33
Locking Beacon II Smart Controller
LOCKING BEACON II SMART
CONTROLLER
BEACON II SMART CONTROLLER is
lockable to prevent programmed settings to be
changed by unauthorized personnel. When the
Controller is Locked, all the Buttons, except
for the MONITOR, CLEAR, and PROG
REVIEW buttons, are disabled.
To LOCK the settings, do the following:
• Press “PROG REVIEW” button.
• Press and hold “MONITOR” button
• While holding “MONITOR” button,
Press “ENTER” button.
• The LCD will display LOCK
This will prevent unauthorized persons from
changing any settings.
To UNLOCK the Controller, repeat these steps.
ERROR CODES
• BXSEN - Room temperature sensor
shorted, open or not installed
• DFSEN - Defrost temperature
sensor shorted, open or not installed
• STSEN - Suction Temperature
sensor shorted, open or not installed
• SPSEN - Suction pressure
transducer shorted, open or not installed
• ODSEN - Outdoor temperature
sensor shorted
• SUPLO - Superheat too low
• SHTDN - Compressor shutdown
(High or low refrigerant pressure or
low oil pressure)
The error code will flash alternately with the
normal display information. When the error
condition is corrected, the error code will
no longer be displayed and only the normal
information will be displayed.
WIRING ERROR
If the Beacon II Smart Controller LCD displays
+COMM+ , this indicates that there is an error in
the communication wiring or that the wiring is
broken, disconnected, shorted, or there is power
loss to one of the boards.
The communication wiring is the MULTI IN and
MULTI OUT connections. Check to make sure
the OUT is connected to IN. Never connect OUT
to OUT or IN to IN.