Heatilator • CRAVE4836-C/ST-C, CRAVE6048-C/ST-C, CRAVE7260-C/ST-C, CRAVE8472-C/ST-C Installation Manual • 2601-980 Rev. N • 11/21
24
SIDE DISCHARGE FRAMING DIMENSIONS
A
B
C
D
E
F
Height of
Discharge
Opening
Width of
discharge
Opening
Minimum
Clearance
Bottom of
Appliance
to Bottom of
Discharge
Opening
Minimum
Clearance
Bottom of
Appliance
to Ceiling
Minimum
Clearance to
Combustible
Materials
Minimum
Clearance
Appliance
Opening to
Ceiling
CRAVE4836-C
CRAVE4836ST-C
Inches
12-1/4
8-3/4
62-3/4
76-1/2
18
52
millimeters
311
222
1594
1943
457
1321
CRAVE6048-C
CRAVE6048ST-C
Inches
12-1/4
8-3/4
62-3/4
76-1/2
18
52
millimeters
311
222
1594
1943
457
1321
CRAVE7260-C
CRAVE7260ST-C
Inches
12-1/4
8-3/4
62-3/4
76-1/2
18
52
millimeters
311
222
1594
1943
457
1321
CRAVE8472-C
CRAVE8472ST-C
Inches
12-1/4
8-3/4
81-1/4
95
18
70-1/2
millimeters
311
222
2064
2413
457
1791
Figure 3.14 Passive Heat Side Discharge Framing Dimensions
Framing Dimensions - Passive Heat Side Discharge (PH-SIDE) Single-Sided or See-Through
WARNING! Risk of Fire!
DO NOT place
combustible objects or combustible materials
in non-combustible zone. Appliance and
combustible materials will overheat.
ROOM CEILING
1-1/2 IN. (2 X 4 FRAMING)
= PASSIVE HEAT
DISCHARGE OPENING
DISCHARGE OPENING
CHASE CEILING ZONE
CHASE CEILING (REQUIRED)
Side Discharge: Air conveyed into the room through two discharge registers,
one on each side of appliance.
E
B
A
C
D
E = NON-COMBUSTIBLE ZONE
(BOTH SIDES)
APPLIANCE MAY BE INSTALLED
OFF OF FLOOR
F