18
7058-205A
6/16/2014
HEATILATOR ECO-CHOICE
We strongly recommend a minimum of 60
inches (1.5m) vertical, however above the
eve is preferred.
Both installations are approved for mobile home
installations. Must use 3 or 4 inch (76 to 102mm)
“L” or “PL” Listed pellet venting or Listed double
wall pipe and authorized Outside Air Kit in mobile
homes. Single wall pipe is approved for residential
installations only.
Air Clearance to Pipe
:
This appliance was tested with standard 3 inch
(76mm) Listed pellet vent.
Pellet pipe manufactures Listed reduce clearance
pipe may be use for reduce clearance from 3 inch
(76mm) air clearance to no less than 1 inch (25mm)
air clearance to combustibles for approved Listed
pellet pipe.
Follow pipe manufactures listed air clearances to
combustibles and installation instructions for all
reduced air clearances installations.
D. Vertical into Existing Class A Chimney
Firestop
Flashing
Rain Cap
6 in.
(152mm)
Minimum.
Non-combustible Hearth Pad
3 in. (76mm)
Minimum.
Cleanout Cover
12 in. (305mm)
Minimum
Ceiling Support
6 in. (152mm) Flue
Connector
6 in. (152mm) Class A
Chimney Connector
Adapter
3 in. to 6 in.
(76-152mm)
Top Vent Kit
Non-combustible Hearth Pad
Clean-out Cover
Tee
Wall Thimble
Support
Bracket
Every 60 in.
(1.5m)
12 in.
(305mm)
Minimum
Rain Cap
Flashing
2 in. (51mm) Minimum
6 in. (152mm)
Minimum
Figure 18.2
Firestop
Flashing
Rain Cap
6 in.
(152mm)
Min.
Non-combustible Hearth Pad
3 in. (76mm)
Min.
12 in.
(305mm)
Minimum
3 in. to 3 in.
(76-76mm)
Top Vent Kit
Clean-out Cover
Figure 18.1
C. Through The Wall & Vertical - External
B. Vertical - Interior - Typical Installation
PREFERRED METHOD #1
PREFERRED METHOD #2
Figure 18.3
NOTE:
In Canada, where passage through a wall or partition of
combustible construction is desired, the installation shall conform
to CAN/CSA-B365