Heatilator  •  ADI-ZC-FB  •  2032-900  Rev. E  •  8/05

9

3

Installing the Insert

Step 1.   Installing the Vent System

Vent System Installation Precautions

Before starting installation of vent kits, the installer should
read these instructions and the Vent Kit Instructions to
ensure that a proper vent installation is completed.

Consult your local building codes before beginning the
installation.

WARNING: THIS GAS INSERT AND VENT AS-
SEMBLY MUST BE VENTED DIRECTLY TO THE

OUTSIDE AND MUST NEVER BE ATTACHED TO A
CHIMNEY SERVING A SEPARATE SOLID FUEL
BURNING APPLIANCE. EACH GAS APPLIANCE
MUST USE A SEPARATE VENT SYSTEM. COMMON
VENT SYSTEMS ARE PROHIBITED.

Fireplace ADI-ZC-FB is approved with vent termination kits
LINK-DV-30, LINK-DV-30B, LINK-DV4-30 and LINK-DV4-30B
as shown in Figures 3 & 4. Approved vent system termina-
tions are labeled for identification. 3-inch diameter listed
flexible aluminum and stainless steel gas vent is used for
both the incoming combustion air and exhaust vent pipes.
NO OTHER VENTING SYSTEMS OR COMPONENTS MAY
BE USED. Detailed installation instructions are included
with each vent termination kit and should be used in con-
junction with this manual.

Horizontal Venting

The vent system on this model CANNOT be terminated
horizontally.

Vertical Venting

The vent pipes 

MUST

 be connected to the proper collars

on the unit 

AND

 the exhaust vent pipe 

MUST

 be connected

to the termination cap or the unit will not operate. The com-
bustion air vent pipe CAN be connected to the termination
cap (LINK -DV30, LINK -DV30B) or it can terminate inside
the chimney (LINK-DV4-30, LINK-DV4-30B). The bottom
opening of the chimney must be sealed around the vent
pipes if the combustion air vent is NOT connected to the
termination cap. See Figure 3.

NOTE:

 The minimum vertical rise (exhaust vent) is 14 feet

and the maximum vertical rise is 50 feet. These dimensions
are measured from the starting collars of the unit to the end
of the last section of vent pipe. See dimension V in Figure 3.

Vent System Approvals

!

A vertical vent termination system installed on this model
will require one (1) length of 3” stainless steel liner, one (1)
length of 3-inch flexible vent pipe for the combustion air,
one (1) length of 3-inch flexible vent pipe for the exhaust air
and one (1) Termination Cap.

!

NOTE:

The damper of the existing chimney may need to be

removed to allow installation of the flexible-vent pipe.

WARNING: THIS FIREPLACE HAS BEEN
CONVERTED FOR USE WITH A GAS

FIREPLACE INSERT ONLY AND CANNOT BE USED
FOR BURNING WOOD OR SOLID FUELS UNLESS
ALL ORIGINAL PARTS HAVE BEEN REPLACED,
AND THE FIREPLACE REAPPROVED BY THE
AUTHORITY HAVING JURISDICTION.

NOTE:

 The above label, located in the instruction package,

must be affixed to the existing fireplace prior to installation.

For zero clearance factory built woodburning fireplaces, the
use of kit LINK-ZC-ADP in place of the standard square
flashing will allow you to mount the adaptor and cap on
class “A” metal pipe.

Connecting the Vent Pipe

Install the 3” flexible vent pipe(s) down through the chimney.
Secure the end of the flexible vent pipe for exhaust to the
provided 3’ section of stainless steel flexible vent pipe. A 3”
collar is factory installed on one end for mating the two
ends of flexible pipe.

WARNING: THE 3’ SECTION OF STAINLESS
STEEL FLEXIBLE PIPE MUST BE ATTACHED DI-

RECTLY TO THE EXHAUST COLLAR OF THE UNIT.

Attach either 4’ or 30’ section of intake liner to the intake
collar on the collar slide-plate using 3 screws. This assembly
may be removed from the unit to aid installation. Slide insert
into position, while pulling intake collar assembly towards
the front of the unit. Slide the gas insert into place, and
position any excess flexible vent pipe back up into the
chimney. Secure the assembly in place using one screw to
the center bracket (see Figure 4).

!

Содержание ADI-ZC-FB

Страница 1: ...H APPLIANCE FOR FUTURE REFERENCE 1 This appliance may be installed in an af termarket permanentlylocated manufac tured mobile home wherenotprohibited by local codes 2 This appliance is only for use wi...

Страница 2: ...ce front READ and UNDERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warran...

Страница 3: ...System 9 Step 2 Positioning Leveling and Securing the Insert 13 Step 3 The Gas Control Systems 13 Step 4 The Gas Supply Line 13 Step 5 Gas Pressure Requirements 14 Step 6 Wiring the Appliance 14 Wiri...

Страница 4: ...ed in accordance with local codes or in the absence of local codes with the National Electric Code ANSI NFPA No 70 in the United States or to the CSAC22 1 Canadian Electric Code in Canada These models...

Страница 5: ...EXTEN SION IF PRESENT MUST COMPLY WITH EI THER OF THE FOLLOWING 1 THE SOLID FUEL BURNING FIREPLACE MANUFACTURER S SPECIFICATION OR 2 LOCAL BUILDING CODES REQUIRED BY AUTHORITY HAVING JURISDICTION WAR...

Страница 6: ...R EXHAUST STARTING COLLAR ON OFF SWITCH OPTIONAL 3 SIDED ADI ZC FB MINIMUM FIREPLACE SIZE LOCATION Inches Millimeters A Front Width 30 7 8 784 B Rear Width 25 5 8 651 C Depth 15 381 Height 19 1 2 495...

Страница 7: ...the maximum vertical rise is 50 feet These dimensions are measured from the starting collars of the unit to the end of the last section of vent pipe See dimension V in Figure 3 Vent System Approvals...

Страница 8: ...E THE ROOF TOP THESE MINIMUM HEIGHTS ARENECESSARYINTHEINTEREST OF SAFETY SEE THE FOLLOWING DIAGRAM FOR MINIMUM HEIGHTS PROVIDED THE TERMINATION CAP IS AT LEAST 2 FEET FROM A VER TICAL WALL AND 2 FEET...

Страница 9: ...THE INLET AIR COLLAR OF THE UNIT AND EITHER ATTACHED TO THE INLETAIRCOLLAROFTHETERMINATIONCAP OR TERMINATED IN THE CHIMNEY This option shows both exhaust and inlet air vent pipes attached to the adapt...

Страница 10: ...KING HANDLE SLIDING PLATE STAINLESS STEEL ADAPTER FOR EXHAUST MUST BE INSTALLED INLET AIR VENT PIPE 3 INCH COLLAR OPTIONAL LINK ZC ADPB For Flashing Class A Pipe TERMINATION CAP SQUARE FLASHING REMOVE...

Страница 11: ...building codes to properly size the gas supply line leading to the 1 2 inch 13 mm hook up at the unit This gas fireplace is designed to accept a 1 2 inch 13 mm gas supply line To install the gas supp...

Страница 12: ...ECT REMOTE CONTROLS IF AB SENT FOR EXTENDED TIME PERIODS THIS WILL PRE VENT ACCIDENTAL APPLIANCE OPERATION For Standing Pilot Ignition Wiring Appliance Requirements This appliance DOES NOT require 110...

Страница 13: ...glass doors JUNCTION BOX VARIABLE SPEED CONTROL TEMPERATURE SENSOR SWITCH WHT GRN BLK BLK 110 120 VAC BLOWER BLOWER RECEPTACLE BLK BLK BLK BLK WHT GROUND WHT BLK BLK BLK REMOTE RECEPTACLE SPEED CONTRO...

Страница 14: ...oles in burner top see Figure 12 Space dime size ember pieces about a 1 2 inch apart Never press embers into burner ports DO NOT cover burner ports Place dime size pieces around front and sides of bur...

Страница 15: ...ew minutes for the lines to purge themselves of this air Once the purging is complete the appliance will light and will operate normally Subsequent lightings of the fireplace will not require this pur...

Страница 16: ...ILOT position turn the control knob counter clockwise to the PILOT position 6 To light the pilot press the control knob and then press the red or black piezo button once every second The piezo makes a...

Страница 17: ...vacuum the control compartment fireplace logs and burner areas surrounding the logs Checking Flame Patterns Flame Height Frequency Periodically By Qualified service technician Home owner Task Make a...

Страница 18: ...copper lead Start the pilot and hold the valve knob in If the millivolt reading is less than 15mV replace the thermocouple b Defective valve If the thermocouple is producing more than 15 millivolts re...

Страница 19: ...necessary e Improper vent cap installation Check for proper installation and freedom from debris or blockage 6 Glass soots a Flame impingement Adjust the log set so that the flame does not excessivel...

Страница 20: ...itions inadequate ventilation or drafting caused by tight sealing construction of the structure air handling devices such as exhaust fans or forced air furnaces or other causes 5 use of fuels other th...

Отзывы: