34
Alarm Codes
Alarm Codes
• *BOXHI : Box temperature too high
• *BOXLO : Box temperature too low
• *STRUP :System Start-up failure
Compressor pumps down and tries
to restart after 4 minutes.
• *INFLT : Input fault (Box Temp.,
Suction Temp., Pressure Transducer
open or not installed)
• Power failure
When an ALARM condition occurs, the
BEACON II SMART CONTROLLER will
display “CALL FOR SERVICE”, the ALARM
code, the System Number, and Unit Number,
and will sound an internal buzzer.
The alarm code will flash alternately with the
normal display information. When the alarm
condition is corrected, the alarm code will
no longer be displayed and only the normal
information will be displayed.
The system will pumpdown and cycle off and
will not restart until the fault is cleared for the
following conditions:
• Suction sensor shorted, open or
not installed
• Room temperature sensor shorted,
open or not installed
• Pressure Transducer open or
not installed
The system will pumpdown, cycle off and try to
restart for three consecutive times. Each try will
be after the 4 minutes “Hold Off” period, for the
following fault conditions.
• Oil pressure
• High pressure or low pressure cutout
After the fourth try, the Alarm contacts will be
closed and an alarm message displayed on the
LCD screen. To clear this condition, the system
should be cycled through the “Service” mode
after correction is complete.
On Multiple systems the Alarm contacts on each
of the Master Evaporator will announce Alarms
for that system.
ALARM BUZZER
The ALARM buzzer will sound when an Alarm
condition occurs. This buzzer will turn off when
the Alarm condition is cleared. The buzzer can
also be silenced at any time by pressing the
“CLEAR” button.