SAF-T WRAP INSULATION:

Saf-T Wrap is available in tee sections and 24” lengths,
therefore two lengths will be required for each 4’ section of
Sat-T Liner.  Saf-T Wrap must cover the Saf-T liner from the
appliance tee or the top of the smoke chamber area to within
8” but not closer than 4” of the top of the masonry chimney.
See Fig. 19 for a topview.

FIG.19

FIG.18

COVER PLATE:

Saf-T Liner  black Cover Plate provides a decorative finish to the
installation of a side wall masonry chimney.   See Fig. 18.

OPENING OF THE CHIMNEY
NOTE: Wear eye protection and dust respirator.

An opening for the liner system will have to be made for any existing masonry chimney without an opening.  If there is an
opening, it may need to be expanded in order to insert the tee take off into the removable tee or accommodate the support
system chosen.

To make the initial opening into the masonry chimney, select a brick that is at the level you want the stove pipe to enter the wall
(at least 18” from unprotected combustibles unless a listed wall penetration assembly or other approved method is used).  The
wall penetration assembly must be above the appliance.  Drill a series of holes in the mortar around the perimeter of the brick

1/4” 8lbs density

refractory ceramic

fiber

Aluminum

Jacket

STORM COLLAR:

A Storm Collar is required at the top of the masonry chimney to
support the liner in conjunction with the Top Plate. Install the
Storm Collar directly below the expanded portion of the Saf-T
Liner section by tightening the clamp screw.  The Storm Collar
will then rest on the Top Plate.  See Figs. 17 and 24.

FIG.17

Содержание Saf-T Liner

Страница 1: ...on instructions Saf T Liner has been tested and listed using all the supports sections etc described herein Deletion or modification of any of the required parts or materials may seriously impair the...

Страница 2: ...he roof of a building and not less than 2 feet above any portion of the building within ten feet see Fig 1 Materials 024 304 Stainless Steel 024 316L Stainless Steel Includes 1 8 Stainless Steel Blind...

Страница 3: ...2 and Figure 2 Saf T Wrap is available for tee sections and in 24 lengths Saf T Wrap must cover the Saf T Liner from the appliance tee or the top of the smoke chamber area to within 8 but not closer...

Страница 4: ...A B Always wear eye protection and heavy gloves throughout installation Wear eye protection and dust respirator whenever in contact with creosote soot mortar or insulation Before the installation of t...

Страница 5: ...assembly will be supported from the top of the chimney The installer must verify that there is at least 1 inch clearance to combustibles outside a 3 nominal layer of masonry as well as 1 inch clearan...

Страница 6: ...horizontal run FIXED LENGTHS Saf T Liner is available in 12 18 24 36 and 48 fixed Lengths To determine the length and number of liner sections required complete the following Calculate the number of...

Страница 7: ...ze can have a negative impact of chimney performance and safety Use these components only when appropriate See Fig 13 RAIN CAP Saf T Liner Rain Cap is made of stainless steel and required to cap the l...

Страница 8: ...it may need to be expanded in order to insert the tee take off into the removable tee or accommodate the support system chosen To make the initial opening into the masonry chimney select a brick that...

Страница 9: ...ON CAUTION must be used when working on a roof Proper and safe scaffolding should be used for a safe installation of the Saf T Liner Always use a respirator and eye protection when using Saf T Wrap MA...

Страница 10: ...p Plate supporting the upper sections of the liner system Slide the Rain Cap into the female portion of the Saf T Liner section and secure with the four self drilling screws provided See Figs 5 and 25...

Страница 11: ...is not used the single wall connector pipe must be at least 18 from combustible construction material Clearances from the solid fuel burning appliances to combustible materials must be strictly adhere...

Страница 12: ...y walls and cause cracking buckling distortion and or burnout in chimney liners A chimney liner damaged in such a way as to permit leakage of flue gases should be repaired or replaced Since there is a...

Страница 13: ...workmanship For products installed after January 1 2009 for a period of Ten 10 years from original installation we will provide replacement product with a similar or like quality of available Selkirk...

Отзывы: