background image

 

  

 

 

 

World Leaders in Ultra-Pure Heating 

Revision 10

 

 

www.heateflex.com

 

01/17/13 

405 E. Santa Clara St. 
Arcadia, CA 91006-7218  
Tel: (626) 599-8566 Fax: (626) 599-9567 

At this point the manual inlet/outlet valves can be reopened and D.I. water flushed through the 
unit until the effluent water quality meets the user‟s qualification specifications.  Note that 
there is also a zero dead leg valve on the right side of the unit, which can be used to direct the 
water passing through the unit to drain rather than through the normal outlet of the unit. 
 

__________________________________________________________ 
6.2  Initial Heat-Up 

 
Before introducing steam and heating up the unit, make sure that the unit will always "see" a 
minimum of 20 psig in D.I. water supply line pressure at all flows which are to be used.  This 
requirement is based on two factors.  First, since the shellside pressure in the exchanger is 
approximately 15 psig there would never be reverse flow of "dirty" or contaminated steam into 
the process if a tube in the exchanger develops a leak.  Second, since the temperature of the 
water in the exchanger can reach 120°C the D.I. water will begin to boil if a minimum D.I. 
water pressure of 15 psig is not present.  This means any throttling valves to control flow 
through the unit should be downstream of the unit rather than upstream.  The maximum D.I. 
water pressure should be limited to 60 psig which is based on the working pressure rating of 
the PVDF piping. 
 
Please note that a loss of D.I. water supply line pressure will not harm the unit in any way, and 
in fact, the unit can be run dry with no effect.  For example, if a unit is to be taken out of 
service for time, the process side of the unit can be "drained and dried" by simply draining the 
external piping and boiling out all of the water in the exchanger.  This can be followed by a 
CDA or nitrogen purge.  The CDA or nitrogen will also be heated as it passes through the 
exchanger to evaporate the last residual water left in the external piping.  Also, note that the 
Auto-Isolation System will attempt to close the isolation valves when the D.I. water pressure 
falls below the Low Process Pressure alarm set point, so the isolation valves will have to be set 
to “Flow” or opened manually. 
 
Once the unit is fully facilitated as described in the previous section, return the pneumatic 
isolation valves and the cold bypass valve to their normal, non-energized position, closed for 
the isolation valves and open for the cold bypass valve.  Again, check that the manual isolation 
valves on the heads are fully open, and that the manual inlet/outlet valves are fully open.  The 
manual outlet valve can be throttled down to minimize the flow of D.I. water through the unit, 
or alternatively the outlet valve can be closed and the zero-dead leg valve on the right side of 
the unit can be opened if flow is to be directed to other than the process distribution piping at 
this time. 
 
Check the pressure gauge on the small air regulator on the inside of the electrical enclosure to 
see that there is a minimum of 60 psig and adjust as necessary to a range of 60 to 70 psig.  This 
air is used to activate the pneumatic valves on the unit. 
 
At this point remember that almost any unplanned event during the next steps can be 
immediately remedied by depressing the EMO switch, which will close the pneumatic steam  

Содержание FLUIDIX

Страница 1: ...orld Leaders in Ultra Pure Heating Revision 10 www heateflex com 01 17 13 405 E Santa Clara St Arcadia CA 91006 7218 Tel 626 599 8566 Fax 626 599 9567 FLUIDIX SERIES Ultra Pure D I WATER HEATING SYSTE...

Страница 2: ...World Leaders in Ultra Pure Heating Revision 10 www heateflex com 01 17 13 405 E Santa Clara St Arcadia CA 91006 7218 Tel 626 599 8566 Fax 626 599 9567...

Страница 3: ...Safety Systems Preventive Maintenance and Servicing Installation and Start up Procedures Servicing Policies Section II APPENDIX Touch Screen Displays External Flow Sensors Temperature Dead Band Signa...

Страница 4: ...perature Trending 3 2 5 Alarm Menu and Alarm Screens 3 2 6 Date and Time Set Up 3 2 7 Alarm History 3 3 The Remote Control Panel 3 4 Input Output Functions 4 0 Safety Systems 4 1 Overview 4 2 Shellsid...

Страница 5: ...Adjusting Temperature Control Parameters 7 0 Servicing Policies 7 1 Self Service 7 2 Factory Service 7 3 Warranty Section II 8 0 Appendix 8 1 Important Touch Screen Notes 8 2 Touch Screen Displays 8 2...

Страница 6: ...stic Information S Water Leak Alarm T Water Leak Diagnostic Information 8 2 7 Alarm History 8 2 8 External Flow Sensor 8 3 Pressure Relief Valve Calibration Procedure 8 4 Quality Control Documentation...

Страница 7: ...World Leaders in Ultra Pure Heating Revision 10 www heateflex com 01 17 13 405 E Santa Clara St Arcadia CA 91006 7218 Tel 626 599 8566 Fax 626 599 9567 Section I Instruction Manual...

Страница 8: ...World Leaders in Ultra Pure Heating Revision 10 www heateflex com 01 17 13 405 E Santa Clara St Arcadia CA 91006 7218 Tel 626 599 8566 Fax 626 599 9567...

Страница 9: ...vailable to others who may later need to refer to it Another feature of this manual is the sections dealing with servicing We realize that the competitive business in which this equipment will be used...

Страница 10: ...bundle wound helically around a central support which is mounted to the exchanger cover Removal of this exchanger cover gives complete access to the Fluidix tube bundle for inspection of all its comp...

Страница 11: ...endent of the most extreme variations in D I water flow rate D I water is heated in the Fluidix PFA heat exchanger to above the set point temperature and is continuously blended in varying ratios with...

Страница 12: ..._______________________________________________ 2 4 Ancillary Systems The PC series D I water heating systems are offered with two optional systems the Auto Isolation System and the Auto Shutdown Syst...

Страница 13: ...on from set point for the process temperature as with conventional temperature control systems Additionally the PLC has a trimmer function which is based on the temperature sensor at the outlet of the...

Страница 14: ...N MENU would return the display to the main menu and pressing the box labeled OPEN would open the steam valve on the unit The ability to operate or change any settings to the unit via the touch screen...

Страница 15: ...re D I Flow Rate D I Process Pressure and Actuator Position The current status of the Auto Shutdown System Auto Isolation System Pressure Relief Venting Systems and the Vessel Flooding system are also...

Страница 16: ...FLOW RATE column in the Look Up Table Enter this value for the Look Up Table under FLOW RATE by pressing the box in the first row Next open an outlet valve until the flow rate is at the increment ent...

Страница 17: ...resume normal operation To manually reset the alarm press the ALARM RESET button located on the System Status screen or the Alarm Menu screen Other alarms automatically reset see Section 4 7 Summary...

Страница 18: ...in the order that they appear The log will roll out older alarm log entries once the maximum allowed number of entries is achieved The box located at the left of each entry designates the status of th...

Страница 19: ...matically opens so that there is always a flow of water to the tools hot or cold The Auto Shutdown will also initiate causing the steam inlet valve to also shut down when the Auto Isolation is initiat...

Страница 20: ...faces on the equipment Only voltages of 24 volts or less are supplied to components outside of the electrical enclosure on the unit and the highest voltage within the electrical enclosure is 120 VAC A...

Страница 21: ...initiation on the System Status screen of the main or remote panels or loss of power at the main unit the Auto Shutdown System will also be initiated When an Auto Shutdown occurs the pneumatic ball va...

Страница 22: ...between the exchanger outlets and the hot mixing valve located on the right side of the main control panel The balance of the piping is exposed to temperatures at or below the system set point temper...

Страница 23: ...exchanger tubing and the associated thermal expansion The pressure relief valves will vent momentarily to prevent a build up of pressure due to this thermal expansion ________________________________...

Страница 24: ...point There is a default alarm delay of 20 seconds when this alarm is triggered In addition this alarm condition needs to be reset manually by pressing the ALARM RESET button The factory flow rate ala...

Страница 25: ..._____________ 4 4 1 Loss of D I Water Line Pressure Auto Isolation When there is a loss of D I line pressure the pressure of the steam outside the exchanger tubing could force dirty steam or contamina...

Страница 26: ...user s steam trap or condensate removal system fails the vessel will also begin to flood with condensate This will also cause the float switch to trip which will activate the Vessel Flooding alarm Au...

Страница 27: ...ure condition if set to AUTO mode There is an alarm delay on specific alarm types detailed above The delay time for the Low Process Temperature Process Over Temperature and Low Process Pressure alarms...

Страница 28: ...ving is provided for by the user Also please note that D I water leaks downstream of the unit will not be affected by this action as the unit is fitted with an automatic bypass valve which is fail saf...

Страница 29: ...ird TC for the hot valve D I input temperature and a fourth TC for measuring the steam temperature within the exchanger vessel Generally a thermocouple s accuracy does not degrade over time and replac...

Страница 30: ...line pressure and to check against the value displayed on the touch screen monitor __________________________________________________________ 5 1 4 Flow Sensor The D I water flow rate is measured by...

Страница 31: ...r same to see if the pressure goes down If so there is a leak in one of the individual tubes in the exchanger If a tube leak is suspected close the manual isolation valves standard configuration on th...

Страница 32: ...if the silicone disks or PFA caps are not available the stainless fittings can be removed and replaced by a 1 4 pipe plug or a short piece of 1 4 PFA tubing can be used to connect the two open fitting...

Страница 33: ...be obtained from the factory already pre cut Wrap the seal around the tube in a helical fashion with the adhesive side towards the tubing as also shown in the next figure push the nut down over the se...

Страница 34: ...ply A dedicated regulator for each unit is recommended if other steam powered equipment up stream of the unit may cause variations in the steam pressure supplied to the unit as this will affect the pr...

Страница 35: ...can be run dry with no effect For example if a unit is to be taken out of service for time the process side of the unit can be drained and dried by simply draining the external piping and boiling out...

Страница 36: ...ton to clear the alarm conditions The next step is to enter the operational password on the Main Menu screen touching the area above the PRESS FOR SYSTEM STATUS button or to the left of the DATE label...

Страница 37: ...g The facility steam regulator if steam is being throttled down from a higher pressure steam system should be adjusted at this point to read right at 15 psig on the pressure gauge on the exchanger ves...

Страница 38: ...coverage for factory servicing __________________________________________________________ 7 2 Factory Servicing The equipment is covered by a warranty as outlined below Any claims for warranty coverag...

Страница 39: ...re processed on the condition that prompt notification of a defect is given within the warranty period Heateflex Corporation shall have the sole right to determine whether in fact a warranty situation...

Страница 40: ...y to perform and meet the specifications of the purchase order the unit shows a design deficiency which inhibits its ability to perform to specification and where said deficiency or said inhibition is...

Отзывы: