Code +050004036 Rel. 1.0 – 11/03/2008
10
d: Defrost parameters
Display
Parameter and description
Measurement
unit
Min
Max
Bn
1
Bn
2
Bn
3
Bn
4
Bn
5
Bn
6
d0
Type of defrost
0=defrost with elec. element ends with
temperature or time
1=defrost with hot gas ends with temperature or
time
2=defrost with elec. element ends with time
3=defrost with hot gas ends with time
4= defrost with elec. element ends with time or
temperature (if defrost ends with time ED1 and ED2
are not displayed)
Select
0 4 2 0 0 2 0 0
dI
Interval between 2 defrosts
Time
0 250 8 8 6 12 8 6
dt1
Temperature at end of evaporator defrost
°C/°F
-50
200 4 4 4 4 4 4
dt2
Temperature at end of aux. evaporator defrost
°C/°F
-50
200 4 4 4 4 4 4
dP1
Maximum evaporator defrost duration
Min
1 250 45 45 30 45 45 30
dP2
Maximum aux. evaporator defrost duration
Min
1 250 45 45 30 45 45 30
d3
Delayed defrost activation
Min
0 250 0 0 0 0 0 0
d4
Defrost when the controller is switched on
0=no
1=yes
Select
0 1 0 0 0 0 0 0
d5
Delay defrost when the controller is switched on
Min
0 250 120 240 240 120 240 240
d6
Block display during defrost
0=alternating display of temperature and DEF
1=display temperature present before defrost
2=always display DEF
-
0 2 2 2 2 2 2 2
dd
Dripping duration after defrost
Min
0 15 0 4 4 0 4 4
d8
High-temperature alarm (AH) exclusion duration
after defrost and/or door open
Time
0 15 1 1 1 1 1 1
d8d
Alarm timer after door opening (alarm “dor”)
Min
0 250 2 2 2 2 2 2
d9
Priority defrost for delayed compressor
start/stop
0=respected
1=not respected (priority defrost)
Select
0 1 0 0 0 0 0 0
d/1
Read defrost probe 1
°C/°F
- - - - - - - -
d/2
Read defrost probe 2
°C/°F
- - - - - - - -
dC
Defrost duration time base
0=hours/minutes
1=Minutes/seconds
Select
0 1 0 0 0 0 0 0
d10
Smart defrost: Compressor running time with an
evaporator temperature below D11 to start
defrost
0=function disabled
>0 =running time
dC
0 250 0 0 0 0 0 0
d11
Temperature threshold for smart defrost
°C/°F
-20
20 1 1 1 1 1 1
d12
Auto-adaptive advanced defrost
0=skip defrost disconnected, automatic variation
disconnected
1=skip defrost disconnected, automatic variation
connected
2= skip defrost connected, automatic variation
disconnected
3= skip defrost connected, automatic variation
connected
-
0 3 0 0 0 0 0 0
dn
Average defrost duration in percentage in
relation to dt1 or dt2
-
1 100 65 65 65 65 65 65
dH
Proportional variation factor of dI
-
0 100 50 50 50 50 50 50