlling device needs to 
maintain a list of devices that will receive controlling commands. These 
lists are called ”Association Groups”. They are always related to the specific 
event triggered (e.g., sensor reports). In case the event is triggered, all 
devices stored in the respective association group will receive a joint 
wireless command.

SETTING AND REMOVING ASSOCIATIONS

Associations may be assigned and removed via Z-Wave commands.
Please refer to your primary controller/Z-Wave gateway for more 
information.

Содержание HEATIT Z-TRM3

Страница 1: ...etwork to communicate with the other devices within it Devices may also be removed from a network The add remove processes are initiated by the primary controller of the Z Wave network The primary controller has a mode for adding or removing devices Please refer to your primary controller manual on how to set the primary controller in add remove mode The device may only be added or removed from th...

Страница 2: ...ller is in add remove mode When the device is removed from the network it will NOT revert to factory settings There are two ways to add the Heatit Z TRM3 to a Z Wave network 6 1 METHOD 1 STANDARD MANUAL 1 Press Center confirm for 10 seconds The display will show OFF 2 Press Right down 5 times until you see Con on the display 3 Start the add remove device process in your primary controller 4 Start ...

Страница 3: ...cture OFF Turns the thermostat off Sensors CHOICE OF SENSORS F Depending on your choice of sensors the menu will change SEn Select the right Ohm value for your external floor sensor NTC type 10 12 15 22 33 or 47kΩ Default 10kΩ CAE Calibration for external sensor CAF Calibration for floor sensor CAr Calibration for internal sensor br1 The display brightness may be adjusted in this menu Con Activati...

Страница 4: ... pressing Left and Right up and down buttons for 10 seconds OPn will appear on the display 19 ERROR CODES Err Adding fail See Chapter 6 1 Add Remove Er1 Internal error Contact your local dealer Er2 Z Wave error Contact your local dealer Er3 Internal error Contact your local dealer Er4 Floor sensor error You have chosen F AF or A2F sensor mode without having a floor sensor connected or the sensor m...

Страница 5: ...PTION 50 to 400 5 0 C to 40 0 C Default is 50 5 0 C MULTICHANNEL SUPPORT Heatit Z TRM3 has support for the Multichannel Command Class This allows the thermostat to be perceived as many devices by the primary controller where each of the devices has association groups in order to send information to other Z Wave devices See the chapter concerning Association Groups for more information Commands sen...

Страница 6: ...1 Display brightness active state Configure the brightness of the display in active state VALUE DESCRIPTION 0 to 100 0 to 100 Default 100 Parameter 18 Parameter Size 2 Temperature report interval Time interval between consecutive temperature reports Temperature reports can also be sent as a result of polling VALUE DESCRIPTION 30 to 32767 30 seconds to 32767 seconds Default is 60 seconds Parameter ...

Страница 7: ...umulated Watt instant andVolt instant The thermostat will report when asked Rate import Import 0x01 Meter type Electric meter 0x01 Precision 1 decimal 0x01 PRECISION VALUE SCALE SUPPORTED VALUE SIZE 1 decimal 0x01 kWh 0x01 4 2 decimals 0x01 W 0x02 4 1 decimal V 0x04 2 THERMOSTAT DEVICE 1 Supported Command Classes Association version 2 Z Wave Plus Information version 2 Association version 2 Associa...

Страница 8: ...12 15 22 33 and 47 kΩ 25 C IP Code IP 21 Approvals Z Wave Plus CE EN 60730 1 EN 60730 2 9 EMC 2014 30EU RoHS 2011 65 EU LVD 2014 35 EU Approved for use in bathrooms TERMINAL Use 1 5mm or 2 5mm according to load MAINTENANCE The product is maintenance free but must not be covered ART NO PRODUCT COLOR Z WAVE FREQUENCY 54 305 99 Heatit Z TRM3 thermostat 3600W 16A White RAL 9003 EU 868 4MHz 54 305 98 H...

Отзывы: