15
Programming & Reviewing
Locking The Beacon II Board
The Beacon II board is lockable to prevent programmed
setting changes by unauthorized personnel. When
locked, the program setpoints cannot be changed.
To
lock
the setting:
•
Press “
PROGRAM REVIEW
” button.
•
Press and
hold
“
MONITOR
” button.
•
While holding
“
MONITOR
” button,
press “
ENTER
” button.
•
The LCD will display
Loc
.
This will prevent unauthorized personnel program
changes. To
unlock
, repeat steps above. LCD will
display “
UnL
”.
• OFF
Box Temp
/ oFF
Box Temperature/ Mode is displayed
All Evaporators
• COOLING
Single Evaporator- Box Temp
/Coo
Box Temperature/ Mode is displayed
Multiple Evaporators
Master Evap
-
Box Temp
/ Coo
Box Temperature/ Mode is displayed
Slave Evaps -
Coo
Operating Mode is displayed
• Pumpdown
All Evaporators
Pdn
• DEFROST
All Evaporators
dEF
• TEST
All Evaporators
tSt
• SERVICE
All Evaporators
SEr
• ALARMS
A 1
High Box Temp
A 2
Low Box temp
A 3
System Start-up
failure
Compressor pumps down and tries
to restart after 4 minutes.
A 4
Input Fault
Box Temp., Suction Temp., Pressure
Transducer open or not installed
STATUS INDICATOR LED
A RED, three-digit , alphanumeric LED on the
Beacon II board indicates status, alarms and
error codes.
Programming And Reviewing
Settings/Changes (Cont’d.)
Use this button to
“CLEAR/TEST”
Pressing this button ONCE
will return the LED display to
the default display. With the system in the
OFF
mode,
pressing and holding this button will start the
“TEST”
mode. In the “
TEST”
mode it will cycle through each
output for 10 seconds. The display will only show “tst”
during “
TEST
” mode. Test mode will automatically
terminate after 3 sequences.
Содержание BEACON II H-IM-79E
Страница 2: ...2 2007 Heatcraft Refrigeration Products LLC ...
Страница 28: ...28 Wiring ...
Страница 29: ...29 Wiring ...
Страница 30: ...30 Wiring ...
Страница 31: ...31 Wiring ...
Страница 32: ...32 Wiring ...
Страница 33: ...33 Wiring ...