Heatilator • EL36/EL42 • 4044-132 Rev P • 02/07
24
The last section of pipe
must stop between the
distances given below.
2 in. (51 mm) above top
of the chase.
7 in. (178 mm) below top
of the chase.
{
Top of Pipe
1-1/2 in. (38 mm)
min. overlap
Figure 6.9 Installing a TCT375 Terra Cotta Cap
•
For installations utilizing an TCT375 Terra Cotta Cap the last
chimney section must be between 7 in. (178 mm) below
the chase top and 2 in. (51 mm) above. See Figure 6.9.
•
For chase installations you can use a TR344 Round
Termination Cap, a TR342 Round Telescoping Termination
Cap, an ST375, TS345 or TS345P Square Termination
Cap, or a TCT375 Terra Cotta Termination Cap.
•
For installations utilizing a European Copper Series
Termination Cap, See Figure 6.10.
•
Install termination caps following instructions provided
with them.
chimney top
2 - 6 in.
(51-152 mm)
2 in. (51 mm)
typical
chase
top
(metal or masonry)
Cap Base
(cap inner flue)
SL pipe
inner flue
screw (8)*
bracket (8)
Figure 6.10 Installing a European Copper Series Termination Cap
(CT3-King shown)