Heatilator • EL36/EL42 • 4044-132 Rev P • 02/07
13
3 ft min. from top of
uppermost chimney
section to air inlet.
Attic insulation shield
(not shown) must be
used to keep insulation
away from chimney.
Ceilng firestop
on floor of attic.
Sharp Edges
• Wear protective gloves and safety
glasses during installation.
CAUTION
Outside Air
Shield
Outside Air
Plate
Assembly
2 Wire Ties
Flexible Duct
(not supplied)
Figure 4.1 Installation of Outside Air Kit
Outlet placed
higher than 3 ft
below the
termination cap
Attic space
Garage or
combustible
liquids storage
Outlet blocked by
snow, leaves, etc.
Clear area
outside
house or in
ventilated
crawl space
YES
NO
NO
NO
NO
Use only duct materials specified
by manufacturer (preferably with
short run or mainly straight duct,
except small dip for cold air trap
which will help prevent flow of cold air).
Factory-built
fireplace
Figure 4.3 Outside Combustion Air Placement
4
4
Installation of Fireplace
Figure 4.2 Outside Air Inlet Locations
A. Install the Outside Air Kit
This
fi
replace will operate correctly only if adequate ventila-
tion is provided to allow proper draft to the
fi
replace system.
See Section 2.
The outside air kit is an optional feature with this
fi
replace
and its use is highly recommended to minimize the effects
of negative pressure within the structure. We recommend
you utilize the shortest duct run to optimize the performance
of the outside air kit. Cold air
fl
ow can be minimized by put-
ting a small dip in the duct creating a cold air trap. This trap
can also help prevent heat build-up and exhausting out the
intake due to the stack effect. The outside air kit inlet should
be positioned in a manner that will not allow snow, leaves,
etc. to block the inlet. In some installations the air duct
may need to be run vertically. In such an installation, a 3 ft
(.914 m) height difference must be maintained from the top
of the uppermost chimney section to the outside combustion
air inlet. See Figure 4.2.
See Figure 4.3 for proper placement of outside air inlet.
The outside air kit is installed on the left hand side of the
fi
replace. See Figure 4.4 for handle location/operation.
Fire Risk
Asphyxiation Risk
Do not draw outside combustion air from:
• Wall,
fl
oor or ceiling cavity.
• Enclosed space such as an attic or
garage.
• Close proximity to exhaust vents or
chimneys.
Fumes or odor may result.
WARNING
¨