Heatilator • CRAVE4836-C/ST-C, CRAVE6048-C/ST-C, CRAVE7260-C/ST-C, CRAVE8472-C/ST-C Installation Manual • 2601-980 Rev. N • 11/21
Figure 4.19
Top Vent - Vertical Termination
Venting with 3 elbows
Note
: Use DVP Series
components only.
CRAVE4836-C, CRAVE4836ST-C
CRAVE6048-C, CRAVE6048ST-C
CRAVE7260-C, CRAVE7260ST-C
V
1
+ V
2
Minimum
H
1
+ H
2
Maximum
1-1/2 ft.
457 mm
4 ft.
1.2 m
3 ft.
914 mm
9 ft.
2.7 m
4 ft.
1.2 m
12 ft.
3.7 m
5 ft.
1.5 m
15 ft.
4.6 m
V
1
+ V
2
+ H
1
+ H
2
= 63 ft. (19.2 m) Maximum
H
1
+ H
2
= 23 ft. (7.1 m) Maximum
WARNING! Risk of Fire!
DO NOT attach elbow directly to the appliance.
•
The CRAVE4836-C/CRAVE4836ST-C, CRAVE6048-C/CRAVE6048ST-C and CRAVE7260-C/CRAVE7260ST-C
require a
minimum of 18 inches of vertical venting before attaching any elbow to the appliance.
• The CRAVE8472-C/CRAVE8472ST-C requires a minimum of 30 inches of vertical venting before attaching any elbow to
the appliance.
CRAVE8472-C, CRAVE8472ST-C
V
1
+ V
2
Minimum
H
1 +
H
2
Maximum
2-1/2 ft.
762 mm
4 ft.
1.2 m
4 ft.
1.2 m
9 ft.
2.7 m
5 ft.
1.5 m
12 ft.
3.7 m
6 ft.
1.8 m
15 ft.
4.6 m
V
1
+ V
2
+ H
1
+ H
2
= 63 ft. (19.2 m) Maximum
H
1
+ H
2
= 23 ft. (7.1 m) Maximum
INSTALLED
HORIZONTALLY
H
1
H
2
V
2
v
1
V
1