CHIMNEY MAINTENANCE INSTRUCTIONS:

Formation of creosote and soot and the subsequent need for removal occurs when solid fuel is burned slowly, producing tar and
other organic vapors, which combine with expelled moisture to form creosote.  The creosote vapors condense in the cooler flue
of a slow burning fire.  As a result, creosote residue accumulates on the flue lining.  When ignited, this can result in an
extremely hot and possibly damaging chimney fire.

The chimney connector and Saf-T Liner should be inspected frequently during the heating season and cleaned annually (more
often if necessary) by a professional, certified chimney sweep.

The chimney should be inspected at least every 6 to 8 weeks during the heating season and once prior to the season to
determine if (1) a creosote or soot buildup has occurred or (2) if some other mechanism has caused a failure of the liner
system.  To inspect and/or clean the chimney, loosen the four Tek screws and remove the rain cap.  If creosote or soot has
accumulated, have the chimney professionally cleaned to reduce the risk of a chimney fire.

Properly installed and well maintained stovepipes and chimneys can usually withstand an occasional moderate chimney fire,
but the intentional setting of a chimney fire to “burnout” the creosote should be avoided.  This is a dangerous method to clean
a chimney and can cause severe damage to chimneys, liners and possible damage to the structure of the house.

After any chimney fire always have the chimney system inspected by a knowledgeable and certified professional before any
further use.  The excessive heat during a chimney fire can crack chimney walls, and cause cracking, buckling, distortion and/
or burnout in chimney liners.  A chimney liner damaged in such a way as to permit leakage of flue gases should be repaired or
replaced.  Since there is a greater likelihood that a subsequent chimney fire could spread beyond the confines of the damaged
flue to the house itself.  If no such damage is visible, the chimney system installed per these instructions is  suited for further
use subject to the inspection schedule outlined above.

PI-LINER R0301 - 02/19/16

HOMEOWNER

KEEP FOR YOUR RECORDS

Year 1 Maintenance
Done by_____________
Date________________

Year 2 Maintenance
Done by_____________
Date________________

Year 3 Maintenance
Done by_____________
Date________________

Year 4 Maintenance
Done by_____________
Date________________

Year 5 Maintenance
Done by_____________
Date________________

Year 6 Maintenance
Done by_____________
Date________________

Year 7 Maintenance
Done by_____________
Date________________

Year 8 Maintenance
Done by_____________
Date________________

Year 9 Maintenance
Done by_____________
Date________________

Year 10 Maintenance
Done by_____________
Date________________

Name ____________________________________________________________________________
Address __________________________________________________________________________
City, State, Zip _____________________________________________________________________

Installing Company _________________________________________________________________
Address __________________________________________________________________________
Phone (    ) ________________________________________________________________________

Date of Installation __________________________________________________________________
Installed by ________________________________________________________________________

Содержание Saf-T Liner

Страница 1: ...on instructions Saf T Liner has been tested and listed using all the supports sections etc described herein Deletion or modification of any of the required parts or materials may seriously impair the...

Страница 2: ...he roof of a building and not less than 2 feet above any portion of the building within ten feet see Fig 1 Materials 024 304 Stainless Steel 024 316L Stainless Steel Includes 1 8 Stainless Steel Blind...

Страница 3: ...2 and Figure 2 Saf T Wrap is available for tee sections and in 24 lengths Saf T Wrap must cover the Saf T Liner from the appliance tee or the top of the smoke chamber area to within 8 but not closer...

Страница 4: ...A B Always wear eye protection and heavy gloves throughout installation Wear eye protection and dust respirator whenever in contact with creosote soot mortar or insulation Before the installation of t...

Страница 5: ...assembly will be supported from the top of the chimney The installer must verify that there is at least 1 inch clearance to combustibles outside a 3 nominal layer of masonry as well as 1 inch clearan...

Страница 6: ...horizontal run FIXED LENGTHS Saf T Liner is available in 12 18 24 36 and 48 fixed Lengths To determine the length and number of liner sections required complete the following Calculate the number of...

Страница 7: ...ze can have a negative impact of chimney performance and safety Use these components only when appropriate See Fig 13 RAIN CAP Saf T Liner Rain Cap is made of stainless steel and required to cap the l...

Страница 8: ...it may need to be expanded in order to insert the tee take off into the removable tee or accommodate the support system chosen To make the initial opening into the masonry chimney select a brick that...

Страница 9: ...ON CAUTION must be used when working on a roof Proper and safe scaffolding should be used for a safe installation of the Saf T Liner Always use a respirator and eye protection when using Saf T Wrap MA...

Страница 10: ...p Plate supporting the upper sections of the liner system Slide the Rain Cap into the female portion of the Saf T Liner section and secure with the four self drilling screws provided See Figs 5 and 25...

Страница 11: ...is not used the single wall connector pipe must be at least 18 from combustible construction material Clearances from the solid fuel burning appliances to combustible materials must be strictly adhere...

Страница 12: ...y walls and cause cracking buckling distortion and or burnout in chimney liners A chimney liner damaged in such a way as to permit leakage of flue gases should be repaired or replaced Since there is a...

Страница 13: ...workmanship For products installed after January 1 2009 for a period of Ten 10 years from original installation we will provide replacement product with a similar or like quality of available Selkirk...

Отзывы: