Code +050004036 Rel. 1.0 – 11/03/2008
18
5 – List of alarm codes
Code
Description
Display icon
Alarm relay
Buzzer
Reset
Before any intervention, always check the wiring.
rE
Controller virtual probe damaged or disconnected
Flashing
On On
Automatic
E0
Ambient probe S1 damaged or disconnected
Flashing
Off Off
Automatic
E1
Defrost probe S2 damaged or disconnected
Flashing
Off Off
Automatic
E2
Probe S3 damaged or disconnected
Flashing
Off Off
Automatic
E3
Probe S4 damaged or disconnected
Flashing
Off Off
Automatic
E4
Probe S5 damaged or disconnected
Flashing
Off Off
Automatic
‘---‘
Probe not validated
None
Off
Off
Automatic
LO
Low temperature alarm
Flashing
On On
Automatic
HI
High temperature alarm
Flashing
On On
Automatic
AFr
Anti-frost alarm
Flashing
On On
Manual
IA
Instantaneous alarm with external contact
Flashing
On On
Automatic
dA
Delayed alarm with external contact
Flashing
On On
Automatic
dEF
Defrost in progress
On
Off Off
Automatic
Ed1
Defrost on evaporator 1 finished with time
None
Off
Off
Automatic/manual
Ed2
Defrost on evaporator 2 finished with time
None
Off
Off
Automatic/manual
Pd
Maximum pump-down time alarm
Flashing
On On
Automatic/manual
LP
Low-pressure alarm
Flashing
On On
Automatic/manual
AtS
Pump-down automatic start up
Flashing
On On
Automatic/manual
cht
Condenser high temperature pre-warning
None
Off
Off
Automatic/manual
CHT
Condenser high temperature alarm
Flashing
On On
Manual
dor
Door open too long alarm
Flashing
On On
Automatic
Etc
Internal clock defective
Flashing
Off Off
Automatic
EE
Machine parameters Eprom error
Flashing
Off Off
Automatic
EF
Operating parameters Eprom error
Flashing
Off Off
Automatic
HA
HACCP alarm type HA
Flashing
Off Off
Automatic
HF
HACCP alarm type HF
Flashing
Off Off
Automatic
rCt
Controller validated for remote programming
None
Off
Off
Automatic
Add
Automatic address attribution procedure in progress
None
Off
Off
Automatic
Prt
Report print-out in progress
None
Off
Off
Automatic
ccb
Start continuous cycle request
Indication
ccE
End continuous cycle request
Indication
dFb
Start defrost request
Indication
dFE
Stop defrost request
Indication
On
On Indication
Off
Off Indication
rES
Reset manual-reset alarms; reset HACCP
alarms; reset temperature monitoring
Indication
n1 - n6
Indicates an alarm on units 1-6 present in the system
Flashing
On
On
Automatic
dnL
Download in progress
Indication
d1 - d6
Download errors on units 1-6